215 sections in this chapter.
R.51-50-51-50-001 Authority.
0.2K chars
These rules are adopted under the authority of chapter 19.27 RCW.[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 04-01-108, § 51-50-001, filed 12/17/03, effective 7/1/04.]
R.51-50-51-50-002 Purpose.
0.6K chars
The purpose of these rules is to implement the provisions of chapter 19.27 RCW, which provides that the state building code council shall maintain the State Building Code in a status which is consistent with the purpose as set forth in RCW 19.27.020. In maintaining the codes the …
R.51-50-51-50-003 International Building Code.
1.3K chars
The 2021 edition of the International Building Code, including Appendix E, published by the International Code Council is hereby adopted by reference with the exceptions noted in this chapter of the Washington Administrative Code.[Statutory Authority: RCW 19.27.031 and 19.27.074.…
R.51-50-51-50-005 International Building Code requirements for barrier-free accessibility.
1.2K chars
Chapter 11 and other International Building Code requirements for barrier-free access, including ICC A117.1-2017 and Appendix E, are adopted pursuant to chapters 70.92 and 19.27 RCW.Pursuant to RCW 19.27.040, Chapter 11 and requirements affecting barrier-free access shall not be …
R.51-50-51-50-007 Exceptions.
2.3K chars
The exceptions and amendments to the International Building Code contained in the provisions of chapter 19.27 RCW shall apply in case of conflict with any of the provisions of these rules.The provisions of this code do not apply to temporary growing structures used solely for the…
R.51-50-51-50-008 Implementation.
1.1K chars
The International Building Code adopted under chapter 51-50 WAC shall become effective in all counties and cities of this state on March 15, 2024.[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 23-23-102, § 51-50-008, filed 11/15/23, effective 3/16/24; WSR 22-13-094, 23-12…
R.51-50-51-50-009 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-009, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 16-03-064, § 51-50-009, filed 1/19/16, effective 7/1/16; WSR 04-01-108, § 51-50-009, filed 12/17/03, effective 7/1/0…
R.51-50-51-50-0107 Section 107—Construction documents.
1.0K chars
107.2 Construction documents. Construction documents shall be in accordance with Sections 107.2.1 through 107.2.9.107.2.9 Nonstructural components. Construction documents shall indicate if structural support and anchoring documentation for nonstructural components is part of the …
R.51-50-51-50-0108 Temporary structures and uses.
0.8K chars
108.1 General. The building official is authorized to issue a permit for temporary structures and temporary uses. Such permits shall be limited as to time of service, but shall not be permitted for more than 180 days. The building official is authorized to grant extensions for de…
R.51-50-51-50-0110 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0110, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-21-021, § 51-50-0110, filed 10/9/20, effective 11/9/20.]
R.51-50-51-50-0200 Chapter 2—Definitions.
8.0K chars
SECTION 202—DEFINITIONS.ADULT FAMILY HOME. A dwelling, licensed by the state of Washington department of social and health services, in which a person or persons provide personal care, special care, room and board to more than one but not more than six adults who are not related …
R.51-50-51-50-0303 Section 303—Assembly Group A.
1.0K chars
303.4 Assembly Group A-3. Group A-3 occupancy includes assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:• Amusement arcades;• Art galleries more than 3,000 square feet (279 m2);• …
R.51-50-51-50-0305 Section 305—Educational Group E.
0.7K chars
305.2.4 Family home child care. Family home child care licensed by Washington state for the care of 16 or fewer children shall be classified as Group R-3 or shall comply with the International Residential Code.[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 26-07-066, s 51…
R.51-50-51-50-0306 Section 306—Factory Group F.
1.6K chars
306.2 Moderate-hazard factory industrial, Group F-1. Factory industrial uses that are not classified as factory industrial F-2 low hazard shall be classified as F-1 moderate hazard and shall include, but not be limited to, the following:Aircraft (manufacturing, not to include rep…
R.51-50-51-50-0308 Section 308—Institutional Group I.
2.7K chars
308.2 Institutional Group I-1. Institutional Group I-1 occupancy shall include buildings, structures or portions thereof for more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised environment and receive custodial care. Buildings of Group I-1 shall b…
R.51-50-51-50-0309 Section 309—Mercantile Group M.
0.8K chars
309.1 Mercantile Group M. Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and where the public has …
R.51-50-51-50-0310 Section 310—Residential Group R.
