26,490 sections across 2,319 Louisiana regulatory chapters.
Chapter 303. Transportation of Hazardous Liquids by Pipeline―Pressure Testing [49 CFR Part 195 Subpart E]-30308 Testing of Tie-Ins [49 CFR 195.308]
0.1K chars
A. Pipe associated with tie-ins must be pressure tested, either with the section to be tied in or separately. [49 CFR 195.308]
Chapter 303. Transportation of Hazardous Liquids by Pipeline―Pressure Testing [49 CFR Part 195 Subpart E]-30310 Records [49 CFR 195.310]
1.2K chars
A. A record must be made of each pressure test required by this Chapter, and the record of the latest test must be retained as long as the facility tested is in use. [49 CFR 195.310(a)] B. The record required by §30310.A must include: [49 CFR 195.310(b)] 1. the pressure recording…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30105 For operators installing valves in accordance with §30258.C, §30258.D, or that are subject to the requirements in §30418, those procedures should provide for rupture identification as soon as practicable. [49 CFR 195.402(e)(4)]
2.4K chars
5. control of released hazardous liquid or carbon dioxide at an accident scene to minimize the hazards, including possible intentional ignition in the cases of flammable highly volatile liquid; [49 CFR 195.402(e)(5)] 6. minimization of public exposure to injury and probability of…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30118 [49 CFR 195.452(a)(3)]
3.7K chars
4. Low stress pipelines as specified in § 30118. [49 CFR 195.452(a)(4)] B. What program and practices must operators use to manage pipeline integrity? Each operator of a pipeline covered by this Section must: [49 CFR 195.452(b)] 1. develop a written integrity management program t…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30122 [49 CFR 195.418(b)(3)]
0.7K chars
4. Crossovers. An operator may use a manual valve as an alternative equivalent technology for a crossover connection if, during normal operations, the valve is closed to prevent the flow of hazardous liquid or carbon dioxide with a locking device or other means designed to preven…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30123 [49 CFR 195.418(b)(4)]
0.3K chars
C. Manual operation upon identification of a rupture. Operators using a manual valve as an alternative equivalent technology pursuant to Subsection A of this Section must develop and implement operating procedures and appropriately designate and locate nearby personnel to ensure …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30133 [49 CFR 195.402(f)]
0.2K chars
G. Exception. An operator of a gathering line must only comply with the requirements of §30402 effective as of October 4, 2022, and need not comply with the other requirements of this section. [49 CFR 195.402(g)]
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-301418 [49 CFR 195.452(i)(4)(ii)]
9.1K chars
c. An operator may request an exemption from the compliance deadline requirements of this section if it can demonstrate to PHMSA, in accordance with the notification procedures in §30418, that installing an EFRD by that compliance deadline would be economically, technically, or o…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30161 However, for steel pipe in pipelines being converted under §30111, if one or more factors of the design formula (§30161) are unknown, one of the following pressures is to be used as design pressure: [49 CFR 195.406(a)(1)]
1.5K chars
a. 80 percent of the first test pressure that produces yield under section N 5.0 of appendix N of ASME B31.8 (incorporated by reference, see §507), reduced by the appropriate factors in §30161.A and E; or [49 CFR 195.406(a)(1)(i)] b. if the pipe is 12-3/4 in. (324 mm.) or less ou…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30304 [49 CFR 195.452(d)(1)]
20.6K chars
2. Newly Identified Areas. If an operator obtains information (whether from the information analysis required under Subsection G of this section, Census Bureau maps, or any other source) demonstrating that the area around a pipeline segment has changed to meet the definition of a…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30400 Scope [49 CFR 195.400]
0.1K chars
A. This Chapter prescribes minimum requirements for operating and maintaining pipeline systems constructed with steel pipe. [49 CFR 195.400]
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30401 General Requirements [49 CFR 195.401]
2.1K chars
A. No operator may operate or maintain its pipeline systems at a level of safety lower than that required by this Chapter and the procedures it is required to establish under §30402.A. [49 CFR 195.401(a)] B. An operator must make repairs on its pipeline system according to the fo…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30402 An operator must develop the procedures no later than August 1, 2011, and must implement the procedures according to the following schedule. The procedures required by Subsections and Paragraphs B, C.5, D.2, D.3, F and G of this Section must be implemented no later than October 1, 2011. The procedures required by Paragraphs C.1 through C.4, D.1, D.4, and E must be implemented no later than August 1, 2012. The training procedures required by Subsection H must be implemented no later than August 1, 2012, except that any training required by another Paragraph of this Section must be implemented no later than the deadline for that Paragraph. [49 CFR 195.446(a)]
