43,797 sections across 2,191 Washington regulatory chapters.
R.296-307-296-307-40009 Systems mounted on farm wagons (implements of husbandry) for the application of ammonia.
2.1K chars
This section applies to systems mounted on farm equipment that are used for the field application of ammonia.WAC 296-307-40011 through 296-307-40037 also apply unless otherwise noted.(1) All containers must be securely mounted.(2) Container valves and accessories must meet the fo…
R.296-307-296-307-40011 Approved anhydrous ammonia equipment.
2.3K chars
All equipment must be approved by one of the following methods:(1) The equipment was installed before February 8, 1973, and was approved and tested, and installed according to either the requirements of the American National Standard for the Storage and Handling of Anhydrous Ammo…
R.296-307-296-307-40013 Construction, original test, and requalification of nonrefrigerated containers.
2.6K chars
The code is the Unfired Pressure Vessel Code of the American Society of Mechanical Engineers (Section VIII of the ASME Boiler Construction Code), 1952, 1956, 1959, 1962, 1965, 1968 and 1971 editions, the joint code of the American Petroleum Institute and the American Society of M…
R.296-307-296-307-40015 Marking nonrefrigerated containers and systems (other than DOT containers).
3.3K chars
(1) System nameplates, when required, must be permanently attached to the system so they are readily accessible for inspection.(2) Each container or system covered in WAC 296-307-40005 and 296-307-40007 must be marked as follows:(a) With indication that the container or system me…
R.296-307-296-307-40017 Locations for anhydrous ammonia containers.
1.3K chars
(1) When selecting the location for a storage container, the employer must take into account the physiological effects of ammonia and adjacent fire hazards. Containers located indoors must be in areas especially approved for container storage.(2) Containers must be located at lea…
R.296-307-296-307-40019 Container accessories.
2.3K chars
(1) All accessories must be designed for at least the maximum working pressure of the part of the system on which they are installed. All accessories must be fabricated from materials suitable for anhydrous ammonia service.(2) All connections to containers must have shut-off valv…
R.296-307-296-307-40021 Piping, tubing, and fittings.
2.3K chars
(1) All piping, tubing and fittings must be made of material suitable for anhydrous ammonia service.(2) All piping, tubing and fittings must be designed for a pressure of at least the maximum pressure to which they may be subjected in service.(3) All piping must be well supported…
R.296-307-296-307-40023 Specifications for hoses.
1.8K chars
(1) Hose used in ammonia service and subject to container pressure must meet the requirements of the joint Rubber Manufacturers Association and the Fertilizer Institute "Hose Specifications for Anhydrous Ammonia."(2) Hose subject to container pressure must be designed for a minim…
R.296-307-296-307-40025 Safety-relief devices.
6.3K chars
(1) Every container used in systems covered by WAC 296-307-400 must have one or more spring-loaded safety-relief valves or the equivalent.(2) The discharge from safety-relief valves must be vented away from the container, upward, and unobstructed to the atmosphere. All safety-rel…
R.296-307-296-307-40027 Emergency precautions when handling anhydrous ammonia.
3.3K chars
(1) The employer must train employees required to handle ammonia in the safe operating practices and the proper action to take in an emergency. Employees must be instructed to use the equipment listed in subsection (3) of this section in an emergency.(2) If ammonia system leaks, …
R.296-307-296-307-40029 Filling densities.
1.3K chars
Filling density means the percent ratio of the weight of the gas in a container to the weight of water at 60°F that the container will hold. One pound of water equals 27.737 cubic inches at 60°F. To determine the weight capacity of the tank in pounds, the weight of a gallon (231 …
R.296-307-296-307-40031 Transfer of liquids.
3.7K chars
(1) Anhydrous ammonia must always be at a temperature suitable for the material of construction and design of the receiving containers. Ordinary steels are not suitable for refrigerated ammonia. See Appendix R of API Standard 620 "Recommended Rules for Design and Construction of …
R.296-307-296-307-40033 Tank car unloading points and operations.
1.5K chars
(1) Provisions for unloading tank cars must meet DOT requirements.(2) Unloading operations must be performed by reliable employees who are properly instructed and responsible for careful compliance with all procedures.(3) Caution signs must be placed on the track or car to give n…
R.296-307-296-307-40035 Liquid-level gauging device.
1.7K chars
(1) Each container except those filled by weight must have an approved liquid-level gauging device.(2) All gauging devices must be arranged so that the maximum liquid level to which the container is filled is easily determined.(3) Gauging devices that require bleeding of the prod…
R.296-307-296-307-40037 Maintenance of aboveground uninsulated containers.
0.5K chars
Aboveground uninsulated containers should have a reflective surface maintained in good condition. We recommend white for painted surfaces, but other light reflecting colors are acceptable.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 2…
R.296-307-296-307-40039 Electrical equipment and wiring.
0.8K chars
(1) Electrical equipment and wiring for use in ammonia installations must be general purpose or weather resistant as appropriate.(2) Where concentrations of ammonia in the air in excess of 16% by volume are likely to be encountered, electrical equipment and wiring must be specifi…
R.296-307-296-307-410 Storage and handling of liquefied petroleum gases.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-410, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-410, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-41001 Scope.
