332 sections in this chapter.
51-11C-51-11C-40322 Section C403.2.2—Ventilation and exhaust.
3.2K chars
C403.2.2 Ventilation and exhaust.C403.2.2.1 Ventilation. Ventilation, either natural or mechanical, shall be provided in accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation is provided, the system shall be configured to provide no greater …
51-11C-51-11C-40323 Section C403.2.3—Fault detection and diagnostics.
1.6K chars
C403.2.3 Fault detection and diagnostics. New buildings with an HVAC system serving a gross conditioned floor area of 100,000 square feet (9290 m2) or larger shall include a fault detection and diagnostics (FDD) system to monitor the HVAC system's performance and automatically id…
51-11C-51-11C-40324 Section C403.2.4—Variable flow capacity.
1.9K chars
C403.2.4 Variable flow capacity. For fan and pump motors 5.0 hp and greater including motors in or serving custom and packaged air handlers serving variable air volume fan systems, constant volume fans, heating and cooling hydronic pumping systems, pool and service water pumping …
51-11C-51-11C-40325 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40325, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40325, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40326 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40326, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40326, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40327 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40327, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40327, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40328 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40328, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40328, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40329 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40329, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40329, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40330 Section C403.3—Equipment selection.
0.8K chars
C403.3 Equipment selection. Heating and cooling equipment installed in mechanical systems shall be sized in accordance with Section C403.3.1 and shall not be less efficient in the use of energy than as specified in Section C403.3.2.[Statutory Authority: RCW 19.27A.020, 19.27A.025…
51-11C-51-11C-40331 Section C403.3.1—Equipment and system sizing.
1.4K chars
C403.3.1 Equipment and system sizing. The output capacity of heating and cooling equipment shall be not greater than that of the smallest available equipment size that exceeds the loads calculated in accordance with Section C403.1.2. A single piece of equipment providing both hea…
51-11C-51-11C-40332 Section C403.3.2—HVAC equipment performance requirements.
6.9K chars
C403.3.2 HVAC equipment performance requirements. Equipment shall meet the minimum efficiency requirements of Tables C403.3.2(1) through C403.3.2(16) when tested and rated in accordance with the applicable test procedure. Plate-type liquid-to-liquid heat exchangers shall meet the…
51-11C-51-11C-403321 Table C403.3.2(1)—Electrically operated unitary air conditioners and condensing units.
4.2K chars
Table C403.3.2(1)Minimum Efficiency Requirements—Electrically Operated Unitary Air Conditioners and Condensing Unitsc,dEquipment TypeSize CategoryHeating Section TypeSubcategory or Rating ConditionMinimum EfficiencyTest ProcedureaAir conditioners, air cooled< 65,000 Btu/hbAllSpli…
51-11C-51-11C-403322 Table C403.3.2(2)—Electrically operated air-cooled unitary heat pumps—Minimum efficiency requirements.
3.4K chars
Table C403.3.2(2)Electrically Operated Air-Cooled Unitary Heat Pumps—Minimum Efficiency RequirementsEquipment TypeSize CategoryHeating Section TypeSubcategory or Rating ConditionMinimum EfficiencyTest ProcedureaAir cooled (cooling mode) < 65,000 Btu/hAllSplit System, three phase …
51-11C-51-11C-403323 Table C403.3.2(3)—Water chilling packages—Minimum efficiency requirements.
3.1K chars
Table C403.3.2(3)Water Chilling Packages—Minimum Efficiency Requirementsa,b,e,f Size Category Path APath BTest ProcedurecEquipment TypeUnitsFLIPLV.IPFLIPLV.IPAir-cooled chillers< 150 tonsEER(Btu/Wh)≥ 10.100≥ 13.700≥ 9.700≥ 15.800 ≥ 150 tonsEER(Btu/Wh)≥ 10.100≥ 14.000≥ 9.700≥ 16.1…
51-11C-51-11C-403324 Table C403.3.2(4)—Minimum efficiency requirements—Electrically operated PTAC, PTHP, SPVAC, SPVHP, room air conditioners.
