# 2025-18393: New Rules Ensure Power Plants Survive Deep Freezes Without Fail

2025-18393, Before Commissioners: David Rosner, Chairman; Lindsay S. See and Judy W. Chang; North American Electric Reliability Corporation: Order Approving Extreme Cold Weather Reliability Standard EOP-012-3 and Directing Data Collection, is a Federal Register notice from Energy Department, Federal Energy Regulatory Commission published 2025-09-23, effective 2025-10-01; PRIA reads it as touching household money (as of 2026-06-08).

- Canonical: https://policyrisk.com/federal-register/2025-18393
- As of: 2026-06-08
- Plain-text twin of the page above; the HTML and this file carry the same facts.

## Facts
- Document number: 2025-18393
- Title: Before Commissioners: David Rosner, Chairman; Lindsay S. See and Judy W. Chang; North American Electric Reliability Corporation: Order Approving Extreme Cold Weather Reliability Standard EOP-012-3 and Directing Data Collection
- Type: Notice
- Agencies: Energy Department; Federal Energy Regulatory Commission
- Citation: 90 FR 45761
- Published: 2025-09-23
- Effective: 2025-10-01
- Comments close: not stated
- Significant: no
- Touches household money: yes
- Regulation identifier numbers: none
- Last updated: 2026-06-08

## In one line

New Rules Ensure Power Plants Survive Deep Freezes Without Fail

## Summary

The Federal Energy Regulatory Commission just approved a new cold weather rule, EOP-012-3, to help power plants get ready for freezing weather and keep the lights on during big winter storms. This update replaces the old rule and requires better preparation and data collection from power companies across North America. The changes kick in soon and aim to prevent costly blackouts when the cold hits hard.

## Effects PRIA read

- New Cold-Weather Rule Starts Oct 1, 2025: benefit, high. The Federal Energy Regulatory Commission approved Reliability Standard EOP-012-3 to take effect October 1, 2025. The Commission says the standard improves generator cold-weather preparedness to help keep the lights on during extreme winter storms.
- New Timelines for Fixing Freeze Issues: cost, medium. Generator owners must follow new corrective-action timelines under EOP-012-3: implementing new freeze-protection measures within 48 months and remedying issues with existing measures within 24 months. For fleet reviews, corrective actions must be implemented within 24 months of review or no later t…
- New Units Must Meet Cold Standard by 2027: cost, medium. Generating units that begin commercial operation on or after October 1, 2027 must be capable of operating at the Standard's Extreme Cold Weather Temperature without using a corrective action plan. New units cannot rely on a corrective-action workaround to meet cold-weather capability if they enter…
- NERC Must Report Biennial Constraint Data: benefit, low. The Commission directed NERC to submit anonymized, regional data biennially starting by October 2026 and ending October 2034 on: (1) number of submitted Generator Cold Weather Constraint declarations, (2) number approved, (3) aggregate MVA of approved declarations, and (4) summaries of rationales.…
- Estimated Compliance Reporting Burden: cost, low. The Commission estimates EOP-012-3 affects 1,314 U.S. generator owners. The order estimates an added burden of 1 response per entity at 4 hours each (total 5,256 hours) and an estimated cost of $333,861.12 for those hours.
- Specific Wind-Turbine Low-Temp Limitation: mixed, medium. Attachment 1 to the Standard identifies low-temperature operability of wind turbine towers manufactured before October 1, 2029 and that entered commercial operation before October 1, 2031 as a known Generator Cold Weather Constraint. The Standard says this limitation should not serve as the basis f…

## Related documents

- [2026-22879](https://policyrisk.com/federal-register/2026-22879): Combined Notice of Filings #1, 2026-11-10
- [2026-22878](https://policyrisk.com/federal-register/2026-22878): ConocoPhillips Company; Notice of Institution of Section 206 Proceeding and Refund Effective Date, 2026-11-10
- [2026-22877](https://policyrisk.com/federal-register/2026-22877): Combined Notice of Filings, 2026-11-10
- [2026-22803](https://policyrisk.com/federal-register/2026-22803): Northern Illinois Hydropower, LLC; Notice of Request for Extension of Time To Commence and Complete Construction Accepted for Filing, Solic…, 2026-11-09
- [2026-22791](https://policyrisk.com/federal-register/2026-22791): Combined Notice of Filings, 2026-11-09
- [2026-22721](https://policyrisk.com/federal-register/2026-22721): Transcontinental Gas Pipe Line Company, LLC; Notice of Schedule for the Preparation of an Environmental Assessment for the Leidy Access Exp…, 2026-11-06

## Sources
- [2025-18393 on federalregister.gov](https://www.federalregister.gov/documents/2025/09/23/2025-18393/before-commissioners-david-rosner-chairman-lindsay-s-see-and-judy-w-chang-north-american-electric)
- [2025-18393 as published (PDF)](https://www.govinfo.gov/content/pkg/FR-2025-09-23/pdf/2025-18393.pdf)

## Related
- [Previous: 2025-18392, Texas Eastern Transmission, LP; Notice of Scoping Period Requesting Comments on…](https://policyrisk.com/federal-register/2025-18392)
- [Next: 2025-18397, Agency Information Collection Activities: Proposed Collection: Public Comment R…](https://policyrisk.com/federal-register/2025-18397)
- [All Federal Register documents](https://policyrisk.com/federal-register)

Source: PRIA, https://policyrisk.com/federal-register/2025-18393 (as of 2026-06-08).