815 sections in this chapter.
R.296-307-296-307-36421 Installing equipment in wet locations.
0.7K chars
(1) Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations must be installed to prevent moisture or water from entering and accumulating within the enclosures. In wet locations the enclosures must be weatherproof.(2) Switches, circuit breakers…
R.296-307-296-307-366 Wiring design and protection.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-366, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-366, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-36603 Use and identification of grounded and grounding conductors.
0.8K chars
(1) A conductor used as a grounded conductor must be identified separately from all other conductors. A conductor used as an equipment grounding conductor must be identified separately from all other conductors.(2) A grounded conductor must not be attached to any terminal or lead…
R.296-307-296-307-36606 Ampere rating for outlet devices.
0.4K chars
Outlet devices must have an ampere rating at least equal to the load served.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-36606, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodified as § 296-307-36606, filed 4/7/97, ef…
R.296-307-296-307-36609 Conductors.
2.5K chars
This section applies to branch circuit, feeder, and service conductors rated 600 volts, nominal, or less and run outdoors as open conductors.(1) Conductors supported on poles must provide a horizontal climbing space of at least the following:(a) For power conductors below communi…
R.296-307-296-307-36612 Design and protection requirements that apply to service-entrances.
1.2K chars
(1) Disconnecting means for service-entrances must meet the following requirements:(a) Means must be provided to disconnect all conductors in a building or other structure from the service-entrance conductors. The disconnecting means must plainly indicate whether it is in the ope…
R.296-307-296-307-36615 Overcurrent protection.
2.2K chars
(1) The following requirements apply to overcurrent protection of circuits rated 600 volts, nominal, or less.(a) Conductors and equipment must be protected from overcurrent according to their ability to safely conduct current.(b) Except for motor running overload protection, over…
R.296-307-296-307-36618 Grounding for premises wiring systems.
2.5K chars
The following systems that supply premises wiring must be grounded:(1) All 3-wire DC systems must have their neutral conductor grounded.(2) Two-wire DC systems operating at 50-300 volts between conductors must be grounded.Exception:This requirement does not apply if: 1. They supp…
R.296-307-296-307-36621 Grounding the conductor in AC premises wiring.
0.4K chars
For AC premises wiring systems the identified conductor must be grounded.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-36621, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodified as § 296-307-36621, filed 4/7/97, effec…
R.296-307-296-307-36624 General requirements that apply to grounding conductors.
1.4K chars
(1) For a grounded system, a grounding electrode conductor must be used to connect both the equipment grounding conductor and the grounded circuit conductor to the grounding electrode. Both the equipment grounding conductor and the grounding electrode conductor must be connected …
R.296-307-296-307-36627 Continuous path to ground.
0.4K chars
The path to ground from circuits, equipment, and enclosures must be permanent and continuous.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-36627, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodified as § 296-307-36627,…
R.296-307-296-307-36630 Grounding supports, enclosures, and equipment.
4.2K chars
(1) Metal cable trays, metal raceways, and metal enclosures for conductors must be grounded.Exceptions:1. Metal enclosures such as sleeves that are used to protect cable assemblies from physical damage need not be grounded; or 2. Metal enclosures for conductors added to existing …
R.296-307-296-307-36633 Grounding fixed equipment.
1.3K chars
(1) Noncurrent-carrying metal parts of fixed equipment, if required to be grounded by this section, must be grounded by an equipment grounding conductor that is contained within the same raceway, cable, or cord, or runs with or encloses the circuit conductors. For DC circuits onl…
R.296-307-296-307-36636 Grounding high voltage systems.
2.3K chars
Grounded high voltage (1000 volts or more) systems and circuits must meet all requirements of WAC 296-307-366 and the additional requirements of this section.(1) Systems supplying portable or mobile high voltage equipment, other than substations installed on a temporary basis, mu…
R.296-307-296-307-368 Wiring methods, components, and equipment for general use.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-368, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-368, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-36803 Factory-assembled equipment.
0.6K chars
WAC 296-307-368 does not apply to conductors that are an integral part of factory-assembled equipment.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-36803, filed 10/20/20, effective 11/20/20. Statutory Authority: RCW 49.17.040. …
R.296-307-296-307-36806 Temporary wiring.
4.0K chars
Temporary electrical power and lighting wiring methods may be of a class less than would be required for a permanent installation. All requirements for permanent wiring apply to temporary wiring installations, except as indicated in this section.(1) Temporary electrical power and…
R.296-307-296-307-36809 Cable trays.