4.7K chars
Table C403.3.2(4)Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners and Room Air-Conditioner Heat Pumps—Minimum Efficiency RequirementseEquipme…
51-11C-51-11C-403325 Table C403.3.2(5)—Minimum efficiency requirements—Warm air furnaces and unit heaters.
3.1K chars
Table C403.3.2(5)Warm Air Furnaces and Combination Warm Air Furnaces/Air-Conditioning Units, Warm Air Duct Furnaces and Unit Heaters—Minimum Efficiency RequirementsEquipment TypeSize Category (Input)Subcategory or Rating ConditionMinimum Efficiencyd,cTest ProcedureaWarm-air furna…
51-11C-51-11C-403326 Table C403.3.2(6)—Minimum efficiency requirements—Gas-fired and oil-fired boilers.
2.5K chars
Table C403.3.2(6)Gas- and Oil-Fired Boilers—Minimum Efficiency RequirementsEquipment TypeaSubcategory or Rating ConditionSize Category (Input)Minimum EfficiencyTest ProcedureaBoilers, hot waterGas-fired< 300,000 Btu/hg,h for applications outsidethe U.S.82% AFUEDOE 10 C.F.R. 430 A…
51-11C-51-11C-403327 Table C403.3.2(7)—Heat rejection equipment—Minimum efficiency requirements.
4.7K chars
Table C403.3.2(7)Heat Rejection Equipment—Minimum Efficiency RequirementsiEquipment TypeaTotal System Heat Rejection Capacity at Rated ConditionsSubcategory or Rating ConditionhPerformanceRequiredb,c,d,f,gTest Procedurea,ePropeller or axial fan open-circuit cooling towersAll95°F …
51-11C-51-11C-403328 Table C403.3.2(8)—Electrically operated variable refrigerant flow air conditioners—Minimum efficiency requirements.
1.2K chars
Table C403.3.2(8)Electrically Operated Variable Refrigerant Flow Air Conditioners—Minimum Efficiency RequirementsbEquipment TypeSize CategoryHeating Section TypeSubcategory or Rating ConditionMinimum EfficiencyTest Procedurea < 65,000 Btu/hAllVRF Multi-Split System13.0 SEER VRF A…
51-11C-51-11C-403329 Tables C403.3.2(9) through C403.3.2(16)—HVAC equipment minimum efficiency requirements.
17.1K chars
Table C403.3.2(9)Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps—Minimum Efficiency RequirementsbEquipment TypeSize CategoryHeating Section TypeSubcategory or Rating ConditionMinimum EfficiencyTest Procedurea < 65,000 Btu/hAllVRF Multi-Split Syst…
51-11C-51-11C-40333 Section C403.3.3—Hot gas bypass.
0.9K chars
C403.3.3 Hot gas bypass limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as i…
51-11C-51-11C-40334 Section C403.3.4—Boilers.
5.0K chars
C403.3.4Boiler requirements.Boiler systems shall comply with Sections C403.3.4.1 through C403.3.4.5.2.C403.3.4.1 Combustion air positive shut-off. Combustion air positive shut-off shall be provided on all newly installed boiler systems as follows:1. All boiler systems with an inp…
51-11C-51-11C-40335 Section C403.3.5—Dedicated outdoor air systems.
8.0K chars
C403.3.5 Dedicated outdoor air systems (DOAS). For buildings with occupancies as shown in Table C403.3.5, outdoor air shall be provided to each occupied space by a dedicated outdoor air system (DOAS) which delivers 100 percent outdoor air without requiring operation of the heatin…
51-11C-51-11C-40336 Section C403.3.6—Ventilation for Group R-2 occupancy.
1.3K chars
C403.3.6 Ventilation for Group R-2 occupancy. For all Group R-2 dwelling and sleeping units, a balanced ventilation system with a heat recovery system shall provide outdoor air directly to all habitable spaces. The heat recovery system shall have a 60 percent minimum sensible rec…
51-11C-51-11C-40337 Section C403.3.7—Hydronic system flow rate.