0.9K chars
Chapter 296-307 WAC Part U2 covers the storage and handling of liquefied petroleum gases.The requirements of WAC 296-307-410 apply to all LP-gas installations covered by this part.For additional requirements related to:See WAC:Cylinder systems 296-307-415Systems using non-DOT con…
R.296-307-296-307-41003 LP-gas installations not covered by this part.
1.3K chars
(1) This part does not apply to:(a) LP-gas refrigerated storage systems;(b) LP-gas used with oxygen;(c) LP-gas used in utility gas plants (covered by the National Fire Protection Association Standard for the Storage and Handling of Liquefied Petroleum Gases at Utility Gas Plants,…
R.296-307-296-307-41005 Definitions that apply to this part.
1.5K chars
Adequate ventilation (for fire prevention during normal operation). The concentration of the gas in a gas-air mixture does not exceed 25% of the lower flammable limit.Containers. All vessels, such as tanks, cylinders, or drums, used to transport or store LP-gases.DOT. The federal…
R.296-307-296-307-41007 Odorizing LP-gas.
1.0K chars
The employer must ensure that all LP-gas is odorized by an approved agent to indicate by distinct odor, the presence of gas down to concentration in air of a maximum of 1/5 the lower limit of flammability.Exception:Odorization is not required if it will create a hazard in further…
R.296-307-296-307-41009 Approval of LP-gas containers and equipment.
1.3K chars
(1) Each system of DOT containers must have approved container valves, connectors, manifold valve assemblies, and regulators.(2) Each non-DOT system using containers of 2,000 gallons or less water capacity, must have a container assembly, one or more regulators, and other necessa…
R.296-307-296-307-41011 Construction and test requirements for containers.
1.4K chars
(1) Containers must be designed, constructed, and tested according to the Rules for Construction of Unfired Pressure Vessels, section VIII, Division 1, American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, 1968 edition, unless otherwise specified.(2) Co…
R.296-307-296-307-41013 Welding containers.
0.9K chars
(1) The employer must ensure that all welding to the shell, head, or any other part of the container subject to internal pressure, meets the requirements of the code under which the tank was fabricated. The employer may weld on saddle plates, lugs, or brackets attached to the con…
R.296-307-296-307-41015 Marking containers.
2.1K chars
(1) The employer must ensure that containers are marked according to DOT regulations or with the following:(a) Indication that the container meets the requirements of the code under which it is constructed, and all marks required by that code.(b) Indication whether the container …
R.296-307-296-307-41017 Container locations.
3.8K chars
The employer must ensure that containers are located according to the following:(1) Containers and first stage regulating equipment are located outdoors.Containers may be located indoors under any of the following conditions:(a) In buildings used exclusively for container chargin…
R.296-307-296-307-41019 Valves and accessories.
2.4K chars
(1) Valves, fittings, and accessories connected directly to the container including primary shut-off valves, must have a rated working pressure of at least 250 psig and must be of material and design suitable for LP-gas service. The use of cast iron for container valves, fittings…
R.296-307-296-307-41021 Piping, tubing, and fittings.
6.7K chars
(1) Pipe must be wrought iron or steel (black or galvanized), brass, copper, or aluminum alloy. Aluminum alloy pipe must be at least Schedule 40 according to the specifications for Aluminum Alloy Pipe, ANSI H38.7-1969 (ASTM, B241-1969), and must be suitably marked at each end of …
R.296-307-296-307-41023 Specifications for hoses.
2.5K chars
(1) Hose must be fabricated of materials that are resistant to the action of LP-gas in the liquid and vapor phases. If wire braid is used for reinforcing the hose, it must be of corrosion-resistant material such as stainless steel.(2) Hose subject to container pressure must be ma…
R.296-307-296-307-41025 Safety devices.
7.9K chars
(1) Every container except those constructed according to DOT specifications and every vaporizer (except motor fuel vaporizers and vaporizers described in WAC 296-307-41029(3) and 296-307-42007 (6)(a) whether heated by artificial means or not, must have one or more safety-relief …
R.296-307-296-307-41027 Construction and installation of indirect fired vaporizers.
3.7K chars
Indirect fired vaporizers utilizing steam, water, or other heating medium must be constructed and installed according to the following:(1) Vaporizers must be constructed according to the requirements of WAC 296-307-41011 and must be permanently marked as follows:(a) With the code…
R.296-307-296-307-41029 Construction and installation of atmospheric vaporizers.
0.8K chars
Atmospheric vaporizers using heat from the ground or surrounding air must be installed as follows:(1) Buried underground; or(2) Located inside the building near where the pipe enters the building, if the capacity of the unit does not exceed one quart;(3) Vaporizers of less than o…
R.296-307-296-307-41031 Construction and installation of direct gas-fired vaporizers.
4.2K chars
Direct gas-fired vaporizers must be constructed, marked, and installed as follows:(1) According to the requirements of the American Society of Mechanical Engineers Boiler and Pressure Vessel Code, 1968, that apply to the maximum working conditions for which the vaporizer is desig…
R.296-307-296-307-41033 Construction and installation of direct gas-fired tank heaters.
