51-11C-51-11C-40375 Section C403.7.5—Loading dock and garage ventilation system controls.
3.1K chars
C403.7.5 Loading dock, motor vehicle repair garage, and parking garage ventilation system controls. Mechanical ventilation systems for loading docks, motor vehicle repair garages, and parking garages shall be designed to exhaust the airflow rates (maximum and minimum) determined …
51-11C-51-11C-40376 Section C403.7.6—Energy recovery ventilation systems.
6.2K chars
C403.7.6 Energy recovery ventilation systems. Energy recovery ventilation systems shall be provided as specified in Sections C403.7.6.1 and C403.7.6.2.C403.7.6.1 Ventilation for Group R-2 occupancy. For all Group R-2 dwelling and sleeping units, a balanced ventilation system with…
51-11C-51-11C-40377 Section C403.7.7—Exhaust systems.
6.6K chars
C403.7.7 Exhaust systems.C403.7.7.1 Kitchen exhaust systems.C403.7.7.1.1 Replacement air. Replacement air introduced directly into the exhaust hood cavity shall not be greater than 10 percent of the hood exhaust airflow rate.C403.7.7.1.2 Kitchen exhaust hood certification and max…
51-11C-51-11C-40378 Section C403.7.8—Shutoff dampers.
3.9K chars
C403.7.8 Shutoff dampers. Mechanical openings shall be provided with shutoff dampers in accordance with Sections C403.7.8.1 through C403.7.8.4.C403.7.8.1 Shutoff dampers for building isolation. Outdoor air supply, exhaust openings and relief outlets and stairway and elevator hois…
51-11C-51-11C-4038 Section C403.8—Fan and fan controls.
17.9K chars
C403.8 Fan and fan controls. Fans in HVAC systems shall comply with Sections C403.8.1 through C403.8.5.1.The airflow requirements of Section C403.8.5.1 shall apply to all fan motors. Low capacity ventilation fans shall also comply with Section C403.8.4.C403.8.1 Fan System. Each f…
51-11C-51-11C-4039 Section C403.9—Heat rejection and heat recovery equipment.
7.9K chars
C403.9 Heat rejection and heat recovery equipment.C403.9.1 Heat rejection equipment. Heat rejection equipment, including air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers and evaporative condensers, shall comply with this section.EXCEP…
51-11C-51-11C-40391 Section C403.10—Construction of HVAC system elements.
13.8K chars
C403.10 Construction of HVAC system elements. Ducts, plenums, piping and other elements that are part of an HVAC system shall be constructed and insulated in accordance with Sections C403.10.1 through C403.10.3.1.C403.10.1 Duct and plenum insulation and sealing.C403.10.1.1 Ducts,…
51-11C-51-11C-40392 Section C403.11—Mechanical systems outside the building envelope.
1.6K chars
C403.11 Mechanical systems located outside of the building thermal envelope. Mechanical systems providing heat outside of the thermal envelope of a building shall comply with Sections C403.11.1 through C403.11.3.C403.11.1 Heating outside a building. Systems installed to provide h…
51-11C-51-11C-40393 Section C403.12—High efficiency single zone VAV systems.
6.4K chars
C403.12 High efficiency single-zone variable air volume (VAV) systems. For HVAC systems subject to the requirements of Section C403.3.5 but utilizing Exception 2 of that section, a high efficiency single-zone VAV system may be provided without a separate parallel DOAS when the sy…
51-11C-51-11C-40394 Section C403.13—Dehumidification for plant growth.
1.4K chars
C403.13 Dehumidification in spaces for plant growth and maintenance. Equipment that dehumidifies building spaces used for plant growth and maintenance shall be one of the following:1. Stand-alone dehumidifiers that meet the following minimum integrated energy factors as measured …
51-11C-51-11C-40400 Section C404—Service water heating and pressure-booster systems.
0.3K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40400, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40400, filed 2/1/13, effe…
51-11C-51-11C-40401 Section C404.1—General.
0.7K chars
C404.1 General. This section covers the minimum efficiency of, and controls for, service water-heating equipment and insulation of service hot water piping.EXCEPTION:Energy using equipment used by a manufacturing, industrial or commercial process other than maintaining comfort an…
51-11C-51-11C-40402 Section C404.2—Service water-heating equipment performance efficiency.