9.1K chars
B. Roles and Responsibilities. Each operator must define the roles and responsibilities of a controller during normal, abnormal, and emergency operating conditions. To provide for a controller’s prompt and appropriate response to operating conditions, an operator must define each…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30403 Emergency Response Training [49 CFR 195.403]
1.9K chars
A. Each operator shall establish and conduct a continuing training program to instruct emergency response personnel to: [49 CFR 195.403(a)] 1. carry out the emergency procedures established under §30402 that relate to their assignments; [49 CFR 195.403(a)(1)] 2. know the characte…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30404 Maps and Records [49 CFR 195.404]
1.8K chars
A. Each operator shall maintain current maps and records of its pipeline systems that include at least the following information: [49 CFR 195.404(a)] 1. location and identification of the following pipeline facilities: [49 CFR 195.404(a)(1)] a. breakout tanks; [49 CFR 195.404(a)(…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30405 Protection against Ignitions and Safe Access/Egress Involving Floating Roofs [49 CFR 195.405]
1.1K chars
A. After October 2, 2000, protection provided against ignitions arising out of static electricity, lightning, and stray currents during operation and maintenance activities involving aboveground breakout tanks must be in accordance with API RP 2026 (incorporated by reference, see…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30406 Maximum Operating Pressure [49 CFR 195.406]
0.3K chars
A. Except for surge pressures and other variations from normal operations, no operator may operate a pipeline at a pressure that exceeds any of the following: [49 CFR 195.406(a)] 1. the internal design pressure of the pipe determined in accordance with
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30408 Communications [49 CFR 195.408]
0.9K chars
A. Each operator must have a communication system to provide for the transmission of information needed for the safe operation of its pipeline system. [49 CFR 195.408(a)] B. The communication system required by §30408.A must, as a minimum, include means for: [49 CFR 195.408(b)] 1…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30410 Line Markers [49 CFR 195.410]
1.7K chars
A. Except as provided in §30410.B, each operator shall place and maintain line markers over each buried pipeline in accordance with the following: [49 CFR 195.410(a)] 1. markers must be located at each public road crossing, at each railroad crossing, and in sufficient number alon…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30412 Inspection of Rights-of-Way and Crossings under Navigable Waters [49 CFR 195.412]
0.5K chars
A. Each operator shall, at intervals not exceeding three weeks, but at least 26 times each calendar year, inspect the surface conditions on or adjacent to each pipeline right-of-way. Methods of inspection include walking, driving, flying or other appropriate means of traversing t…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30413 Underwater Inspection and Reburial of Pipelines in the Gulf of America and Its Inlet[49 CFR 195.413]
2.3K chars
A. Except for gathering lines of 4 1/2 inches (114 mm) nominal outside diameter or smaller, each operator shall prepare and follow a procedure to identify its pipelines in the Gulf of America and its inlets in waters less than 15 feet (4.6 meters) deep as measured from mean low w…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30414 Inspections of Pipelines in Areas Affected by Extreme Weather and Natural Disasters[49 CFR 195.414]
2.6K chars
A. General. Following an extreme weather event or natural disaster that has the likelihood of damage to infrastructure by the scouring or movement of the soil surrounding the pipeline, such as a named tropical storm or hurricane; a flood that exceeds the river, shoreline, or cree…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30416 Pipeline Assessments[49 CFR 195.416]
0.9K chars
A. Scope. This section applies to onshore line pipe that can accommodate inspection by means of in-line inspection tools and is not subject to the integrity management requirements in § 30452. [49 CFR 195.416(a)] B. General. An operator must perform an initial assessment of each …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30417 Notification of Potential Rupture[49 CFR 195.417]
1.9K chars
A. As used in this part, a notification of potential rupture means the notification to, or observation by, an operator (e.g., by or to its controller(s) in a control room, field personnel, nearby pipeline or utility personnel, the public, local responders, or public authorities) …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30418 Valves: Onshore Valve Shut-Off For Rupture Mitigation [49 CFR 195.418]
