332 sections in this chapter.
51-11C-51-11C-40807 Section C408.7—Refrigeration system commissioning.
1.0K chars
C408.7 Refrigeration system commissioning. All installed refrigeration systems subject to Section C410 shall be included in the commissioning process required by Section C408.1.EXCEPTIONS:1. Self-contained refrigeration systems are exempt from the commissioning process. 2.Total i…
51-11C-51-11C-40900 Section C409—Energy metering and energy consumption management.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40900, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40901 Section C409.1—General.
2.9K chars
C409.1 General. All new buildings and additions shall have the capability of metering all source energy usage in accordance with Section C409.2 in addition to the source energy for on-site renewable energy production in accordance with Section C409.2.4 and the end-use energy usag…
51-11C-51-11C-40902 Section C409.2—Energy source metering.
2.1K chars
C409.2 Energy source metering. Buildings shall have a meter at each energy source. For each energy supply source listed in Section C409.2.1 through C409.2.4, meters shall collect data for the whole building or for each separately metered portion of the building where not exempted…
51-11C-51-11C-40903 Section C409.3—End-use metering.
6.1K chars
C409.3 End-use metering. Meters shall be provided to collect energy use data for each end-use category listed in Sections C409.3.1 through C409.3.7. These meters shall collect data for the whole building or for each separately metered portion of the building where not exempted by…
51-11C-51-11C-40904 Section C409.4—Measurement devices, data acquisition system and energy display.
3.4K chars
C409.4 Measurement devices, data acquisition system and energy display.C409.4.1 Meters. Meters and other measurement devices required by this section shall be configured to automatically communicate energy data to a data acquisition system and energy display. Source meters may be…
51-11C-51-11C-40905 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40905, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03…
51-11C-51-11C-41000 Section C410—Refrigeration system requirements.
16.8K chars
C410.1 General. Walk-in coolers, walk-in freezers, refrigerated warehouse coolers, refrigerated warehouse freezers, and refrigerated display cases shall comply with this Section.Table C410.2Minimum Efficiency Requirements: Commercial Refrigerators and Freezers and RefrigerationEq…
51-11C-51-11C-41100 Section C411—Renewable energy.
11.5K chars
C411.1 On-site renewable energy. Each new building or addition larger than 10,000 square feet of gross conditioned floor area shall include a renewable energy generation system consisting of not less than 0.5 W/ft2 or 1.7 Btu/ft2 multiplied by the sum of the gross conditioned flo…
51-11C-51-11C-41200 Section C412—Compressed air systems.
6.8K chars
C412.1 General. All new compressed air systems, and all additions or alterations of compressed air systems where the total combined horsepower (hp) of the compressor(s) is 25 hp or more, shall meet the requirements of this section. These requirements apply to the compressors, rel…
51-11C-51-11C-50000 Chapter 5 [CE]—Existing buildings.
5.5K chars
C501 General.C501.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing buildings and structures.C501.1.1 Existing buildings. Except as specified in this chapter, this code shall not be used to require the remov…
51-11C-51-11C-50200 Section C502—Additions.
5.8K chars
C502.1 General.Additions to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion of the existing building or building system to comply with this code. Addit…
51-11C-51-11C-50300 Section C503—Alterations.
31.7K chars
C503.1 General. Alterations to any building or structure shall comply with the requirements of Section C503 and the code for new construction. Alterations to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to ne…
51-11C-51-11C-50400 Section C504—Repairs.
1.5K chars
C504.1 General. Buildings and structures, and parts thereof, shall be repaired in compliance with Section C501.3 and this section. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be…
51-11C-51-11C-50500 Section C505—Change of space conditioning, occupancy or use.
9.0K chars
C505.1 General. Buildings or spaces undergoing a change in space conditioning alteration shall comply with Sections C505.2 and C505.4. Buildings or spaces undergoing a change in occupancy alteration shall comply with Sections C505.3 and C505.4. Spaces changing from one use type t…
51-11C-51-11C-50600 Section C506—Metering for existing buildings.
1.1K chars
C506.1 Metering in existing buildings. Where new or replacement systems or equipment are installed in an existing building that was constructed subject to the requirements of this section, metering shall be provided for such new or replacement systems or equipment so that their e…
51-11C-51-11C-60000 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A, 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-60000, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05…
51-11C-51-11C-600000 Chapter 6 [CE]—Referenced standards.
19.1K chars
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that refe…
51-11C-51-11C-61000 Appendix A—Default heat loss coefficients.
0.2K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-61000, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24.]
51-11C-51-11C-61010 Section A101—General.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61010, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61011 Section A101.1—Scope.
0.5K chars
A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the WSEC. This chapter includes tables of seasonal average heat loss coefficients for specified nominal insulation.[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. …
51-11C-51-11C-61012 Section A101.2—Description.