2.1K chars
Direct gas-fired tank heaters must be constructed and installed as follows:(1) Direct gas-fired tank heaters, and tanks to which they are applied, must only be installed aboveground.(2) Tank heaters must be permanently marked with the name of the manufacturer, the rated Btu input…
R.296-307-296-307-41035 Construction and installation of dehydrators.
2.4K chars
The vaporizer section of vaporizer-burners used for dehydrators or dryers must be located outdoors; they must be constructed and installed as follows:(1) Vaporizer-burners must have a minimum design pressure of 250 psig with a factor safety of five.(2) Manually operated positive …
R.296-307-296-307-41037 Maximum filling densities.
1.4K chars
(1)Filling density. The percent ratio of the weight of the gas in a container to the weight of water the container will hold at 60°F. All containers must be filled according to the filling densities shown in Table U-4.TABLE U-4MAXIMUM PERMITTED FILLING DENSITY Aboveground contain…
R.296-307-296-307-41039 LP-gas in buildings.
3.8K chars
(1) Vapor may be piped into buildings at pressures over 20 psig only if the buildings or separate areas thereof:(a) Are constructed according to this section;(b) Are used exclusively to house equipment for vaporization, pressure reduction, gas mixing, gas manufacturing, or distri…
R.296-307-296-307-41041 Transferring of liquids.
4.0K chars
When transferring liquids, the employer must ensure that:(1) At least one attendant remains close to the transfer connection from the time the connections are first made until they are finally disconnected, during the transfer of the product.(2) Containers must be filled or used …
R.296-307-296-307-41043 Training for workers.
0.5K chars
Workers performing installation, removal, operation, and maintenance work must be properly trained in that function.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-41043, filed 10/20/20, effective 11/20/20. WSR 97-09-013, recodif…
R.296-307-296-307-41045 Fire protection for LP-gas installations.
1.3K chars
(1) Open flames or other sources of ignition are prohibited in vaporizer rooms (except those housing direct-fired vaporizers), pumphouses, container charging rooms or other similar locations. Direct-fired vaporizers are prohibited in pumphouses or container charging rooms.Note:LP…
R.296-307-296-307-41047 Electrical requirements that apply to LP-gas installations.
5.4K chars
(1) Electrical equipment and wiring must be specified by and installed according to chapter 296-307 WAC Part T, for ordinary locations.(2) Fixed electrical equipment and wiring installed within classified areas must comply with Table U-5 and must be installed according to chapter…
R.296-307-296-307-41049 Liquid-level gauging devices.
6.8K chars
(1) Each container manufactured after December 31, 1965, and filled on a volumetric basis must have a fixed liquid-level gauge to indicate the maximum permitted filling level according to subsection (5) of this section. Each container manufactured after December 31, 1969, must ha…
R.296-307-296-307-41051 Requirements that apply to appliances.
1.6K chars
(1) New commercial and industrial gas consuming appliances must be approved.Exception:Any appliance that was originally manufactured for operation with a gaseous fuel other than LP-gas and is in good condition may be used with LP-gas only after it is properly converted, adapted, …
R.296-307-296-307-415 Cylinder systems.
0.2K chars
[WSR 97-09-013, recodified as § 296-307-415, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. WSR 96-22-048, § 296-306A-415, filed 10/31/96, effective 12/1/96.]
R.296-307-296-307-41501 Scope.
0.7K chars
WAC 296-307-415 applies to systems using DOT containers. Cylinder systems must meet all requirements of WAC 296-307-410 (unless otherwise indicated) and the additional requirements of this section.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21…
R.296-307-296-307-41503 Cylinder system.
0.5K chars
Cylinder system. Includes the container base or bracket, containers, container valves, connectors, manifold valve assembly, regulators, and relief valves.[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 20-21-091, § 296-307-41503, filed 10/20/20, effe…
R.296-307-296-307-41505 Marking containers used in cylinder systems.
0.9K chars
(1) Containers must be marked according to DOT regulations. Additional markings that do not conflict with DOT regulations may be used.(2) Each container must be marked with its water capacity in pounds or other identified unit of weight.(3) Exception: If the employer is the only …
R.296-307-296-307-41507 Additional requirements that apply to cylinder systems installed outdoors.
1.5K chars
(1) Containers must not be buried below ground. However, systems may be installed in a compartment or recess below grade level, such as a niche in a slope or terrace wall that is used for no other purpose, if the container and regulating equipment are not in contact with the grou…
R.296-307-296-307-41509 Additional requirements that apply to cylinder system installed indoors.
8.1K chars
(1) When portable containers are necessary and it is not practical to use them outdoors, containers and equipment may be used indoors only if they meet the requirements of this section.(a) Containers in use. Connected for use.(b) Systems using containers with a water capacity gre…
R.296-307-296-307-41511 Valves and accessories.
1.8K chars
(1) Valves in the assembly of multiple container systems must be arranged so that containers can be replaced without shutting off the flow of gas in the system.Note:An automatic changeover device is not required.(2) Regulators and low-pressure relief devices must be rigidly attac…