Grounding of Frames, Casings, and Other Electrical Equipment

Ala. Code § 25-9-172 — under Title 25.

Ala. Code § 25-9-172

Where grounding wires are used to ground metallic sheaths, armors, conduits, frames, casings and other metallic enclosures, such grounding wires must comply with the following conditions:

(1) The cross-sectional area (size) of the grounding wire shall be at least one-half the cross-sectional area (size) of the power conductor where the power conductor used is No. 6 A.W.G. or larger.

(2) Where the power conductor used is less than No. 6 A.W.G., the cross-sectional area (size) of the grounding wire shall be equal to the cross-sectional area (size) of the power conductor.

History: (Acts 1949, No. 207, p. 242, §41; Acts 1975, 4th Ex. Sess., No. 147, p. 2866, §1.)