7.4K chars
C404.2 Service water-heating equipment performance efficiency. Water-heating equipment and hot water storage tanks shall meet the requirements of Table C404.2. The efficiency shall be verified through certification and listed under an approved certification program, or if no cert…
51-11C-51-11C-404021 Table C404.2—Minimum performance of water-heating equipment.
8.2K chars
Table C404.2Minimum Performance of Water-Heating EquipmentEquipment TypeSize Category(input)Subcategory or Rating ConditionDraw PatternPerformance Requireda,jTest ProcedurebElectric table-top water heatersk≤ 12 kWc≥ 20 gal≤ 120 galVery smallLowMediumHighUEF ≥ 0.6323 - (0.0058 × V…
51-11C-51-11C-40403 Section C404.3—Efficient heated water supply piping.
3.6K chars
C404.3 Efficient heated water supply piping. Heated water supply piping shall be in accordance with Section C404.3.1 or C404.3.2. The flow rate through 1/4-inch (6.4 mm) piping shall be not greater than 0.5 gpm (1.9 L/m). The flow rate through 5/16-inch (7.9 mm) piping shall be n…
51-11C-51-11C-40404 Section C404.4—Heat traps.
1.0K chars
C404.4 Heat traps for hot water storage tanks. Storage tank-type water heaters and hot water storage tanks that have vertical water pipes connecting to the inlet and outlet of the tank shall be provided with integral heat traps at the vertical inlets and outlets or shall have pip…
51-11C-51-11C-40405 Section C404.5—Water heater installation.
0.3K chars
C404.5 Water heater installation. Electric water heaters in unconditioned spaces or on concrete floors shall be placed on an incompressible, insulated surface with a minimum thermal resistance of R-10.[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 R…
51-11C-51-11C-40406 Section C404.6—Pipe insulation.
3.4K chars
C404.6 Insulation of piping. Piping from a water heater to the termination of the heated water fixture supply pipe shall be insulated in accordance with Table C403.10.3. On both the inlet and outlet piping of a storage water heater or heated water storage tank, the piping to a he…
51-11C-51-11C-40407 Section C404.7—Heated-water circulating and temperature maintenance systems.
4.2K chars
C404.7 Heated-water circulating and heat trace temperature maintenance systems. Heated-water circulation systems for temperature maintenance shall be in accordance with Section C404.7.1. Electric resistance heat trace systems for temperature maintenance shall be in accordance wit…
51-11C-51-11C-40408 Section C404.8—Demand recirculation controls.
0.9K chars
C404.8 Demand recirculation controls.Demand recirculation water systems shall have controls that comply with both of the following:1. The controls shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a…
51-11C-51-11C-40409 Section C404.9—Domestic hot water meters.
1.0K chars
C404.9 Domestic hot water meters. Each individual dwelling unit in a Group R-2 occupancy with central service domestic hot water systems shall be provided with a domestic hot water meter to allow for domestic hot water billing based on actual domestic hot water usage.EXCEPTION:Dw…
51-11C-51-11C-404091 Section C404.10—Drain water heat recovery units.
0.4K chars
C404.10 Drain water heat recovery units. Drain water heat recovery units shall comply with CSA B55.2. Potable waterside pressure loss shall be less than 10 psi (69 kPa) at maximum design flow. For Group R occupancies, the efficiency of drain water heat recovery unit efficiency sh…
51-11C-51-11C-40410 Section C404.11—Pools and spas.
3.6K chars
C404.11 Energy consumption of pools and permanent spas. The energy consumption of pools and permanent spas shall be controlled by the requirements in Sections C404.11.1 through C404.11.4.C404.11.1 Heaters. Pool water heaters using electric resistance heating as the primary source…
51-11C-51-11C-40413 Section C404.13—Service water pressure-booster systems.
1.3K chars
C404.13 Servicewater pressure-booster systems. Service water pressure-booster systems shall be designed and configured such that the following apply:1. One or more pressure sensors shall be used to vary pump speed and/or start and stop pumps. The sensors shall either be located n…
51-11C-51-11C-40414 Section C404.14—Demand responsive water heating.