1.8K chars
(1) Only the following may be installed in cable tray systems:(a) Mineral-insulated metal-sheathed cable (Type MI);(b) Armored cable (Type AC);(c) Metal-clad cable (Type MC);(d) Power-limited tray cable (Type PLTC);(e) Nonmetallic-sheathed cable (Type NM or NMC);(f) Shielded nonm…
R.296-307-296-307-36812 Open wiring on insulators.
1.6K chars
(1) Open wiring on insulators is only permitted on systems of 600 volts, nominal, or less for industrial or agricultural establishments and for services.(2) Conductors must be rigidly supported on noncombustible, nonabsorbent insulating materials and must not contact any other ob…
R.296-307-296-307-36815 Wiring requirements that apply to cabinets, boxes, and fittings.
1.5K chars
(1) Conductors entering boxes, cabinets, or fittings must be protected from abrasion, and openings through which conductors enter must be closed. Unused openings in cabinets, boxes, and fittings must also be closed.(2) All pull boxes, junction boxes, and fittings must have covers…
R.296-307-296-307-36818 Switches.
1.1K chars
(1) Single-throw knife switches must be connected so that the blades are dead when the switch is in the open position. Single-throw knife switches must be placed so that gravity will not tend to close them. Single-throw knife switches approved for use in the inverted position mus…
R.296-307-296-307-36821 Location of switchboards and panelboards.
0.8K chars
Switchboards that have any exposed live parts must be located in permanently dry locations and accessible only to qualified persons. Panelboards must be mounted in cabinets, cutout boxes, or enclosures approved for the purpose and must be dead front. However, panelboards other th…
R.296-307-296-307-36824 Insulating conductors.
0.7K chars
All conductors used for general wiring must be insulated unless otherwise permitted in this section. The conductor insulation must be approved for the voltage, operating temperature, and location of use. Insulated conductors must be distinguishable by appropriate color or other m…
R.296-307-296-307-36827 Use of flexible cords and cables.
1.7K chars
(1) Flexible cords and cables must be approved and suitable for conditions of use and location. Flexible cords and cables must be used only for:(a) Pendants;(b) Wiring of fixtures;(c) Connection of portable lamps or appliances;(d) Elevator cables;(e) Wiring of cranes and hoists;(…
R.296-307-296-307-36830 Identification, splicing and termination of flexible cords and cables.
1.2K chars
(1) A conductor of a flexible cord or cable that is used as a grounded conductor or an equipment grounding conductor must be distinguishable from other conductors. Types SJ, SJO, SJT, SJTO, S, SO, ST, and STO must be durably marked on the surface with the type designation, size, …
R.296-307-296-307-36833 Multiconductor portable cable.
1.2K chars
Multiconductor portable cable for use in supplying power to portable or mobile equipment at over 600 volts, nominal, must consist of No. 8 or larger conductors employing flexible stranding. Cables operated at over 2,000 volts must be shielded to confine the voltage stresses to th…
R.296-307-296-307-36836 Use of fixture wires.
0.9K chars
(1) A fixture wire must be approved for the voltage, temperature, and location of use. A fixture wire used as a grounded conductor must be identified.(2) Fixture wires may be used:(a) For installation in lighting fixtures and in similar equipment where enclosed or protected and n…
R.296-307-296-307-36839 Wiring for lighting fixtures, lampholders, lamps, and receptacles.
1.2K chars
(1) Fixtures, lampholders, lamps, rosettes, and receptacles must have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 8 feet above the floor may have exposed parts.(2) Handlamps of the portable type…
R.296-307-296-307-36842 Wiring for receptacles, cord connectors, and attachment plugs (caps).
0.8K chars
(1) Receptacles, cord connectors, and attachment plugs must be constructed so that no receptacle or cord connector will accept an attachment plug with a different voltage or current rating than that for which the device is intended. However, a 20-ampere T-slot receptacle or cord …
R.296-307-296-307-36845 Wiring for appliances.
0.7K chars
(1) Appliances, other than those in which the current-carrying parts at high temperatures are necessarily exposed, must have no live parts normally exposed to employee contact.(2) Each appliance must have a disconnecting means.(3) Each appliance must be marked with its rating in …
R.296-307-296-307-36848 Wiring for motors, motor circuits, and controllers.
4.1K chars
(1) If specified that one piece of equipment must be "in sight from" another piece of equipment, one must be visible and not more than 50 feet from the other.(2) Disconnecting means must meet the following requirements:(a) A disconnecting means must be located in sight from the c…
R.296-307-296-307-36851 Wiring for transformers.
2.0K chars
(1) This section applies to the installation of all transformers.Exceptions:1. Current transformers; 2. Dry-type transformers installed as a component part of other apparatus; 3. Transformers that are an integral part of a high frequency or electrostatic-coating apparatus; 4. Tra…
R.296-307-296-307-36854 Wiring for capacitors.
