R.8-901 IFC Section 202 General definitions
0.5K chars
8-901. IFC Section 202 General definitions. Recreational Fire: An outdoor fire burning materials other than rubbish where the fuel being burned is not contained in an incinerator, outdoor fireplace, portable outdoor fireplace, barbeque grill or barbeque pit and has a total fuel a…
R.8-902 IFC Section 202 General definitions
0.4K chars
8-902. IFC Section 202 General definitions. Primitive Camp Structure: Shall include any structure permanent or temporary in nature, used for outdoor camping (transient), open on at least one side with no fully enclosed habitable spaces, less than 400 square feet under roof, and n…
R.8-903 IFC Section 202 General definitions
0.2K chars
8-903. IFC Section 202 General definitions. Add to the listing of A-3 occupancies: Structures, without a commercial kitchen, used in agritourism activity as defined by S.C. Code Ann. 46-53-10(1).
R.8-904 IFC Section 315.3.3 Equipment rooms. Material shall not be stored in boiler rooms, mechani-
0.3K chars
8-904. IFC Section 315.3.3 Equipment rooms. Material shall not be stored in boiler rooms, mechani- cal rooms, electrical equipment rooms or in fire command centers as specified in Section 508.1.5. Rooms shall be labeled with appropriate signage ‘‘No storage allowed.’’
R.8-905 IFC Section 319.11 Clearance requirements
0.3K chars
8-905. IFC Section 319.11 Clearance requirements. Mobile cooking operations shall be separated from buildings, structures, canopies, tents, combustible materials, vehicles, and other cooking operations by a minimum of 10 feet. Exhaust shall be directed away from openings, air int…
R.8-906 IFC Section 503.1.2 Additional access
0.8K chars
8-906. IFC Section 503.1.2 Additional access. The fire code official is authorized to require more than one fire apparatus access road based on the potential for impairment of a single road by vehicle congestion, condition of terrain, climatic conditions or other factors that cou…
R.8-907 IFC Section 503.1.2.1 One- or two-family dwelling residential developments having less than
1.2K chars
8-907. IFC Section 503.1.2.1 One- or two-family dwelling residential developments having less than 50 units. Developments of one- or two-family dwellings where the number of dwelling units does not exceed 50 shall be permitted to have a single approved fire apparatus access road …
R.8-908 IFC Section 503.2.1 Dimensions
0.3K chars
8-908. IFC Section 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm) except for approved security gates in accordance with Section 503.6 and an unobstructed vertical clearance of not less than 13 feet 6 inches (411…
R.8-909 IFC Section 507.1 Required water supply
0.7K chars
8-909. IFC Section 507.1 Required water supply. An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises on which facilities, buildings, or portions of buildings are hereafter constructed or moved into or within the ju…
R.8-910 IFC Section 507.5.1 Where required
1.3K chars
8-910. IFC Section 507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 500 feet (152 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior…
R.8-911 IFC Section 507.5.1.1 Hydrant for standpipe systems
0.4K chars
8-911. IFC Section 507.5.1.1 Hydrant for standpipe systems. Buildings equipped with a standpipe or fire sprinkler system installed in accordance with Section 903 or 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections. Exception : The dista…
R.8-912 IFC Section 507.5.4 Obstruction
0.3K chars
8-912. IFC Section 507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. No parking shall be allowed within 15 …
R.8-913 IFC Section 607.1 General
0.5K chars
8-913. IFC Section 607.1 General. Storage of cooking oil (grease) in commercial cooking operations utilizing above-ground tanks with a capacity greater than 60 gal (227 L) installed within a building shall comply with Sections 607.2 through 607.7 and NFPA 30. For purposes of this…
R.8-914 IFC Section 901.6.3 Records
0.3K chars
8-914. IFC Section 901.6.3 Records. Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained. Copies of the inspection reports shall be sent to the local jurisdiction by the servicing vendor as prescribed by the Fire Code …
R.8-915 IFC Section 907.6.5 Access
0.2K chars
8-915. IFC Section 907.6.5 Access. Access shall be provided to each fire alarm device and notification appliance for periodic inspection, maintenance and testing. Fire alarm notification devices shall be unobstructed and visible at all times.
