R.481—382.31 Judicial review. Judicial review of the board’s decision may be sought in
1.5K chars
accordance with the terms of Iowa Code chapter 17A. 382.31(1) Consistent with Iowa Code section 17A.19(3), if a party does not file a timely application for rehearing, a judicial review petition must be filed with the district court within 30 days after the issuance of the board’…
R.481—382.4 Delivery of notice. Delivery of the notice of hearing by the board constitutes the
0.3K chars
commencement of a contested case proceeding. Delivery may be executed by regular mail. The notice shall be delivered to the appellant, the appellant’s attorney, if known, and the director. [ARC 8886C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—382.5 Contents of notice. The notice of hearing will contain a statement of the time, place,
0.4K chars
and nature of the hearing and a brief statement of the matters asserted. It is the appellant’s burden on appeal to prove compliance with all applicable statutory provisions, administrative rules, and ASME code sections. The notice shall contain a reference to the applicable statu…
R.481—382.6 Scope of issues. Only those issues raised before the director in the petition for
0.2K chars
reconsideration will be considered preserved for appeal to the board. [ARC 8886C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—382.7 File transmitted to the board. Upon receipt of a notice of hearing issued by the
0.5K chars
board, the director shall within 30 days forward to the board and all parties of record to the appeal copies of the challenged inspection report, the appellant’s petition for reconsideration and all supporting documents, all other documents collected by the director in ruling on …
R.481—382.8 Legal representation. Any private party to a contested case is entitled to legal
0.1K chars
representation at the discretion and expense of that party. [ARC 8886C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—382.9 Presiding officer
3.4K chars
382.9(1) The presiding officer in all contested cases is the board, a panel of board members, or an administrative law judge assigned by the department of inspections, appeals, and licensing. When board members act as presiding officer, they conduct the hearing and issue either a…
R.481—390.1 Purpose and scope. These rules institute administrative and operational procedures for
0.5K chars
implementation of Iowa Code chapter 89. An object is not considered “under pressure” and is not within the scope of Iowa Code chapter 89 when there is clear evidence that the manufacturer did not intend it to be operated at more than 3 psi and the object is operating at 3 pounds …
R.481—390.10 Reporting requirements
3.3K chars
390.10(1) Control and safety device reports. Documentation required by this subrule shall be kept on site and be available for inspection by the department or special inspectors. The owner or user shall mail a copy of the documentation required by this subrule to the department. …
R.481—390.11 Publications available for review. Pursuant to Iowa Code section 89.5(3), the standards,
0.2K chars
codes, and publications adopted by reference in these rules are available for review in the office of the department, 6200 Park Avenue, Suite 100, Des Moines, Iowa. [ARC 8887C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—390.12 Notice prior to installation. Written notice of intent to install objects subject to the
0.4K chars
jurisdiction of Iowa Code chapter 89 shall be provided to the director at least ten days before installation. Written notice is accomplished by completing and submitting to the director either: 1. The form designated by the director, or 2. The National Board’s Boiler Installation…
R.481—390.13 Temporary objects
0.8K chars
390.13(1) Certificate to operate. A certificate to operate a temporary object expires one year from the date of issuance or when the temporary object is disconnected. 390.13(2) Inspections. a. An internal inspection and hydrostatic test pursuant to the National Board Inspection C…
R.481—390.14 Conversion of a power boiler to a low-pressure boiler. The following requirements
2.6K chars
apply to the conversion of a power boiler to a low-pressure boiler. The owner shall comply with the requirements of subrule 390.15(1) for each conversion. In addition, the owner shall comply with the requirements of subrule 390.15(2) if the converted object will be located outsid…
R.481—390.15 Definitions regarding objects. The following definitions govern classification and status
4.5K chars
of objects in Iowa. To the extent they do not conflict with the definitions contained in Iowa Code chapter 89, the definitions in this rule are applicable to the rules contained in 481—Chapters 390 through 395. “Active status” means an object is physically attached to the system …
R.481—390.2 Definitions. To the extent they do not conflict with the definitions contained in
9.4K chars
Iowa Code chapter 89, the definitions in this rule are applicable to the rules contained in 481—Chapters 390 through 395. “Alteration” means a change in the object described on the original manufacturer’s data report that affects the pressure-retaining capability of the pressure-…
R.481—390.3 Iowa identification numbers. All objects shall be identified by an Iowa identification
0.6K chars
number. State inspectors and special inspectors shall assign identification numbers as directed by the department to all jurisdictional objects that lack numbers. Identification numbers shall be attached in plain view to the object using one of the following methods: 1. A yellow …
R.481—390.4 Preinspection owner or user preparation
3.9K chars
