322 sections in this chapter.
51-11C-51-11C-40510 Section C405.10—Controlled receptacles.
3.1K chars
C405.10 Automatic receptacle control. The following shall have automatic receptacle control complying with Section C405.10.1:1. At least 50 percent of all 125V, 15- and 20-amp receptacles installed in enclosed offices, conference rooms, rooms used primarily for copy or print func…
51-11C-51-11C-40511 Section C405.11—Voltage drop.
1.1K chars
C405.11 Voltage drop. The total voltage drop across the combination of customer-owned service conductors, feeder conductors and branch circuit conductors shall not exceed five percent.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. …
51-11C-51-11C-40512 Section C405.12—Alternating current-output uninterruptible power supplies (AC-output UPS).
1.0K chars
AC-output UPS systems serving a computer room shall meet or exceed the calculation and testing requirements identified in ENERGY STAR Program Requirements for Uninterruptible Power Supplies (UPSs) – Eligibility Criteria Version 2.0.EXCEPTION:AC-output UPC that utilizes standardiz…