0.5K chars
A. Applicability. For newly constructed and entirely replaced onshore hazardous liquid or carbon dioxide pipeline segments, as defined at §30105, with diameters of 6 inches or greater that could affect high-consequence areas or are located in high consequence areas (HCA), and tha…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30419 Operators are not required to close the alternative equivalent technology fully during the drill; a minimum 25 percent valve closure is sufficient to demonstrate compliance with the drill requirements unless the operator has operational information that requires an additional closure percentage for maintaining reliability. The response drill must occur at least once each calendar year, at intervals not to exceed 15 months. Operators must include in their written procedures the method they use to randomly select which alternative equivalent technology is tested in accordance with this Paragraph; [49 CFR 195.420(e)(2)]
2.4K chars
3. if the 30-minute-maximum response time cannot be achieved in the drill, the operator must revise response efforts to achieve compliance with §30419 no later than 12 months after the drill. Alternative valve shut-off measures must be in accordance with Subsection F of this Sect…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30420 Valve Maintenance [49 CFR 195.420]
2.3K chars
A. Each operator shall maintain each valve that is necessary for the safe operation of its pipeline systems in good working order at all times. [49 CFR 195.420(a)] B. Each operator must, at least twice each calendar year, but at intervals not exceeding 7 1⁄2 months, inspect each …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30422 Pipeline Repairs [49 CFR 195.422]
0.4K chars
A. Each operator shall, in repairing its pipeline systems, insure that the repairs are made in a safe manner and are made so as to prevent damage to persons or property. [49 CFR 195.422(a)] B. No operator may use any pipe, valve, or fitting, for replacement in repairing pipeline …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30424 Pipe Movement [49 CFR 195.424]
1.5K chars
A. No operator may move any line pipe, unless the pressure in the line section involved is reduced to not more than 50 percent of the maximum operating pressure. [49 CFR 195.424(a)] B. No operator may move any pipeline containing highly volatile liquids where materials in the lin…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30426 Scraper and Sphere Facilities [49 CFR 195.426]
0.4K chars
A. No operator may use a launcher or receiver that is not equipped with a relief device capable of safely relieving pressure in the barrel before insertion or removal of scrapers or spheres. The operator must use a suitable device to indicate that pressure has been relieved in th…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30428 Overpressure Safety Devices and Overfill Protection Systems [49 CFR 195.428]
1.8K chars
A. Except as provided in §30428.B, each operator shall, at intervals not exceeding 15 months, but at least once each calendar year, or in the case of pipelines used to carry highly volatile liquids, at intervals not to exceed seven and one-half months, but at least twice each cal…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30430 Firefighting Equipment [49 CFR 195.430]
0.4K chars
A. Each operator shall maintain adequate firefighting equipment at each pump station and breakout tank area. The equipment must be: [49 CFR 195.430] 1. in proper operating condition at all times; [49 CFR 195.430(a)] 2. plainly marked so that its identity as firefighting equipment…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30432 Inspection of In-Service Breakout Tanks [49 CFR 195.432]
2.8K chars
A. Except for breakout tanks inspected under §30432 B and C, each operator shall, at intervals not exceeding 15 months, but at least once each calendar year, inspect each in-service breakout tank. [49 CFR 195.432(a)] B. Each operator must inspect the physical integrity of in-serv…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30434 Signs [49 CFR 195.434]
0.3K chars
A. Each operator must maintain signs visible to the public around each pumping station and breakout tank area. Each sign must contain the name of the operator and a telephone number (including area code) where the operator can be reached at all times. [49 CFR 195.434]
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30436 Security of Facilities [49 CFR 195.436]
0.2K chars
A. Each operator shall provide protection for each pumping station and breakout tank area and other exposed facility (such as scraper traps) from vandalism and unauthorized entry. [49 CFR 195.436]
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30438 Smoking or Open Flames [49 CFR 195.438]
0.2K chars
A. Each operator shall prohibit smoking and open flames in each pump station area and each breakout tank area where there is a possibility of the leakage of a flammable hazardous liquid or of the presence of flammable vapors. [49 CFR 195.438]
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30440 Public Awareness [49 CFR 195.440]