390.4(1) Preparation of objects. Each owner or user shall ensure that each object covered by Iowa Code chapter 89 is prepared for inspection pursuant to this rule. 390.4(2) Confined space and lockout, tagout procedures. a. If an object is a non-permit-required confined space or a…
R.481—390.5 Inspections
8.6K chars
390.5(1) General. All boilers and unfired steam pressure vessels covered by Iowa Code chapter 89 are inspected according to the requirements of the National Board Inspection Code (2021), which is hereby adopted by reference. A department inspector or special inspector must perfor…
R.481—390.6 Fees
1.9K chars
390.6(1) Special inspector commission fee. A $55 fee shall be paid annually to the director to obtain a special inspector commission pursuant to Iowa Code section 89.7. 390.6(2) Certificate fee. A $40 fee shall be paid for each one-year certificate, an $80 fee shall be paid for e…
R.481—390.7 Certificate. No boiler or pressure vessel shall be operated without a current, valid
0.4K chars
certificate to operate. A certificate to operate will not be issued until the boiler or pressure vessel is in compliance with the applicable rules and all fees have been paid. The current certificate to operate or a copy of the current certificate to operate shall be conspicuousl…
R.481—390.8 Special inspector commissions
6.8K chars
390.8(1) Definition of “reputable insurance company.” As used in this rule, “reputable insurance company” means a company recognized by the Iowa insurance division as a licensed insurer, a risk retention group, an alien surplus lines insurer, or a surplus lines insurer. 390.8(2) …
R.481—390.9 Quality reviews, surveys and audits
1.7K chars
390.9(1) An entity that manufactures or repairs boilers, pressure vessels or related equipment may request quality reviews, surveys or audits from certifying organizations such as the ASME or the National Board. The department is authorized to conduct the quality reviews, surveys…
R.481—391.1 Codes and code cases adopted by reference
3.0K chars
391.1(1) ASME boiler and pressure vessel codes adopted by reference. The ASME Boiler and Pressure Vessel Code (2021), including Code Cases, is adopted by reference. Regulated objects shall be designed and constructed in accordance with the ASME Boiler and Pressure Vessel Code (20…
R.481—391.10 Air and ventilation requirements
3.8K chars
391.10(1) Notice concerning other rules. The division and the Iowa department of public safety both enforce requirements concerning air and ventilation. Objects that are covered by both sets of rules must comply with both sets of rules. 391.10(2) Documentation. Documentation of c…
R.481—391.11 Condensate return tank. Condensate return tanks shall be equipped with at least two
0.2K chars
vents or a vent and overflow pipe to protect against a loose float plugging a single connection. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—391.12 Conditions not covered. Any condition not governed by these rules is governed by the
0.1K chars
construction or installation code. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—391.13 English language and U.S. customary units required. All documentation supplied for
0.4K chars
the unit including but not limited to the manufacturers’ data report, drawings, parts lists, installation manuals, and operating manuals shall be in English, and all measurements in U.S. customary units. All pressure gages, thermometers and other controls and safety devices shall…
R.481—391.14 National Board registration. Except for cast iron boilers and cast aluminum boilers, all
0.1K chars
objects shall be registered with the National Board. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—391.15 ASME stamp. All objects shall bear the appropriate ASME stamp. Objects shall not be
2.5K chars
utilized in a manner inconsistent with the stamp. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25] These rules are intended to implement Iowa Code chapter 89. [Filed emergency 12/26/97 after Notice 11/19/97—published 1/14/98, effective 1/1/98] …
R.481—391.2 Safety appliance
0.4K chars
391.2(1) No person shall remove, disable or tamper with a required safety appliance except for the purpose of repair or inspection. 391.2(2) An object shall not be operated unless all required and installed safety appliances are properly functional and operational. [ARC 8894C, IA…
R.481—391.3 Blowoff equipment. The blowdown from an object that enters a sanitary sewer system or
0.9K chars
blowdown that is considered a hazard to life or property shall pass through blowoff equipment that will reduce pressure and temperature. The temperature of the water leaving the blowoff equipment shall not exceed 150 degrees F. If the local jurisdiction has a temperature limit of…
R.481—391.4 Location of discharge piping outlets. The discharge from safety valves, safety relief
0.6K chars
valves, blowoff pipes and other outlets shall comply with the following: 391.4(1) The discharge piping terminates at a safe point of discharge. 391.4(2) When the safety valve or temperature and pressure relief valve discharge is piped away from the object to a safe point of disch…
R.481—391.5 Pipe, valve, and fitting requirements. Pipes, valves, and fittings subject to the effects of
0.2K chars
galvanic action shall not be used on objects covered by these rules. Dielectric fittings shall be used where dissimilar metals are joined. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—391.6 Repairs and alterations to unfired steam pressure vessels. No single repair of an
0.2K chars
unfired steam pressure vessel shall involve replacement of more than 50 percent of the OEM’s pressure- retaining boundary. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—391.7 Plugging boiler tubes. This rule does not apply to tubes in headers of economizers,