1.7K chars
C403.3.7 Hydronic system flow rate. Chilled water and condenser water piping shall be designed such that the design flow rate in each pipe segment shall not exceed the values listed in Table C403.3.7 for the appropriate total annual hours of operation. Pipe sizes for systems that…
51-11C-51-11C-40338 Section C403.3.8—Hydronic coils.
1.9K chars
C403.3.8 Hydronic coil selection. Hydronic coils shall comply with Sections C403.3.8.1 and C403.3.8.2.EXCEPTION:Replacement coils within existing equipment.C403.3.8.1 Chilled-water coil selection. Chilled-water cooling coils shall be selected to provide a 15°F or higher temperatu…
51-11C-51-11C-40340 Section C403.4—HVAC system controls.
0.9K chars
C403.4 HVAC system controls. HVAC systems shall be provided with controls in accordance with Sections C403.4.1 through C403.4.12 and shall be capable of and configured to implement all required control functions in this code.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27…
51-11C-51-11C-40341 Section C403.4.1—Thermostatic controls.
8.1K chars
C403.4.1 Thermostatic controls. The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls capable of responding to temperature within the zone. Controls in the same zone or in neighboring zones connected by openings larger than …
51-11C-51-11C-40342 Section C403.4.2—Off-hour controls.
3.6K chars
C403.4.2 Off-hour controls. For all occupancies other than Group R, each zone shall be provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system.EXCEPTIONS:1. Zones that will be operated continuously. 2. Zones…
51-11C-51-11C-40343 Section C403.4.3—Hydronic systems controls.
4.7K chars
C403.4.3 Hydronic systems controls. The heating of fluids that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Sections C403.4.3.1 through C403.4.3.3. Hydronic heating systems com…
51-11C-51-11C-403431 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-403431, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-403431, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40344 Section C403.4.4—Part load controls.
3.8K chars
C403.4.4 Part load controls. Hydronic systems greater than or equal to 300,000 Btu/h (88 kW) in design output capacity supplying heated or chilled water to comfort conditioning systems shall include controls that are configured to:1. Automatically reset the supply-water temperatu…
51-11C-51-11C-40345 Section C403.4.5—Pump isolation.
1.1K chars
C403.4.5 Pump isolation. Chilled water plants including more than one chiller shall be capable of and configured to reduce flow automatically through the chiller plant when a chiller is shut down and automatically shut off flow to chillers that are shut down. Chillers piped in se…
51-11C-51-11C-40346 Section C403.4.6—Variable flow controls.
1.7K chars
C403.4.6 Variable flow controls. Individual pumps required by this code to have variable speed control shall be controlled in one of the following manners:1. For systems having a combined pump motor horsepower less than or equal to 20 hp (15 kW) and without direct digital control…
51-11C-51-11C-40347 Section C403.4.7—Combustion heating equipment controls.
1.1K chars
C403.4.7 Combustion heating equipment controls. Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control.EXCEPTIONS:1. Boilers. 2. Radiant heaters.C403.4.7.1 Combustion decorative vented appliance, combustion fireplace and…
51-11C-51-11C-40348 Sections C403.4.8 through C403.4.10—Group R requirements.
2.7K chars
C403.4.8 Group R-1 hotel/motel guestrooms. See Section C403.7.4.C403.4.9 Group R-2 and R-3 dwelling units. The primary space conditioning system within each dwelling unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The ther…
51-11C-51-11C-40349 Sections C403.4.11 and C403.4.12.
3.7K chars
C403.4.11 Direct digital control systems. Direct digital control (DDC) shall be required as specified in Sections C403.4.11.1 through C403.4.11.4.C403.4.11.1 DDC applications. DDC shall be provided in the applications and qualifications listed in Table C403.4.11.1 and for load ma…
51-11C-51-11C-40350 Section C403.5—Economizers.
8.8K chars
C403.5 Economizers. Air economizers shall be provided on all new cooling systems including those serving computer server rooms, electronic equipment, radio equipment, and telephone switchgear. Economizers shall comply with Sections C403.5.1 through C403.5.5.EXCEPTIONS:1a. For oth…
51-11C-51-11C-40351 Section C403.5.1—Integrated economizer control.