2.8K chars
A. Each pipeline operator must develop and implement a written continuing public education program that follows the guidance provided in the American Petroleum Institute’s (API) Recommended Practice (RP) 1162 (incorporated by reference, see §30107). [49 CFR 195.440(a)] B. The ope…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30442 Damage Prevention Program [49 CFR 195.442]
4.0K chars
A. Except as provided in §30442.D, each operator of a buried pipeline must carry out, in accordance with this section, a written program to prevent damage to that pipeline from excavation activities. For the purpose of this Section, the term excavation activities includes excavat…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30444 Leak Detection [49 CFR 195.444]
1.1K chars
A. Scope. Except for offshore gathering and regulated rural gathering pipelines, this section applies to all hazardous liquid pipelines transporting liquid in single phase (without gas in the liquid). [49 CFR 195.444(a)] B. General. A pipeline must have an effective system for de…
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30446 Control Room Management [49 CFR 195.446]
0.5K chars
A. General. This Section applies to each operator of a pipeline facility with a controller working in a control room who monitors and controls all or part of a pipeline facility through a SCADA system. Each operator must have and follow written control room management procedures …
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30450 High Consequence Areas―Definitions [49 CFR Part 195.450]
0.1K chars
A. The following definitions apply to this Section and
Chapter 304. Transportation of Hazardous Liquids by Pipeline―Operation and Maintenance [49 CFR Part 195 Subpart F]-30454 Integrity Assessments for Certain Underwater Hazardous Liquid Pipeline Facilities Located in High Consequence Areas [49 CFR 195.454]
1.1K chars
A. Notwithstanding any pipeline integrity management program or integrity assessment schedule otherwise required under § 30452, each operator of any underwater hazardous liquid pipeline facility located in a high consequence area that is not an offshore pipeline facility and any …
Chapter 305. Admission Review-30501 Admission Process
2.5K chars
A. ICF/MRs will be subject to a review of each client's need for ICF/MR services. B. Interdisciplinary Team (ID Team). Before admission to an ICF/MR, or before authorization for payment, an interdisciplinary team of health professionals will make a comprehensive medical, social a…
Chapter 305. Admission Review-30503 Certification Requirements
7.8K chars
A. The following documentation and procedures are required to obtain medical certification for ICF/MR Medicaid vendor payment. The documentation should be submitted to the appropriate HSS regional office. 1. Social evaluation: a. must not be completed more than 90 days prior to a…
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30501 Scope [49 CFR 195.501]
0.6K chars
A. This Subchapter prescribes the minimum requirements for operator qualification of individuals performing covered tasks on a pipeline facility. [49 CFR 195.501(a)] B. For the purpose of this Subchapter, a covered task is an activity, identified by the operator, that: [49 CFR 19…
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30503 Definitions [49 CFR 195.503]
0.8K chars
Abnormal Operating Condition―a condition identified by the operator that may indicate a malfunction of a component or deviation from normal operations that may: 1. indicate a condition exceeding design limits; or 2. result in a hazard(s) to persons, property, or the environment. …
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30505 Qualification Program [49 CFR 195.505]
2.0K chars
A. Each operator shall have and follow a written qualification program. The program shall include provisions to: 1. identify covered tasks; [49 CFR 195.505(a)] 2. ensure through evaluation that individuals performing covered tasks are qualified; [49 CFR 195.505(b)] 3. allow indiv…
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30507 Record Keeping [49 CFR 195.507]
0.7K chars
A. Each operator shall maintain records that demonstrate compliance with this Subchapter. 1. Qualification records shall include: [49 CFR 195.507(a)] a. identification of qualified individuals(s); [49 CFR 195.507(a)(1)] b. identification of the covered tasks the individual is qua…
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30509 General [49 CFR 195.509]
0.8K chars
A. Operators must have a written qualification program by April 27, 2001. The program must be available for review by the administrator or by a state agency participating under 49 U.S.C. Chapter 601 if the program is under the authority of that state agency [49 CFR 195.509(a)]. B…
Chapter 305. Transportation of Hazardous Liquids by Pipeline—Qualification of Pipeline Personnel [49 CFR Part 195 Subpart G] and Corrosion Control[49 CFR Part 195 Subpart H]-30551 What do the regulations in this Subchapter cover? [49 CFR 195.551]
0.1K chars
A. This Subchapter prescribes minimum requirements for protecting steel pipelines against corrosion.