815 sections in this chapter.
R.296-307-296-307-40033 Tank car unloading points and operations.
1.5K chars
(1) Provisions for unloading tank cars must meet DOT requirements.(2) Unloading operations must be performed by reliable employees who are properly instructed and responsible for careful compliance with all procedures.(3) Caution signs must be placed on the track or car to give n…
R.296-307-296-307-40035 Liquid-level gauging device.
1.7K chars
(1) Each container except those filled by weight must have an approved liquid-level gauging device.(2) All gauging devices must be arranged so that the maximum liquid level to which the container is filled is easily determined.(3) Gauging devices that require bleeding of the prod…
R.296-307-296-307-40037 Maintenance of aboveground uninsulated containers.
0.5K chars
Aboveground uninsulated containers should have a reflective surface maintained in good condition. We recommend white for painted surfaces, but other light reflecting colors are acceptable.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 2…
R.296-307-296-307-40039 Electrical equipment and wiring.
0.8K chars
(1) Electrical equipment and wiring for use in ammonia installations must be general purpose or weather resistant as appropriate.(2) Where concentrations of ammonia in the air in excess of 16% by volume are likely to be encountered, electrical equipment and wiring must be specifi…
R.296-307-296-307-410 Storage and handling of liquefied petroleum gases.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-410, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-410, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-41001 Scope.
0.9K chars
Chapter 296-307 WAC Part U2 covers the storage and handling of liquefied petroleum gases.The requirements of WAC 296-307-410 apply to all LP-gas installations covered by this part.For additional requirements related to:See WAC:Cylinder systems 296-307-415Systems using non-DOT con…
R.296-307-296-307-41003 LP-gas installations not covered by this part.
1.3K chars
(1) This part does not apply to:(a) LP-gas refrigerated storage systems;(b) LP-gas used with oxygen;(c) LP-gas used in utility gas plants (covered by the National Fire Protection Association Standard for the Storage and Handling of Liquefied Petroleum Gases at Utility Gas Plants,…
R.296-307-296-307-41005 Definitions that apply to this part.
1.5K chars
Adequate ventilation (for fire prevention during normal operation). The concentration of the gas in a gas-air mixture does not exceed 25% of the lower flammable limit.Containers. All vessels, such as tanks, cylinders, or drums, used to transport or store LP-gases.DOT. The federal…
R.296-307-296-307-41007 Odorizing LP-gas.
1.0K chars
The employer must ensure that all LP-gas is odorized by an approved agent to indicate by distinct odor, the presence of gas down to concentration in air of a maximum of 1/5 the lower limit of flammability.Exception:Odorization is not required if it will create a hazard in further…
R.296-307-296-307-41009 Approval of LP-gas containers and equipment.
1.3K chars
(1) Each system of DOT containers must have approved container valves, connectors, manifold valve assemblies, and regulators.(2) Each non-DOT system using containers of 2,000 gallons or less water capacity, must have a container assembly, one or more regulators, and other necessa…
R.296-307-296-307-41011 Construction and test requirements for containers.
1.4K chars
(1) Containers must be designed, constructed, and tested according to the Rules for Construction of Unfired Pressure Vessels, section VIII, Division 1, American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, 1968 edition, unless otherwise specified.(2) Co…
R.296-307-296-307-41013 Welding containers.
0.9K chars
(1) The employer must ensure that all welding to the shell, head, or any other part of the container subject to internal pressure, meets the requirements of the code under which the tank was fabricated. The employer may weld on saddle plates, lugs, or brackets attached to the con…
R.296-307-296-307-41015 Marking containers.
2.1K chars
(1) The employer must ensure that containers are marked according to DOT regulations or with the following:(a) Indication that the container meets the requirements of the code under which it is constructed, and all marks required by that code.(b) Indication whether the container …
R.296-307-296-307-41017 Container locations.
3.8K chars
The employer must ensure that containers are located according to the following:(1) Containers and first stage regulating equipment are located outdoors.Containers may be located indoors under any of the following conditions:(a) In buildings used exclusively for container chargin…
R.296-307-296-307-41019 Valves and accessories.
2.4K chars
(1) Valves, fittings, and accessories connected directly to the container including primary shut-off valves, must have a rated working pressure of at least 250 psig and must be of material and design suitable for LP-gas service. The use of cast iron for container valves, fittings…
R.296-307-296-307-41021 Piping, tubing, and fittings.
6.7K chars
(1) Pipe must be wrought iron or steel (black or galvanized), brass, copper, or aluminum alloy. Aluminum alloy pipe must be at least Schedule 40 according to the specifications for Aluminum Alloy Pipe, ANSI H38.7-1969 (ASTM, B241-1969), and must be suitably marked at each end of …
R.296-307-296-307-41023 Specifications for hoses.
