20.30.A.880-880-1012 20 CAR § 880-1012. Feedwater supply
1.0K chars
20 CAR § 880-1012. Feedwater supply. (a)(1) A boiler having more than five hundred square feet (500 ft2) of water heating surface shall have at least two (2) means of feeding water. (2) Each source of feeding shall be capable of supplying water to the boiler at a pressure of thre…
20.30.A.880-880-1013 20 CAR § 880-1013. Water fronts
0.3K chars
20 CAR § 880-1013. Water fronts. (a) Each boiler fitted with a water-jacketed boiler-furnace mouth protector, or similar appliance, having valves on the pipes connecting them to the boiler, shall have these valves locked or sealed open. (b) Such valves, when used, shall be of the…
20 CAR § 880-1014. Water column pipes
3.2K chars
20 CAR § 880-1014. Water column pipes. (a)(1) The minimum size of pipes connecting the water column to a boiler shall be one inch (1”). (2) For pressures of four hundred pounds (400 lbs.), or over, lower water column connections to drums shall be provided with shields, sleeves, o…