R.8-916 IFC Section 1010.2.14 Controlled egress doors in Groups I-1 and I-2 as well as I-4 (Adult Day
2.3K chars
8-916. IFC Section 1010.2.14 Controlled egress doors in Groups I-1 and I-2 as well as I-4 (Adult Day Care occupancy only). Electric locking systems, including electro-mechanical locking systems and electromagnetic locking systems, shall be permitted to be locked in the means of e…
R.8-917 IFC 1016.2 Egress through intervening spaces
2.5K chars
8-917. IFC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. 1. Exit access through an enclosed elevator lobby is permitted. Where access to two or more exits or exit access doorways is required in Section 1006.2.1, access…
R.8-918 IFC Section 2303.2.2 Testing
0.4K chars
8-918. IFC Section 2303.2.2 Testing. Emergency disconnect switches shall be tested annually by the responsible party to ensure proper operation; records of testing shall be maintained on site for inspection. Any switches determined to be faulty, the fuel pumps they serve shall be…
R.8-919 IFC Section 2305.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C
0.3K chars
8-919. IFC Section 2305.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 50 feet from pumps, dispensers or storage tank fill-pipe open…
R.8-920 IFC Section 2307.4 Location of dispensing operations and equipment
0.6K chars
8-920. IFC Section 2307.4 Location of dispensing operations and equipment. The point of transfer for LP-gas dispensing operations shall be separated from buildings and other exposures in accordance with NFPA 58 Table 6.7.2.1 and IFC Section 2306.7. Exception: The point of transfe…
R.8-921 IFC Section 2307.7 Public fueling of motor vehicles
0.3K chars
8-921. IFC Section 2307.7 Public fueling of motor vehicles. Self-service LP-gas dispensing systems, including key, code and card lock dispensing systems, shall be limited to the filling of permanently mounted containers providing fuel to the LP-gas powered vehicle, is removed.
R.8-922 IFC Section 6101.1 Scope
0.3K chars
8-922. IFC Section 6101.1 Scope. Storage, handling and transportation of liquefied petroleum gas (LP-gas) and the installation of LP-gas equipment pertinent to systems for such uses shall comply with this chapter and NFPA 58. Properties of LP-gases shall be determined in accordan…
R.8-923 IFC Section 6106.1 Attendants
0.2K chars
8-923. IFC Section 6106.1 Attendants. Dispensing of LP-gas shall be performed by a qualified attendant that meets the requirements of this section and NFPA 58 Section 4.4.
R.8-924 IFC Section 6107.4 Protecting containers from vehicles
0.2K chars
8-924. IFC Section 6107.4 Protecting containers from vehicles. Exception: An alternative method may be used that meets the intent of this section with the approval of the AHJ.
R.8-925 IFC Section 6109.13 Protection of containers
0.3K chars
8-925. IFC Section 6109.13 Protection of containers. LP-gas containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicle protections shall be required as required by the fire code official in accordance with Section 312 or NFPA 58 8.4.2…
R.8-926 IFC Section 6110.1 Removed from service
0.4K chars
8-926. IFC Section 6110.1 Removed from service. Containers not connected for service at customer locations. LP-gas containers at customer locations that are not connected for service shall comply with all of the following: 1. Have LP-gas container outlets, except relief valves, c…
R.8-927 IFC Section 6111.2.1 Near residential, educational and institutional occupancies and other
1.4K chars
8-927. IFC Section 6111.2.1 Near residential, educational and institutional occupancies and other high-risk areas. Separation distance requirements may be reduced to not less than 50 feet as approved by the fire code official, based upon a completed fire safety analysis and consi…