2.5K chars
(1) Hose must be fabricated of materials that are resistant to the action of LP-gas in the liquid and vapor phases. If wire braid is used for reinforcing the hose, it must be of corrosion-resistant material such as stainless steel.(2) Hose subject to container pressure must be ma…
R.296-307-296-307-41025 Safety devices.
7.9K chars
(1) Every container except those constructed according to DOT specifications and every vaporizer (except motor fuel vaporizers and vaporizers described in WAC 296-307-41029(3) and 296-307-42007 (6)(a) whether heated by artificial means or not, must have one or more safety-relief …
R.296-307-296-307-41027 Construction and installation of indirect fired vaporizers.
3.7K chars
Indirect fired vaporizers utilizing steam, water, or other heating medium must be constructed and installed according to the following:(1) Vaporizers must be constructed according to the requirements of WAC 296-307-41011 and must be permanently marked as follows:(a) With the code…
R.296-307-296-307-41029 Construction and installation of atmospheric vaporizers.
0.8K chars
Atmospheric vaporizers using heat from the ground or surrounding air must be installed as follows:(1) Buried underground; or(2) Located inside the building near where the pipe enters the building, if the capacity of the unit does not exceed one quart;(3) Vaporizers of less than o…
R.296-307-296-307-41031 Construction and installation of direct gas-fired vaporizers.
4.2K chars
Direct gas-fired vaporizers must be constructed, marked, and installed as follows:(1) According to the requirements of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code, 1968, that apply to the maximum working conditions for which the vaporizer is desig…
R.296-307-296-307-41033 Construction and installation of direct gas-fired tank heaters.
2.1K chars
Direct gas-fired tank heaters must be constructed and installed as follows:(1) Direct gas-fired tank heaters, and tanks to which they are applied, must only be installed aboveground.(2) Tank heaters must be permanently marked with the name of the manufacturer, the rated Btu input…
R.296-307-296-307-41035 Construction and installation of dehydrators.
2.4K chars
The vaporizer section of vaporizer-burners used for dehydrators or dryers must be located outdoors; they must be constructed and installed as follows:(1) Vaporizer-burners must have a minimum design pressure of 250 psig with a factor safety of five.(2) Manually operated positive …
R.296-307-296-307-41037 Maximum filling densities.
1.4K chars
(1)Filling density. The percent ratio of the weight of the gas in a container to the weight of water the container will hold at 60°F. All containers must be filled according to the filling densities shown in Table U-4.TABLE U-4MAXIMUM PERMITTED FILLING DENSITY Aboveground contain…
R.296-307-296-307-41039 LP-gas in buildings.
3.8K chars
(1) Vapor may be piped into buildings at pressures over 20 psig only if the buildings or separate areas thereof:(a) Are constructed according to this section;(b) Are used exclusively to house equipment for vaporization, pressure reduction, gas mixing, gas manufacturing, or distri…
R.296-307-296-307-41041 Transferring of liquids.
4.0K chars
When transferring liquids, the employer must ensure that:(1) At least one attendant remains close to the transfer connection from the time the connections are first made until they are finally disconnected, during the transfer of the product.(2) Containers must be filled or used …
R.296-307-296-307-41043 Training for workers.
0.5K chars
Workers performing installation, removal, operation, and maintenance work must be properly trained in that function.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-41043, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodif…
R.296-307-296-307-41045 Fire protection for LP-gas installations.
1.3K chars
(1) Open flames or other sources of ignition are prohibited in vaporizer rooms (except those housing direct-fired vaporizers), pumphouses, container charging rooms or other similar locations. Direct-fired vaporizers are prohibited in pumphouses or container charging rooms.Note:LP…
R.296-307-296-307-41047 Electrical requirements that apply to LP-gas installations.
5.4K chars
(1) Electrical equipment and wiring must be specified by and installed according to chapter 296-307 WAC Part T, for ordinary locations.(2) Fixed electrical equipment and wiring installed within classified areas must comply with Table U-5 and must be installed according to chapter…
R.296-307-296-307-41049 Liquid-level gauging devices.
6.8K chars
(1) Each container manufactured after December 31, 1965, and filled on a volumetric basis must have a fixed liquid-level gauge to indicate the maximum permitted filling level according to subsection (5) of this section. Each container manufactured after December 31, 1969, must ha…
R.296-307-296-307-41051 Requirements that apply to appliances.
1.6K chars
(1) New commercial and industrial gas consuming appliances must be approved.Exception:Any appliance that was originally manufactured for operation with a gaseous fuel other than LP-gas and is in good condition may be used with LP-gas only after it is properly converted, adapted, …
R.296-307-296-307-415 Cylinder systems.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-415, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-415, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-41501 Scope.
0.7K chars
WAC 296-307-415 applies to systems using DOT containers. Cylinder systems must meet all requirements of WAC 296-307-410 (unless otherwise indicated) and the additional requirements of this section.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21…
R.296-307-296-307-41503 Cylinder system.