1.9K chars
310.3 Residential Group R-2. Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:Apartment housesCongregate living facilities (nontransient) with more than 16 occupantsBoarding houses (…
R.51-50-51-50-0312 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-01-090, § 51-50-0312, filed 12/12/19, effective 7/1/20; WSR 16-06-108 and 16-03-064, § 51-50-0312, filed 3/1/16 and 1/19/16, effective 7/1/16.]
R.51-50-51-50-0403 Section 403—High-rise buildings.
1.7K chars
403.4.8.3 Standby power loads. The following are classified as standby power loads:1. Ventilation and automatic fire detection equipment for smokeproof enclosures.2. Elevators.3. Where elevators are provided in a high-rise building for accessible means of egress, fire service acc…
R.51-50-51-50-0405 Section 405—Underground buildings.
0.6K chars
405.7.2 Smokeproof enclosure. Every required stairway serving floor levels more than 30 feet (9144 mm) below the finished floor of its level of exit discharge shall comply with the requirements for a smokeproof enclosure as provided in Sections 909.20 and 1023.12. Where interior …
R.51-50-51-50-0406 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-0406, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. WSR 07-01-091, § 51-50-0406, filed 12/19/06, effective 7/1/07.]
R.51-50-51-50-0407 Reserved.
0.8K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0407, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-0407, filed 12/12/19, effective 7/1/20; WSR 16-03-064, § 51-50-0407, filed 1/19/16, effective 7/…
R.51-50-51-50-0412 Section 412—Aircraft-related occupancies.
1.8K chars
412.2.2.1 Stairways. Stairways in airport traffic control towers shall be in accordance with Section 1011. Exit stairways shall be smokeproof enclosures complying with one of the alternatives provided in Section 909.20. Where interior exit stairways and ramps are pressurized in a…
R.51-50-51-50-0420 Section 420—Groups I-1, R-1, R-2, R-3, and R-4.
8.1K chars
420.2 Separation walls. Walls separating dwelling units in the same building, walls separating sleeping units in the same building and walls separating dwelling or sleeping units from other occupancies contiguous to them in the same building shall be constructed as fire partition…
R.51-50-51-50-0422 Section 422—Ambulatory care facilities.
0.7K chars
422.3.1 Means of egress. Where ambulatory care facilities require smoke compartmentation in accordance with Section 422.3, the fire safety evacuation plans provided in accordance with Section 1002.2 shall identify the building components necessary to support Sections 403 and 404 …
R.51-50-51-50-0427 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.077, 19.27.031 and 19.27.074. WSR 21-14-074 and 21-16-063, § 51-50-0427, filed 7/6/21 and 7/29/21, effective 8/6/21 and 8/29/21. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-0427, filed 1/19/16, effective 7/1/16.]
R.51-50-51-50-0429 Section 429—Electric vehicle charging infrastructure.
4.8K chars
429.1 General. The provisions of this section shall apply to the construction of new buildings and accessory structures, including parking lots and parking garages.Electric vehicle supply equipment (EVSE) shall be installed in accordance with applicable requirements of chapter 19…
R.51-50-51-50-0430 Section 430—Recycled materials.
0.6K chars
430.1 Recyclable materials, compost, and solid waste storage. Space shall be provided for the storage of recycled materials, compost, and solid waste for all new buildings.EXCEPTION:Group R-3 and Group U Occupancies.The storage area shall be designed to meet the needs of the occu…
R.51-50-51-50-0502 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-0502, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. WSR 07-01-091, § 51-50-0502, filed 12/19/06, effective 7/1/07.]
R.51-50-51-50-0503 Section 503—General building height and area limitations.
0.7K chars
503.1.4.1 Enclosure of occupied roof areas. Elements or structures enclosing the occupied roof areas shall not extend more than 48 inches (1220 mm) above the surface of the occupied roof.EXCEPTIONS:1. Penthouses constructed in accordance with Section 1511.2 and towers, domes, spi…
R.51-50-51-50-0504 Section 504—Building height and number of stories.
7.5K chars
Table 504.3Allowable Building Height in Feet Above Grade PlaneaOccupancy ClassificationType of ConstructionSeeFootnotesType IType IIType IIIType IVType VABABABABCHTABA, B, E, F, M, S, UNSbUL16065556555656565655040SUL1808575857527018085857060H-1, H-2, H-3, H-5NSc,dUL16065556555120…
R.51-50-51-50-0505 Section 0505—Mezzanines and equipment platforms.