2.1K chars
C403.5.1 Integrated economizer control. Economizer systems shall be integrated with the mechanical cooling system and be configured to provide partial cooling even where additional mechanical cooling is required to provide the remainder of the cooling load. Controls shall not be …
51-11C-51-11C-40352 Section C403.5.2—Economizer heating system impact.
0.5K chars
C403.5.2 Economizer heating system impact. HVAC system design and economizer controls shall be such that economizer operation does not increase building heating energy use during normal operation.EXCEPTION:Economizers on VAV systems that cause zone level heating to increase due t…
51-11C-51-11C-40353 Section C403.5.3—Air economizers.
3.8K chars
C403.5.3 Air economizers. Air economizers shall comply with Sections C403.5.3.1 through C403.5.3.5.C403.5.3.1 Design capacity. Air economizer systems shall be configured to modulate outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity …
51-11C-51-11C-40354 Section C403.5.4—Waterside economizers.
1.4K chars
C403.5.4 Waterside economizers. Waterside economizers shall comply with Sections C403.5.4.1 and C403.5.4.2.C403.5.4.1 Design capacity. Water economizer systems shall be configured to cool supply air by indirect evaporation and providing up to 100 percent of the expected system co…
51-11C-51-11C-40355 Section C403.5.5—Economizer fault detection and diagnostics.
2.0K chars
C403.5.5 Economizer fault detection and diagnostics (FDD). Air-cooled unitary direct-expansion units with a cooling capacity of 54,000 Btu/h or greater listed in the tables in Section C403.3.2 that are equipped with an economizer in accordance with Section C403.5 shall include a …
51-11C-51-11C-40360 Section C403.6—Requirements for mechanical systems serving multiple zones.
7.2K chars
C403.6 Requirements for mechanical systems serving multiple zones. Sections C403.6.1 through C403.6.10 shall apply to mechanical systems serving multiple zones.C403.6.1 Variable air volume (VAV) and multiple zone systems. Supply air systems serving multiple zones shall be VAV sys…
51-11C-51-11C-403610 Section C403.6.10—High efficiency VAV systems.
10.0K chars
C403.6.10 High efficiency variable air volume (VAV) systems. For HVAC systems subject to the requirements of Section C403.3.5 but utilizing Exception 2 of that section, a high efficiency multiple-zone VAV system may be provided without a separate parallel DOAS when the system is …
51-11C-51-11C-4037 Section C403.7—Ventilation and exhaust systems.
0.4K chars
C403.7 Ventilation and exhaust systems. In addition to other requirements of Section C403 applicable to the provisions of ventilation air or the exhaust of air, ventilation and exhaust systems shall be in accordance with Sections C403.7.1 through C403.7.8.[Statutory Authority: RC…
51-11C-51-11C-40371 Section C403.7.1—Demand control ventilation.
2.9K chars
C403.7.1 Demand control ventilation.C403.7.1.1 Spaces requiring demand control ventilation. Demand control ventilation (DCV) shall be provided for the following:1. Spaces with ventilation provided by single-zone systems where an air economizer is provided to comply with Section C…
51-11C-51-11C-40372 Section C403.7.2—Occupancy sensors.
1.3K chars
C403.7.2 Occupancy sensors. Classrooms, gyms, auditoriums, conference rooms, and other spaces with an occupant load greater than or equal to 25 people per 1000 square feet (93 m2) of floor area (as established in Table 403.3.1.1 of the International Mechanical Code) that are larg…
51-11C-51-11C-40373 Section C403.7.3—Ventilation air heating control.
0.6K chars
C403.7.3 Ventilation air heating control. For ventilation air units with supplemental heating capacity that operate in conjunction with zone heating and cooling systems, supplemental heating shall not warm ventilation supply air to a temperature greater than 55°F (13°C).[Statutor…
51-11C-51-11C-40374 Section C403.7.4—HVAC serving guestrooms.
2.9K chars
C403.7.4 Automatic control of HVAC systems serving guestrooms. In Group R-1 buildings containing more than 50 guestrooms, each guestroom shall be provided with controls complying with the provisions of Sections C403.7.4.1 and C403.7.4.2. Card key controls comply with these requir…