0.5K chars
Cylinder system. Includes the container base or bracket, containers, container valves, connectors, manifold valve assembly, regulators, and relief valves.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-41503, filed 10/20/20, effe…
R.296-307-296-307-41505 Marking containers used in cylinder systems.
0.9K chars
(1) Containers must be marked according to DOT regulations. Additional markings that do not conflict with DOT regulations may be used.(2) Each container must be marked with its water capacity in pounds or other identified unit of weight.(3) Exception: If the employer is the only …
R.296-307-296-307-41507 Additional requirements that apply to cylinder systems installed outdoors.
1.5K chars
(1) Containers must not be buried below ground. However, systems may be installed in a compartment or recess below grade level, such as a niche in a slope or terrace wall that is used for no other purpose, if the container and regulating equipment are not in contact with the grou…
R.296-307-296-307-41509 Additional requirements that apply to cylinder system installed indoors.
8.1K chars
(1) When portable containers are necessary and it is not practical to use them outdoors, containers and equipment may be used indoors only if they meet the requirements of this section.(a) Containers in use. Connected for use.(b) Systems using containers with a water capacity gre…
R.296-307-296-307-41511 Valves and accessories.
1.8K chars
(1) Valves in the assembly of multiple container systems must be arranged so that containers can be replaced without shutting off the flow of gas in the system.Note:An automatic changeover device is not required.(2) Regulators and low-pressure relief devices must be rigidly attac…
R.296-307-296-307-41513 Safety devices for cylinder systems.
1.6K chars
(1) Containers must have safety devices as required by DOT regulations.(2) A final stage regulator of an LP-gas system (excluding any appliance regulator) must have, on the low-pressure side, a relief valve that is set to start to discharge within the limits specified in Table U-…
R.296-307-296-307-41515 Other requirements that apply to cylinder systems.
0.6K chars
(1) Containers must not be reinstalled unless they are requalified according to DOT regulations.(2) A product must not be placed in a container marked with a service pressure less than four-fifths of the maximum vapor pressure of product at 130°F.[Statutory Authority: RCW 49.17.0…
R.296-307-296-307-420 Systems using non-DOT containers.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-420, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-420, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-42001 Scope.
0.7K chars
WAC 296-307-420 applies to systems using storage containers not constructed according to DOT specifications. Non-DOT containers must meet all requirements of WAC 296-307-410 (unless otherwise indicated) and the additional requirements of this section.[Statutory Authority: RCW 49.…
R.296-307-296-307-42003 Design and classification of non-DOT containers.
1.6K chars
Storage containers must be designed and classified according to Table U-8.TABLE U-8 Minimum design pressures of container lb. per sp. in. gaugeContainertypeFor gaseswith vaporpress. Notto exceed lb.per sp. in.gauge 100°F(37.8°C.)1949 andearliereditions ofASME Code(Par. U-68,U-69)…
R.296-307-296-307-42005 Valves and accessories, filler pipes, and discharge pipes for non-DOT containers.
3.3K chars
(1) The filling pipe inlet terminal must not be located inside a building. For containers with a water capacity of 125 gallons or more, such terminals must be located at least 10 feet from any building, and preferably at least 5 feet from any driveway, and must have a protective …
R.296-307-296-307-42007 Additional requirements that apply to safety devices for non-DOT containers.
5.9K chars
(1) All safety devices must comply with the following:(a) All container safety-relief devices must be located on the containers.(b) In industrial and gas manufacturing plants, discharge pipe from safety-relief valves on pipe lines within a building must discharge upward and be pi…
R.296-307-296-307-42009 Reinstallation of non-DOT containers.
0.7K chars
Containers may be reinstalled if they are free from harmful external corrosion or other damage. Where containers are reinstalled underground, the corrosion resistant coating must be put in good condition. Where containers are reinstalled aboveground, the safety devices and gaugin…
R.296-307-296-307-42011 Maximum capacity for non-DOT containers.
0.4K chars
A non-DOT storage container must have a maximum 90,000 gallons water capacity.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-42011, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodified as § 296-307-42011, filed 4/7/97, …
R.296-307-296-307-42013 Installing non-DOT containers.
5.8K chars
(1) Containers installed aboveground must have substantial masonry or noncombustible structural supports on firm masonry foundation, unless otherwise indicated.(2) Aboveground containers must be supported as follows:(a) Horizontal containers must be mounted on saddles that permit…
R.296-307-296-307-42015 Protecting non-DOT containers.
1.2K chars
(1) Valves, regulating, gauging, and other container accessory equipment must be protected against tampering and physical damage. Such accessories must also be protected during the transit of containers intended for installation underground.(2) On underground or combination above…
R.296-307-296-307-42017 Non-DOT containers in industrial plants.
1.3K chars
General provisions applicable to systems in industrial plants (of 2,000 gallons water capacity and more) and to bulk filling plants.(1) When standard watch service is provided, it must be extended to the LP-gas installation and personnel must be properly trained.(2) If loading an…