0.6K chars
505.1 General.Mezzanines shall comply with Section 505.2. Equipment platforms shall comply with Section 505.3.EXCEPTION:Lofts in Group R occupancy dwelling units and sleeping units shall be permitted to comply with Section 420.14, subject to the limitations in Section 420.14.1.[S…
R.51-50-51-50-0506 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0506, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-0506, filed 12/12/19, effective 7/1/20; WSR 19-02-038, § 51-50-0506, filed 12/26/18, effective 7…
R.51-50-51-50-0508 Section 508—Mixed use and occupancy.
0.6K chars
508.5.1 Limitations. The following shall apply to live/work areas:1. The live/work unit is permitted to be not greater than 3,000 square feet (279 m) in area.2. The nonresidential area is permitted to be not more than 50 percent of the area of each live/work unit.3. The nonreside…
R.51-50-51-50-0509 Section 509—Incidental uses.
1.1K chars
Table 509.1Incidental UsesRoom or AreaSeparation and/or ProtectionDry type transformers over 112.5 kVA and required to be in a fire resistant room per NEC (NFPA 70) Section 450.21 (B)11 hour or provide automatic sprinkler system1Dry type transformers rated over 35,000 volts and o…
R.51-50-51-50-0510 Section 510—Special provisions.
2.8K chars
510.2 Horizontal building separation allowance. A building shall be considered as separate and distinct buildings for the purpose of determining area limitations, continuity of fire walls, limitation of number of stories and type of construction where the following conditions are…
R.51-50-51-50-0601 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0601, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 19-02-038, § 51-50-0601, filed 12/26/18, effective 7/1/19.]
R.51-50-51-50-0602 Section 602—Construction classification.
3.3K chars
602.4.2.2.2 Protected area. Interior faces of mass timber elements, including the inside face of exterior mass timber walls and mass timber roofs, shall be protected in accordance with Section 602.4.2.2.1.EXCEPTIONS:Unprotected portions of mass timber ceilings and walls complying…
R.51-50-51-50-0603 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0603, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-21-021, § 51-50-0603, filed 10/9/20, effective 11/9/20; WSR 20-01-090, § 51-50-0603, filed 12/12/19, effective 7…
R.51-50-51-50-0703 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0703, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 19-02-038, § 51-50-0703, filed 12/26/18, effective 7/1/19.]
R.51-50-51-50-0704 Section 704—Fire-resistance rating of structural members.
1.0K chars
704.6.1 Secondary (nonstructural) attachments to structural members. Where primary and secondary structural steel members require fire protection, any additional structural steel members having direct connection to the primary structural frame or secondary structural members shal…
R.51-50-51-50-0705 Section 705—Exterior walls.
6.1K chars
705.2 Projections.Cornices, roof and eave overhangs, projecting floors above, exterior balconies and similar projections extending beyond the exterior wall shall conform to the requirements of this section and Section 1405. Exterior egress balconies and exterior exit stairways an…
R.51-50-51-50-0706 Section 706—Fire walls.
1.1K chars
706.3 Materials.Fire walls that separate a building of Type I or II construction from a building of any construction type shall be of any approved noncombustible materials. Other fire walls shall be built of materials consistent with the types permitted for the type of constructi…
R.51-50-51-50-07070 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-07070, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-07070, filed 12/12/19, effective 7/1/20.]
R.51-50-51-50-0708 Section 708—Reserved.
0.5K chars
[Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-0708, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, amended and recodified as § 51-50-0708, filed 1/20/10, effective 7/1/10. Statutory A…
R.51-50-51-50-0710 Section 710—Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-0710, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-0710, filed 1/20/10, effective 7/1/10.]
R.51-50-51-50-0713 Section 713—Shaft enclosures.
1.4K chars
713.13.7 Chute venting and roof termination. The full diameter of waste and linen chutes shall extend a minimum of 3 feet (0.92 m) above the building roof and be gravity vented in accordance with International Mechanical Code Section 515.EXCEPTIONS:1. Where mechanically ventilate…
R.51-50-51-50-0716 Section 716—Opening protectives.
1.5K chars
716.2.6.1 Door closing.Fire doors shall be latching and self- or automatic-closing in accordance with this section.EXCEPTIONS:1. Fire doors located in common walls separating sleeping units in Group R-l shall be permitted without automatic- or self-closing devices. 2. The elevato…
R.51-50-51-50-0717 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0717, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-0717, filed 12/12/19, effective 7/1/20.]
R.51-50-51-50-0718 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-0718, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 19-02-038, § 51-50-0718, filed 12/26/18, effective 7/1/19.]