0.5K chars
A101.2 Description. These coefficients were developed primarily from data and procedures from the ASHRAE Fundamentals Handbook.Coefficients not contained in this chapter may be computed using the procedures listed in this reference if the assumptions in the following sections are…
51-11C-51-11C-61013 Section A101.3—Air films.
0.4K chars
A101.3 Air films. Default R-values used for air films shall be as follows:R-ValueCondition0.17All exterior surfaces0.61Interior horizontal surfaces, heat flow up0.92Interior horizontal surfaces, heat flow down0.68Interior vertical surfaces[Statutory Authority: RCW 19.27A.020, 19.…
51-11C-51-11C-61014 Section A101.4—Compression of insulation.
1.0K chars
A101.4 Compression of insulation. Insulation which is compressed shall be rated in accordance with Table A101.4 or reduction in value may be calculated in accordance with the procedures in the ASHRAE Fundamentals Handbook.Table A101.4R-value of Fiberglass Batts Compressed Within …
51-11C-51-11C-61015 Section A101.5—Building materials.
3.2K chars
A101.5 Building materials. Default R-values used for building materials shall be as shown in Table A101.5.Table A101.5Default R-values for Building MaterialsMaterialNominal Size (in.)ActualSize (in.)R-Value(Heat Capacityc)Air cavity (unventilated), between metal studs at 16 inche…
51-11C-51-11C-61020 Section A102—Ceilings.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61020, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61021 Section A102.1—General.
1.0K chars
A102.1 General. Table A102.1 lists heat loss coefficients for the opaque portion of exterior ceilings below vented attics, vaulted ceilings and roof decks in units of Btu/h • ft2 • °F of ceiling.They are derived from procedures listed in the ASHRAE Fundamentals Handbook. Ceiling …
51-11C-51-11C-610211 Table A102.1—Default U-factors for ceilings.
0.9K chars
Table A102.1Default U-factors for Ceilings Standard FrameAdvanced FrameCeilings Below Vented Attics FlatBaffled R-190.0490.047 R-300.0360.032 R-380.0310.026 R-490.0270.020 R-600.0250.017Scissors Truss R-30 (4/12 roof pitch)0.0430.031 R-38 (4/12 roof pitch)0.0400.025 R-49 (4/12 ro…
51-11C-51-11C-61022 Section A102.2—Component description.
6.9K chars
A102.2 Component description. The four types of ceilings are characterized as follows:A102.2.1 Ceilings below a vented attic. Attic insulation is assumed to be blown-in, loose-fill fiberglass with a K-value of 2.6 h • ft2 • °F/Btu per inch. Full bag count for specified R-value is…
51-11C-51-11C-610221 Tables A102.2.4—Steel truss framed ceiling Uo values.
2.7K chars
Table A102.2.4(1)Steel Trussa Framed Ceiling UoCavity Truss Span (ft) R-value12141618202224262830323436190.10750.09910.09280.08780.08390.08070.07800.07570.07370.07200.07060.06930.0681300.09070.08230.07600.07100.06710.06380.06120.05890.05690.05520.05380.05250.0513380.08440.07590.0…
51-11C-51-11C-610225 Tables A102.2.5—Default U-factors for metal building roofs.
2.0K chars
Table A102.2.5Default U-factors for Metal Building Roofs Overall U-Factor for Assembly of Base Roof Plus ContinuousInsulation (uninterrupted by framing) Rated R-Value ofContinuous InsulationInsulationSystemRated R-Value ofInsulationOverall U-Factor for Entire Base RoofAssemblyR-6…
51-11C-51-11C-610226 Tables A102.2.6—Assembly U-factors for roofs with insulation entirely above deck.
4.4K chars
Table A102.2.6(1)Assembly U-factors for Roofs with Tapered Insulation Entirely Above Deck Single Slope Rectangular to One-sided,e,f,g,h(Uninterrupted by Framing) Rated R-value of Insulation at Maximum Condition (Rmaxc)151015202530354045505560Rated R-value of insulation at a Minim…
51-11C-51-11C-61030 Section A103—Above grade walls.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61030, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61031 Section A103.1—General.
1.4K chars
A103.1 General. The tables in this section list heat loss coefficients for the opaque portion of above-grade wood stud frame walls, metal stud frame walls and concrete masonry walls (Btu/h • ft2 • °F). They are derived from procedures listed in the ASHRAE Fundamentals Handbook. F…
51-11C-51-11C-61032 Section A103.2—Framing description.
1.6K chars
A103.2 Framing description. For wood stud frame walls, three framing types are considered and defined as follows:A103.2.1 Standard. Studs framed on 16 inch centers with double top plate and single bottom plate. Corners use three studs and each opening is framed using two studs. H…
51-11C-51-11C-61033 Section A103.3—Component description.
0.4K chars
A103.3 Component description. Default coefficients for the following types of walls are listed: Single-stud walls, strap walls, double-stud walls, log walls, stress-skin panels, metal stud walls, and metal building walls.[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapte…
51-11C-51-11C-610331 Section A103.3.1—Single stud wall.
