R.8-1232 IRC Section M1502.3 Duct termination
0.3K chars
8-1232. IRC Section M1502.3 Duct termination. Exhaust ducts shall terminate on the outside of the building. Exhaust duct terminations shall be in accordance with the dryer manufacturer’s installation instructions. Exhaust duct terminations shall be equipped with a backdraft dampe…
R.8-1233 IRC Section M1502.4.2 Duct Installation
1.0K chars
8-1233. IRC Section M1502.4.2 Duct Installation. Exhaust ducts shall be supported at intervals not to exceed 8 feet and within 16 inches of each side of a joint that is not installed in a vertical orientation, secured in place, making rigid contact with the duct at not less than …
R.8-1234 IRC Section M1502.4.6 Duct length
0.2K chars
8-1234. IRC Section M1502.4.6 Duct length. The maximum length of a clothes dryer exhaust duct shall not exceed 35 feet (10668 mm) from the dryer location to the wall or roof termination.