R.296-24-296-24-592 Portable fire extinguishers.
0.2K chars
All sections of this chapter which include WAC 296-24-592 in the section number apply to portable fire extinguishers.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-592, filed 12/24/81.]
R.296-24-296-24-59201 Scope and application.
0.4K chars
The requirements of this section apply to the hydrostatic testing of portable fire extinguishers provided for the use of employees.[Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 01-11-038, § 296-24-59201, filed 5/9/01, effective 9/1/01. Statutory Authority…
R.296-24-296-24-59212 Hydrostatic testing.
3.1K chars
(1) You must ensure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests in addition to an external visual examination.(2) You must ensure that portable fire extinguishers are hydrostatically tested whenever they show new eviden…
R.296-24-296-24-59215 Appendix A—Portable fire extinguishers.
13.2K chars
(1) Scope and application. The scope and application of this section is written to apply to three basic types of workplaces. First, there are those workplaces where the employer has chosen to evacuate all employees from the workplace at the time of a fire emergency. Second, there…
R.296-24-296-24-602 Standpipe and hose systems.
0.2K chars
This section establishes design and installation criteria for standpipe systems.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-602, filed 12/24/81.]
R.296-24-296-24-60201 Scope and application.
0.5K chars
(1) Scope. This section applies to all small hose, Class II and Class III standpipe systems installed to meet the requirements of a particular DOSH standard.(2) Exception. This section does not apply to Class I standpipe systems.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.…
R.296-24-296-24-60203 Protection of standpipes.
0.4K chars
You must ensure that standpipes are located or otherwise protected against mechanical damage. You must repair damaged standpipes promptly.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15-24-100, § 296-24-60203, filed 12/1/15, effective 1/5/16. Stat…
R.296-24-296-24-60205 Equipment.
2.1K chars
(1) Reels and cabinets. Where reels or cabinets are provided to contain fire hose, you must ensure that they are designed to facilitate prompt use of the hose valves, the hose, and other equipment at the time of a fire or other emergency. You must ensure that the reels and cabine…
R.296-24-296-24-60207 Water supply.
0.5K chars
You must ensure that the minimum water supply for standpipe and hose systems, which are provided for the use of employees, are sufficient to provide 100 gallons per minute (6.3 l/s) for a period of at least thirty minutes.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050,…
R.296-24-296-24-60209 Tests and maintenance.
2.2K chars
(1) Acceptance tests.(a) You must ensure that the piping of Class II and Class III systems installed after July 1, 1982, including yard piping, is hydrostatically tested for a period of at least two hours at not less than 200 psi (1,380 kPa), or at least 50 psi (340 kPa) in exces…
R.296-24-296-24-60299 Appendix A—Standpipe and hose systems.
5.2K chars
(1) Scope and application. This section has been written to provide adequate coverage of those standpipe and hose systems that an employer may install in the workplace to meet the requirements of a particular DOSH standard. For example, DOSH permits the substitution of hose syste…
R.296-24-296-24-607 Automatic sprinkler systems.
0.2K chars
The design and installation criteria for automatic sprinkler systems is contained in this section.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-607, filed 12/24/81.]
R.296-24-296-24-60701 Scope and application.
0.7K chars
(1) The requirements of this section apply to all automatic sprinkler systems installed to meet a particular DOSH standard.(2) For automatic sprinkler systems used to meet DOSH requirements and installed prior to the effective date of this standard, compliance with the National F…
R.296-24-296-24-60703 Exemptions.
0.4K chars
Automatic sprinkler systems installed in workplaces, but not required by DOSH are exempt from the requirements of this section.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15-24-100, § 296-24-60703, filed 12/1/15, effective 1/5/16. Statutory Autho…
R.296-24-296-24-60705 General requirements.
3.6K chars
(1) Design.(a) All automatic sprinkler designs used to comply with this standard must provide the necessary discharge patterns, densities, and water flow characteristics for complete coverage in a particular workplace or zoned subdivision of the workplace.(b) You must ensure that…
R.296-24-296-24-60799 Appendix A—Automatic sprinkler systems.
7.6K chars
(1) Scope and application. This section contains the minimum requirements for design, installation and maintenance of sprinkler systems that are needed for employee safety. The occupational safety and health administration is aware of the fact that the National Board of Fire Unde…
R.296-24-296-24-617 Fixed extinguishing systems, general.
0.4K chars
This section applies to criteria required for fixed extinguisher systems and all sections of this chapter having number WAC 296-24-617 in the section number apply.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15-24-100, § 296-24-617, filed 12/1/15,…
R.296-24-296-24-61701 Scope and application.