1.1K chars
(1) All capacitors, except surge capacitors or capacitors included as a component part of other apparatus, must have an automatic means of draining the stored charge after the capacitor is disconnected from its source of supply.(2) Capacitors rated over 600 volts, nominal, must m…
R.296-307-296-307-36857 Ventilation for stored batteries.
0.5K chars
The employer must ensure that there is sufficient diffusion and ventilation of gases from storage batteries to prevent the accumulation of explosive mixtures.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-36857, filed 10/20/20, …
R.296-307-296-307-36860 Miscellaneous requirements that apply to wiring methods.
0.9K chars
(1) Metal raceways, cable armor, and other metal enclosures for conductors must be metallically joined into a continuous electric conductor and must be connected to all boxes, fittings, and cabinets to provide effective electrical continuity.(2) All wiring systems are prohibited …
R.296-307-296-307-370 Special purpose equipment and installations.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-370, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-370, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-37003 Cranes, hoists, and runways.
1.9K chars
The installation of electric equipment and wiring used with cranes, monorail hoists, hoists, and all runways must meet the following requirements:(1) Disconnecting means must meet the following requirements:(a) A readily accessible disconnecting means is provided between the runw…
R.296-307-296-307-37006 Elevators, dumbwaiters, escalators, and moving walks.
1.1K chars
(1) Elevators, dumbwaiters, escalators, and moving walks must have a single means for disconnecting all ungrounded main power supply conductors for each unit.(2) If interconnections between control panels are necessary for operation of the system on a multicar installation that r…
R.296-307-296-307-37009 Disconnecting means for electric welders.
0.8K chars
(1) A disconnecting means must be provided in the supply circuit for each motor-generator arc welder, and for each AC transformer and DC rectifier arc welder that is not equipped with a disconnect mounted as an integral part of the welder.(2) A switch or circuit breaker must be p…
R.296-307-296-307-37012 Electrically driven or controlled irrigation machines.
0.8K chars
(1) If an electrically driven or controlled irrigation machine has a stationary point, a driven ground rod must be connected to the machine at the stationary point for lightning protection.(2) The main disconnecting means for a center pivot irrigation machine must be located at t…
R.296-307-296-307-372 Hazardous (classified) locations.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-372, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-372, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-37203 Scope.
0.9K chars
WAC 296-307-372 covers the requirements for electric equipment and wiring in locations that are classified based on the properties of the flammable vapors, liquids or gases, or combustible dusts or fibers that may be present and the likelihood that a flammable combustible concent…
R.296-307-296-307-37206 Classifications that apply to this section.
7.9K chars
These hazardous locations are classified as follows:(1) Class I locations. Locations in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explosive or ignitable mixtures. They include the following:(a) Class I, Division 1 locatio…
R.296-307-296-307-37209 Equipment, wiring methods, and installations in hazardous locations.
2.6K chars
Equipment, wiring methods, and installations of equipment in hazardous locations must be intrinsically safe, or approved for the hazardous location, or safe for the hazardous location. Requirements for each of these options are as follows:(1) Equipment and associated wiring appro…
R.296-307-296-307-37212 Installing conduit in hazardous locations.
0.5K chars
All conduits must be threaded and wrench-tight. Where it is impractical to make a threaded joint tight, a bonding jumper must be used.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-37212, filed 10/20/20, effective 11/20/20. WSR …
R.296-307-296-307-37215 Equipment to be used in Division 1 and 2 locations.
0.7K chars
Equipment that has been approved for a Division 1 location may be installed in a Division 2 location of the same class and group. General-purpose equipment or equipment in general-purpose enclosures may be installed in Division 2 locations if the equipment does not constitute a s…
R.296-307-296-307-37218 Motors and generators used in hazardous locations.
2.2K chars
In Class I, Division 1 locations, motors, generators and other rotating electric machinery must be:(1) Approved for Class I, Division 1 locations (explosion-proof); or(2) Of the totally enclosed type supplied with positive-pressure ventilation from a source of clean air with disc…
R.296-307-296-307-374 Special systems.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-374, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-374, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-37403 Systems over 600 volts, nominal.
4.6K chars
(1) Wiring methods for fixed installations over 600 volts, nominal, must meet the following requirements:(a) Above-ground conductors must be installed in rigid metal conduit, in intermediate metal conduit, in cable trays, in cablebus, in other suitable raceways, or as open runs o…
R.296-307-296-307-37406 Emergency power systems.
1.1K chars
This section applies to circuits, systems, and equipment intended to supply power for illumination and special loads, in the event of failure of the normal supply.(1) Emergency circuit wiring must be kept entirely independent of all other wiring and equipment and must not enter t…