1.1K chars
C404.14 Demand responsive water heating. Electric storage water heaters with rated water storage volume between 40 and 120 gallons and a nameplate input rating equal to or less than 12kW shall be provided with demand responsive controls that comply with ANSI/CTA-2045-B Level 2 or…
51-11C-51-11C-40415 Section C404.15—Service water heating commissioning.
0.3K chars
C404.15 Commissioning. Service water heating systems shall be commissioned in accordance with Section C408.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40415, filed 7/1/22, 6/7/23…
51-11C-51-11C-40500 Section C405—Electrical power and lighting systems.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40500, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40501 Section C405.1—General.
2.3K chars
C405.1 General. Lighting system controls, the maximum lighting power for interior and exterior applications, electrical energy consumption, vertical and horizontal transportation systems, and minimum efficiencies for motors and transformers shall comply with this section.Sleeping…
51-11C-51-11C-40502 Section C405.2—Electrical power and lighting systems.
1.5K chars
C405.2 Lighting controls. Lighting systems shall be provided with controls that comply with one of the following:1. Lighting controls as specified in Sections C405.2.1 through C405.2.10.2. Luminaire-level lighting controls (LLLC) as specified in Section C405.2.8.1.EXCEPTION:Excep…
51-11C-51-11C-405021 Section C405.2.1—Occupant sensor controls.
5.8K chars
C405.2.1 Occupant sensor controls. Occupant sensor controls shall be installed to control luminaires in the space types listed in Table C405.2.1, and shall comply with the requirements listed in the table.EXCEPTIONS:1. Corridors in manufacturing facilities. 2. General lighting an…
51-11C-51-11C-405022 Section C405.2.2—Time switch controls.
2.9K chars
C405.2.2 Time switch controls. Each area of the building that is not provided with occupant sensor controls complying with Section C405.2.1.1 shall be provided with time switch controls complying with Section C405.2.2.1.EXCEPTIONS:1. Luminaires which are required to have specific…
51-11C-51-11C-405023 Section C405.2.3—Manual controls.
1.5K chars
C405.2.3 Manual controls. All lighting shall have manual controls complying with the following:1. They shall be in a location with ready access to occupants.2. They shall be located where the controlled lights are visible, or shall identify the area served by the lights and indic…
51-11C-51-11C-405024 Section C405.2.4—Light-reduction controls.
2.3K chars
C405.2.4 Light-reduction controls. Where not provided with occupant sensor controls complying with Section C405.2.1.1, general lighting shall be provided with light-reduction controls complying with Section C405.2.4.1.EXCEPTIONS:1. Luminaires controlled by daylight responsive con…
51-11C-51-11C-405025 Section C405.2.5—Daylight responsive controls.
9.7K chars
C405.2.5 Daylight responsive controls.Daylight responsive controls complying with Section C405.2.5.1 shall be provided to control the general lighting within daylight zones in the following spaces:1. Spaces with a total of more than 75 watts of general lighting within primary sid…
51-11C-51-11C-405026 Section C405.2.6—Additional lighting controls.
2.8K chars
C405.2.6 Additional lighting controls. Specific application lighting shall be provided with controls, in addition to controls required by other sections, for the following:1. The following lighting shall be controlled by an occupant sensor complying with Section C405.2.1.1 or a t…
51-11C-51-11C-405027 Section C405.2.7—Area controls.
1.0K chars
C405.2.7 Area controls. The maximum lighting power that may be controlled from a single switch or automatic control device shall not exceed that which is provided by a 20 ampere circuit loaded to not more than 80 percent. A master control may be installed provided the individual …
51-11C-51-11C-405028 Section C405.2.8—Advanced lighting controls.
4.2K chars
C405.2.8 Advanced lighting controls. Any contiguous open office area larger than 5,000 square feet shall have its general lighting controlled by either:1. Luminaire-level lighting controls (LLLC) conforming to the requirements of Section C405.2.8.1.2. Networked lighting control (…
51-11C-51-11C-405029 Section C405.2.9—Exterior lighting controls.