1.0K chars
(1) This section applies to all fixed extinguishing systems installed to meet a particular DOSH standard except for automatic sprinkler systems which are covered by WAC 296-24-607.(2) This section also applies to fixed systems not installed to meet a particular DOSH standard, but…
R.296-24-296-24-61703 General requirements.
3.8K chars
(1) You must ensure that fixed extinguishing system components and agents are designed and approved for use on the specific fire hazards they are expected to control or extinguish.(2) You must notify employees and take the necessary temporary precautions to assure their safety un…
R.296-24-296-24-61705 Total flooding systems with potential health and safety hazards to employees.
2.2K chars
(1) You must provide an emergency action plan in accordance with WAC 296-24-567 for each area within a workplace that is protected by a total flooding system which provides agent concentrations exceeding the maximum safe levels.(2) Systems installed in areas where employees canno…
R.296-24-296-24-61799 Appendix A—Fixed extinguishing systems, general.
4.3K chars
(1) Scope and application. This section contains the general requirements that are applicable to all fixed extinguishing systems installed to meet DOSH standards. It also applies to those fixed extinguishing systems, generally total flooding, which are not required by DOSH, but w…
R.296-24-296-24-622 Fixed extinguishing systems, dry chemical.
0.3K chars
The design and installation requirements specifically applicable to fixed extinguishing systems, using dry chemical as the extinguishing agent, are contained in this section.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-622, filed 12/24/…
R.296-24-296-24-62201 Scope and application.
0.4K chars
This section applies to all fixed extinguishing systems using dry chemical as the extinguishing agent, installed to meet a particular DOSH standard. These systems must also comply with WAC 296-24-617.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15…
R.296-24-296-24-62203 Specific requirements.
2.3K chars
(1) You must ensure that dry chemical agents are compatible with any foams or wetting agents with which they are used.(2) You may not mix together dry chemical extinguishing agents of different compositions. You must ensure that dry chemical systems are refilled with the chemical…
R.296-24-296-24-62299 Appendix A—Fixed extinguishing systems, dry chemical.
1.0K chars
(1) Scope and application. The requirements of this section apply only to dry chemical systems. These requirements are to be used in conjunction with the requirements of WAC 296-24-617.(2) Maintenance. The employer is responsible for assuring that dry chemical systems will operat…
R.296-24-296-24-623 Fixed extinguishing systems, gaseous agent.
0.2K chars
This section contains the design and installation requirements for fixed extinguishing systems using gaseous agents.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-623, filed 12/24/81.]
R.296-24-296-24-62301 Scope and application.
0.6K chars
(1) Scope. This section applies to all fixed extinguishing systems, using a gas as the extinguishing agent, installed to meet a particular DOSH standard. These systems must also comply with WAC 296-24-617. In some cases, the gas may be in a liquid state during storage.(2) Applica…
R.296-24-296-24-62303 Specific requirements.
2.1K chars
(1) You must ensure that agents used for initial supply and replenishment are of the type approved for the system's application. Carbon dioxide obtained by dry ice conversion to liquid is not acceptable unless it is processed to remove excess water and oil.(2) You must ensure tha…
R.296-24-296-24-62399 Appendix A—Fixed extinguishing systems, gaseous agent.
1.7K chars
(1) Scope and application. This section applies only to those systems which use gaseous agents. The requirements of WAC 296-24-617 also apply to the gaseous agent systems covered in this section.(2) Design concentrations. Total flooding gaseous systems are based on the volume of …
R.296-24-296-24-627 Fixed extinguishing systems, water spray and foam.
0.3K chars
This section contains the design and installation requirements for extinguishing systems using water or foam solution as the extinguishing agent.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-627, filed 12/24/81.]
R.296-24-296-24-62701 Scope and application.
0.6K chars
This section applies to all fixed extinguishing systems, using water or foam solution as the extinguishing agent, installed to meet a particular DOSH standard. These systems must also comply with WAC 296-24-617. This section does not apply to automatic sprinkler systems which are…
R.296-24-296-24-62703 Specific requirements.
0.6K chars
(1) You must ensure that foam and water spray systems are designed to be effective in at least controlling fire in the protected area or on protected equipment.(2) You must ensure that drainage of water spray systems is directed away from areas where employees are working and tha…
R.296-24-296-24-62799 Appendix A—Fixed extinguishing systems, water spray and foam.
1.8K chars
(1) Scope and application. This section applies to those systems that use water spray or foam. The requirements of WAC 296-24-617 also apply to this type of system.(2) Characteristics of foams. When selecting the type of foam for a specific hazard, the employer should consider th…
R.296-24-296-24-629 Fire detection systems.
0.3K chars
The requirements for installation, restoration, maintenance, testing and protection of fire detection systems and the criteria for response time can be found in this section.[Statutory Authority: RCW 49.17.040 and 49.17.050. WSR 82-02-003 (Order 81-32), § 296-24-629, filed 12/24/…
R.296-24-296-24-62901 Scope and application.