5.5K chars
A103.3.1 Single-stud wall. Tables A103.3.1(1) through A103.3.1(8): Assumes either 2 x 4 or 2 x 6 studs framed on 16 or 24 inch centers. Headers are solid for 2 x 4 walls and double 2x for 2 x 6 walls, with either dead-air or rigid-board insulation in the remaining space.TABLE A10…
51-11C-51-11C-610332 Section A103.3.2—Strap wall.
0.5K chars
A103.3.2 Strap wall. Table A103.3.2: Assumes 2 x 6 studs framed on 16 or 24 inch centers. 2 x 3 or 2 x 4 strapping is run horizontally along the interior surface of the wall to provide additional space for insulation.Table A103.3.22 x 6: Strap Wall Siding Material/Frame Type Lapp…
51-11C-51-11C-610333 Section A103.3.3—Double stud wall.
1.1K chars
A103.3.3 Double stud wall. Tables A103.3.3(1) and A103.3.3(2): Assumes an exterior structural wall and a separate interior, nonstructural wall. Insulation is placed in both wall cavities and in the space between the two walls. Stud spacing is assumed to be on 24 inch centers for …
51-11C-51-11C-610334 Section A103.3.4—Log wall.
0.5K chars
A103.3.4 Log wall. U-factors for log walls shall be determined using ICC 400 Table 305.3.1.1, U-Factor of log wall (UW) by log thickness (WL) and specific gravity.[Statutory Authority: RCW 19.27A.020, 19.27A.045, 19.27A.160 and chapter 19.27 RCW. WSR 20-01-047, § 51-11C-610334, f…
51-11C-51-11C-610335 Section A103.3.5—Stress skin panel.
0.4K chars
A103.3.5 Stress-skin panel. See Table A103.3.5.Table A103.3.5Stress Skin Panel PanelThickness,InchesU-factor NOTE: R-value of expanded polystyrene: R-3.85 per inchFraming: 6%Spline: 8% 3 1/20.071 5 1/20.048 7 1/40.037 9 1/40.030 11 1/40.025 No thermal bridging between interior an…
51-11C-51-11C-610336 Section A103.3.6—Metal stud walls.
6.8K chars
A103.3.6 Metal stud walls. The nominal R-values in Tables A103.3.6.1 through A103.3.6.3 may be used for purposes of calculating metal stud wall section U-factors in lieu of the ASHRAE zone calculation method as provided in Chapter 27 of the ASHRAE Fundamentals Handbook.A103.3.6.1…
51-11C-51-11C-610337 Section A103.3.7—Concrete and masonry walls.
13.9K chars
A103.3.7 Concrete and masonry walls.A103.3.7.1 Concrete masonry walls. The nominal R-values in Table A103.3.7.1 may be used for purposes of calculating concrete masonry wall section U-factors in lieu of the ASHRAE isothermal planes calculation method as provided in Chapter 27 of …
51-11C-51-11C-61040 Section A104—Below-grade walls and slabs.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61040, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61041 Section A104.1—General.
1.9K chars
A104.1 General. Table A104.1 lists heat loss coefficients for below-grade walls and floors.Coefficients for below-grade walls are given as U-factors (Btu/h • ft2 • °F of wall area). Coefficients for below-grade slabs are listed as F-factors (Btu/h • ft • °F per lineal foot of sla…
51-11C-51-11C-61042 Section A104.2—Component description.
1.2K chars
A104.2 Component description. All below-grade walls are assumed to be 8 inch concrete. The wall is assumed to extend from the slab upward to the top of the mud sill for the distance specified in Table A104.1, with 6 inches of concrete wall extending above grade.Interior insulatio…
51-11C-51-11C-61043 Section A104.3—Insulation description.
0.7K chars
A104.3 Insulation description. Coefficients are listed for the following four configurations:1. Uninsulated: No insulation or interior finish.2. Interior insulation: Interior 2 x 4 insulated wall without a thermal break between concrete wall and slab.3. Interior insulation with t…
51-11C-51-11C-61050 Section A105—Floors over unconditioned space.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61050, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61051 Section A105.1—General.
1.7K chars
A105.1 General. Tables A105.1(1), A105.1(2) and A105.1(3) list heat loss coefficients for floors over unconditioned spaces in units of Btu/h • ft2 • °F.They are derived from procedures listed in the ASHRAE Fundamentals Handbook, assuming an average outdoor temperature of 45°F, an…
51-11C-51-11C-61052 Section A105.2—Crawlspace description.
1.4K chars
A105.2 Crawlspace description. Four configurations are considered: Naturally ventilated crawlspace, mechanically vented crawlspace, heated plenum crawlspace and exposed floor.A105.2.1 Naturally ventilated crawlspaces. Assumed to have 3.0 air changes per hour, with at least 1.0 ft…