1.2K chars
evaporators, superheaters, or reheaters. 391.7(1) General requirements. a. Leaky tubes are replaced or plugged. b. Tube plugs are made of a material that is compatible with the material of the boiler tube being plugged and shall be welded into place or manufactured to be expanded…
R.481—391.8 Equipment room. This rule applies to existing and new installations except as noted in
2.9K chars
subrule 391.10(1). 391.8(1) Clearance requirements. a. This paragraph applies to objects installed after December 1, 2022. Minimum clearance on all sides of objects will be 36 inches, or the manufacturer’s recommended service clearances if they allow sufficient room for inspectio…
R.481—391.9 Fall protection. The owner or user shall provide safe access to object parts over four feet
0.1K chars
high consistent with applicable federal safety regulations. [ARC 8894C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—392.1 Scope. This chapter applies to all power boilers, and it applies to miniature power boilers
0.2K chars
installed on and after September 20, 2006. 481—Chapter 393 applies to miniature power boilers installed prior to September 20, 2006. [ARC 8888C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25]
R.481—392.10 Steam stop valve requirements. This rule applies to power boilers installed prior to July
0.9K chars
1, 1983. Each steam outlet from a boiler, except safety valve and water-column connections, will be fitted with a stop valve located as close as practicable to the boiler. When a stop valve is so located that water can accumulate, ample drains will be provided. The drainage will …
R.481—392.11 Blowoff connection requirements. This rule applies to power boilers installed prior to
2.8K chars
July 1, 1983. Each boiler will have a blowoff pipe fitted with valve or cock, in direct connection with the lowest water space practicable. 392.11(1) When the maximum allowable working pressure exceeds 125 psig, the blowoff pipe will be at least schedule 80 from the boiler to the…
R.481—392.2 Codes adopted by reference. The codes listed in 481—Chapter 391 apply to objects
0.1K chars
covered by this chapter. [ARC 8888C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/25; Editorial change: IAC Supplement 7/9/25]
R.481—392.3 Maximum allowable working pressure for steel boilers. This rule applies to power
2.0K chars
boilers installed prior to July 1, 1983. A boiler constructed with fusion-welded seams and not radiographed and stress relieved during construction shall not be operated at a pressure in excess of 15 pounds per square inch. Boilers with fusion-welded seams that are radiographed a…
R.481—392.4 Maximum allowable working pressure and temperature for cast iron headers and
0.6K chars
mud drums. This rule applies to power boilers installed prior to July 1, 1983. 392.4(1) Tube boiler. The maximum allowable working pressure on a watertube boiler, the tubes of which are secured in cast iron or malleable iron headers or that have cast iron mud drums, will not exce…
R.481—392.5 Rivets. This rule applies to power boilers installed prior to July 1, 1983. When the
0.3K chars
diameter of the rivet holes in the longitudinal joints of a boiler is not known, the diameter and cross- sectional area of rivets, after driving, shall be selected from ASME Code, Section I (1971). [ARC 8888C, IAB 2/19/25, effective 3/26/25; Editorial change: IAC Supplement 7/9/2…
R.481—392.6 Safety valve requirements. This rule applies to power boilers installed prior to July 1,
5.0K chars
1983. 392.6(1) The use of weighted-lever safety valves or safety valves having either the seat or disk of cast iron is prohibited. All power boilers will have direct, springloaded, pop-type safety valves that conform to the construction or installation code. 392.6(2) Each boiler …
R.481—392.7 Boiler feeding requirements. This rule applies to power boilers installed prior to July 1,
1.6K chars
1983. 392.7(1) Each boiler will have a feed supply that will permit it to be fed at any time while under pressure. A boiler having more than 500 square feet of water-heating surface will have at least two means of feeding, one of which will be an approved feed pump, injector, or …
R.481—392.8 Water level indicator requirements. This rule applies to power boilers installed prior to
0.9K chars
July 1, 1983. Outlet connections that allow the escape of an appreciable amount of steam or water will not be placed on the piping. However, this rule does not prohibit the installation of damper regulators, feed water regulators, low-water fuel cutouts, drains, or steam gages. T…
R.481—392.9 Pressure gage requirements. This rule applies to power boilers installed prior to July 1,
1.6K chars
1983. Each boiler will have a pressure gage so located that the gage is readable. The pressure gage will be installed so that it will at all times indicate the pressure in the boiler. Each steam boiler will have the pressure gage connected to the steam space or to the water colum…
R.481—393.1 Scope
0.7K chars
393.1(1) This chapter sets forth requirements in addition to those contained in 481—Chapter 392 for boilers that: a. Have a heating surface of 20 square feet or less; b. Have a gross volume of 5 cubic feet or less, excluding casing and insulation; c. Have an inside shell diameter…
R.481—393.10 Fixtures and fittings. All valves, pipe fittings, and appliances connected to a miniature
1.8K chars
power boiler shall be equal to at least the minimal requirements of the construction or installation code and shall be rated for not less than the maximum allowable working pressure of the miniature power boiler. In no case shall the rating be for less than 125 pounds. [ARC 8889C…