R.175.430 Section 175.430: Clearance Required for USTs
2.7K chars
Section 175.430 Clearance Required for USTs a) Distance to Basements. No UST shall be less than 20 feet from any basement, cellar, pit or below-grade excavation on or off the property. b) Distance to Sewers. Individual tanks and piping shall be buried so that the tops of the tank…
R.175.435 Section 175.435: Testing of Tanks or Lines
0.5K chars
Section 175.435 Testing of Tanks or Lines a) The use of air or non-inert gases to test underground storage tanks or piping containing, or that have contained, flammable or combustible liquids is prohibited. b) Approved tank or line precision testing with inert gases (nitrogen and…
R.175.440 Section 175.440: Venting of Tanks
3.1K chars
Section 175.440 Venting of Tanks a) Vents 1) Each tank shall be provided with a separate working vent pipe, connected with the top of the tank and carried up to the outer air. Except as allowed in subsection (b), manifolding of working vents is prohibited. The pipe shall be arran…