2.6K chars
C405.2.9 Exterior lighting controls. Exterior lighting systems shall be provided with controls that comply with Sections C405.2.9.1 through C405.2.9.4.EXCEPTIONS:1. Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, sec…
51-11C-51-11C-40503 Section C405.2.10—Parking garage lighting control.
1.9K chars
C405.2.10 Parking garage lighting control. Parking garage lighting shall be controlled by an occupant sensor complying with Section C405.2.1.1 or a time-switch control complying with Section C405.2.2.1. Additional lighting controls shall be provided as follows:1. Lighting power o…
51-11C-51-11C-405030 Section C405.3—Lighting for plant growth and maintenance.
0.8K chars
C405.3 Lighting for plant growth and maintenance. All permanently installed luminaires used for plant growth and maintenance shall have a photosynthetic photon efficacy measured at the lamp for luminaires with serviceable or removable lamps or at the luminaire for integrated, non…
51-11C-51-11C-40504 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40504, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40504, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40505 Section C405.4—Interior lighting power requirements.
0.7K chars
C405.4 Interior lighting power requirements. A building complies with this section if its total connected interior lighting power calculated under Section C405.4.1 is no greater than the interior lighting power allowance calculated under Section C405.4.2.[Statutory Authority: RCW…
51-11C-51-11C-405051 Section C405.4.1—Total connected interior lighting power.
4.4K chars
C405.4.1 Total connected interior lighting power. The total connected interior lighting power shall be determined in accordance with Equation 4-13.TCLP = [LVL + BLL + TRK + POE + Other](Equation 4-13)Where:TCLP = Total connected lighting power (watts).LVL = For luminaires with la…
51-11C-51-11C-405052 Section C405.4.2—Interior lighting power requirements.
4.8K chars
C405.4.2 Interior lighting power allowance. The total interior lighting power allowance (watts) for an entire building shall be determined according to Table C405.4.2(1) using the Building Area Method, or Table C405.4.2(2) using the Space-by-Space Method. The interior lighting po…
51-11C-51-11C-405053 Table C405.4.2(1)—Interior lighting power allowances—Building area method.
1.3K chars
Table C405.4.2(1)Interior Lighting Power Allowances—Building Area MethodBuilding Area TypeLPD(w/ft2)Automotive facility0.64Convention center0.64Court house0.79Dining: Bar lounge/leisure0.79Dining: Cafeteria/fast food0.72Dining: Family0.71Dormitory0.46Exercise center0.67Fire stati…
51-11C-51-11C-405054 Table C405.4.2(2)—Interior lighting power allowances—Space-by-space method.
7.0K chars
Table C405.4.2(2)Interior Lighting Power Allowances—Space-by-Space MethodCommon Space-by-Space Typesa,jLPD (w/ft2)Atrium - Less than 20 feet in height0.39Atrium - 20 to 40 feet in height0.48Atrium - Above 40 feet in height0.60Audience/seating area - Permanenti In an auditorium0.6…
51-11C-51-11C-40506 Section C405.5—Exterior lighting.
0.7K chars
C405.5 Exterior lighting power requirements. The total connected exterior lighting power calculated in accordance with Section C405.5.2 shall not be greater than the exterior lighting power allowance calculated in accordance with Section C405.5.3.[Statutory Authority: RCW 19.27A.…
51-11C-51-11C-405061 Section C405.5.1—Exterior building grounds lighting.
0.9K chars
C405.5.1 Exterior building grounds lighting. All exterior building grounds luminaires that operate at greater than 25 watts shall have a minimum efficacy of 100 lumens per watt.EXCEPTIONS:1. Luminaires controlled by a motion sensor. 2. Luminaires that qualify for one of the excep…
51-11C-51-11C-405062 Section C405.5.2—Exterior building lighting power.
3.3K chars
C405.5.2 Total connected exterior building lighting power. The total exterior connected lighting power shall be the total maximum rated wattage of all exterior lighting that is powered through the energy service for the building.EXCEPTION:Lighting used for the following applicati…
51-11C-51-11C-405063 Table C405.5.3(1)—Exterior lighting zones.
0.9K chars
Table C405.5.3(1)Exterior Lighting ZonesLighting ZoneDescription1Developed areas of national parks, state parks, forest land, and rural areas2Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial with limited nighttime use and res…