0.4K chars
This section applies to all automatic fire detection systems installed to meet the requirements of a particular DOSH standard.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15-24-100, § 296-24-62901, filed 12/1/15, effective 1/5/16. Statutory Author…
R.296-24-296-24-62903 Installation and restoration.
0.8K chars
(1) You must ensure that all devices and equipment constructed and installed to comply with this standard are approved for the purpose for which they are intended.(2) You must restore all fire detection systems and components to normal operating condition as promptly as possible …
R.296-24-296-24-62905 Maintenance and testing.
1.2K chars
(1) You must maintain all systems in an operable condition except during repairs or maintenance.(2) You must ensure that fire detectors and fire detection systems are tested and adjusted as often as needed to maintain proper reliability and operating condition except that factory…
R.296-24-296-24-62907 Protection of fire detectors.
0.8K chars
(1) You must ensure that fire detection equipment installed outdoors or in the presence of corrosive atmospheres be protected from corrosion. The employer shall provide a canopy, hood, or other suitable protection for detection equipment requiring protection from the weather.(2) …
R.296-24-296-24-62909 Response time.
1.0K chars
(1) You must ensure that fire detection systems installed for the purpose of actuating fire extinguishment or suppression systems shall be designed to operate in time to control or extinguish a fire.(2) You must ensure that fire detection systems installed for the purpose of empl…
R.296-24-296-24-62911 Number, location and spacing of detecting devices.
0.5K chars
You must ensure that the number, spacing and location of fire detectors is based upon design data obtained from field experience, or tests, engineering surveys, the manufacturer's recommendations, or a recognized testing laboratory listing.[Statutory Authority: RCW 49.17.010, 49.…
R.296-24-296-24-62999 Appendix A—Fire detection systems.
2.9K chars
(1) Installation and restoration. Fire detection systems must be designed by knowledgeable engineers or other professionals, with expertise in fire detection systems and when the systems are installed, there should be an acceptance test performed on the system to insure it operat…
R.296-24-296-24-63299 Appendix B—National consensus standards.
3.3K chars
The following table contains a cross-reference listing of those current national consensus standards which contains information and guidelines that would be considered acceptable in complying with requirements in the specific sections.SectionNational Consensus StandardWAC 296-24-…
R.296-24-296-24-63399 Appendix C—Fire protection references for further information.
10.1K chars
(1) Appendix general references. The following references provide information which can be helpful in understanding the requirements contained in all of the sections of Part G:(a) Fire Protection Handbook, National Fire Protection Association, Batterymarch Park, Quincy, MA 02269-…
R.296-24-296-24-63599 Appendix E—Test methods for protective clothing.
15.4K chars
This appendix contains test methods which must be used to determine if protective clothing affords the required level of protection as specified in chapter 296-811 WAC - fire brigades.(1) Puncture resistance test method for foot protection.(a) Apparatus. You must perform the punc…
R.296-24-296-24-680 Welding, cutting, and brazing.
0.5K chars
You must protect employees from exposure to hexavalent chromium during the stainless steel welding process. See WAC 296-62-08003, Hexavalent chromium for specific criteria.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 15-24-100, § 296-24-680, filed…
R.296-24-296-24-68001 Definitions.
0.8K chars
Welder and welding operator. Any operator of electric or gas welding and cutting equipment.Approved. Listed or approved by a nationally recognized testing laboratory. Refer to WAC 296-24-58501(19) for definitions of listed and approved, and federal regulation 29 C.F.R. 1910.7 for…
R.296-24-296-24-682 Installation and operation of oxygen fuel gas systems for welding and cutting.
0.1K chars
[Order 73-5, § 296-24-682, filed 5/9/73 and Order 73-4, § 296-24-682, filed 5/7/73.]
R.296-24-296-24-68201 General requirements.
2.4K chars
(1) Flammable mixture. You must guard against mixtures of fuel gases and air or oxygen may be explosive and . You must not allow any device or attachment facilitating or permitting mixtures of air or oxygen with flammable gases prior to consumption, except at the burner or in a s…
R.296-24-296-24-68203 Cylinders and containers.
11.0K chars
(1) Approval and marking. All portable cylinders used for the storage and shipment of compressed gases must be constructed and maintained in accordance with the regulations of the United States Department of Transportation, 49 C.F.R. Parts 171-179.(a) You must legibly mark compre…
R.296-24-296-24-68205 Manifolding of cylinders.
7.5K chars
(1) Fuel-gas manifolds.(a) You must approve manifolds either separately for each component part or as an assembled unit.(b) Except as provided in (1)(c) of this section you must limit fuel-gas cylinders connected to one manifold inside a building to a total capacity not exceeding…