R.51-50-51-50-1108 Section 1108—Dwelling units and sleeping units.
1.1K chars
1108.6.2.2.1 Type A units. In Group R-2 Occupancies containing more than 10 dwelling units or sleeping units, at least 5 percent, but not less than one, of the units shall be a Type A unit. All units on a site shall be considered to determine the total number of units and the req…
R.51-50-51-50-11090 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-11090, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-21-021, § 51-50-11090, filed 10/9/20, effective 11/9/20; WSR 20-01-090, § 51-50-11090, filed 12/12/19, effectiv…
R.51-50-51-50-1110 Section 1110—Other features and facilities.
3.4K chars
1110.2 Toilet and bathing facilities. Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible fl…
R.51-50-51-50-1202 Section 1202—Ventilation.
12.7K chars
1202.1 General. Buildings shall be provided with natural ventilation in accordance with Section 1202.5, or mechanical ventilation in accordance with the International Mechanical Code. Ambulatory care facilities and Group I-2 occupancies shall be ventilated by mechanical means in …
R.51-50-51-50-1203 Section 1203—Temperature control.
2.5K chars
1203.1 Equipment and systems. Interior spaces intended for human occupancy shall be provided with active or passive space-heating systems capable of maintaining an indoor temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor on the design heating day…
R.51-50-51-50-1204 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1204, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 16-03-064, § 51-50-1204, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27.031 and chapters 19.27 and…
R.51-50-51-50-1206 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1206, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-1206, filed 12/12/19, effective 7/1/20.]
R.51-50-51-50-1207 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1207, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-1207, filed 12/12/19, effective 7/1/20.]
R.51-50-51-50-1208 Section 1208—Interior space dimensions.
2.0K chars
1208.3 Dwelling unit size. Dwelling units shall have a minimum of 190 square feet (17.7 m2) of habitable space.1208.4 Room area. Every dwelling unit shall have not less than one room that shall have not less than 120 square feet (11.2 m2) of net floor area. Sleeping units and oth…
R.51-50-51-50-1209 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1209, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 20-01-090, § 51-50-1209, filed 12/12/19, effective 7/1/20.]
R.51-50-51-50-1210 Section 1210—Toilet and bathroom requirements.
2.2K chars
1210.3.1 Water closet compartment. Each water closet utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures to ensure privacy. Gender-neutral toilet room water closet compartments shall be in accordance w…
R.51-50-51-50-1402 Section 1402—Performance requirements.
2.5K chars
1402.2 Weather protection. Exterior walls shall provide the building with a weather-resistant exterior wall envelope. The exterior wall envelope shall include flashing as described in Section 1404.4. The exterior wall envelope shall be designed and constructed in such a manner as…
R.51-50-51-50-1403 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1403, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 21-06-035, § 51-50-1403, filed 2/23/21, effective 3/26/21; WSR 16-03-064, § 51-50-1403, filed 1/19/16, effective 7/…
R.51-50-51-50-1405 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-1405, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-1405, filed 2/1/13, effecti…
R.51-50-51-50-1406 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 21-06-035, § 51-50-1406, filed 2/23/21, effective 3/26/21; WSR 19-02-038, § 51-50-1406, filed 12/26/18, effective 7/1/19.]
R.51-50-51-50-1602 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-1602, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. WSR 07-01-091, § 51-50-1602, filed 12/19/06, effective 7/1/07.]
R.51-50-51-50-1604 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1604, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-01-090, § 51-50-1604, filed 12/12/19, effective 7/1…
R.51-50-51-50-1607 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-01-090, § 51-50-1607, filed 12/12/19, effective 7/1/20; WSR 16-03-064, § 51-50-1607, filed 1/19/16, effective 7/1/16; WSR 10-03-097, § 51-50-1607, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.190, 19.27.…
R.51-50-51-50-1609 Section 1609—Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-1609, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-1609, filed 1/20/10, effective 7/1/10.]
R.51-50-51-50-1613 Section 1613—Earthquake loads.
14.8K chars
1613.4 Amendments to ASCE 7. The provisions of Section 1613.4 shall be permitted as an amendment to the relevant provisions of ASCE 7. The text of ASCE 7 shall be amended as indicated in Sections 1613.4.1 through 1613.4.6.1613.4.1 ASCE 7 Section 12.2.5.4. Amend ASCE 7 Section 12.…
R.51-50-51-50-1615 Tsunami loads.
10.4K chars
1615.1 General. The design and construction of Risk Category III and IV buildings and structures located in the Tsunami Design Zones shall be in accordance with Chapter 6 of ASCE 7-22, except as modified by this code. Wherever ASCE 7 is referenced herein, it shall refer to ASCE 7…
R.51-50-51-50-1702 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1702, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1702, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1705 Section 1705—Required special inspections and tests.
2.3K chars
1705.13.6 Plumbing, mechanical and electrical components. Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following:1. Anchorage of electrical equipment for emergency and standby power systems in structures assigned to Seism…
R.51-50-51-50-17090 Preconstruction load tests.
1.6K chars
1709.5 Exterior window and door assemblies. The design pressure rating of exterior windows and doors in buildings shall be determined in accordance with Section 1709.5.1 or 1709.5.2. For exterior windows and doors tested in accordance with Section 1709.5.1 or 1709.5.2, required d…
R.51-50-51-50-1710 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1710, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1710, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1715 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1715, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-1715, filed 2/1/…
R.51-50-51-50-1807 Section 1807—Foundation walls, retaining walls and embedded posts and poles.
0.6K chars
1807.2.2 Design lateral soil loads. Retaining walls shall be designed for the lateral soil loads set forth in Section 1610. For structures assigned to Seismic Design Category D, E, or F, the design of retaining walls supporting more than 6 feet (1829 mm) of backfill height measur…
R.51-50-51-50-1901 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1901, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1901, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1903 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1903, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1903, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1904 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1904, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1904, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1905 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1905, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1905, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1908 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1908, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1908, filed 1/19/16, effective 7/1/…
R.51-50-51-50-1909 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-1909, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 16-03-064, § 51-50-1909, filed 1/19/16, effective 7/1/…
R.51-50-51-50-2103 Section 2103—Masonry construction materials.
0.6K chars
2103.2.4 Mortar for adhered masonry veneer. Mortar for use with adhered masonry veneer shall conform to ASTM C270 for Type N or S, or shall comply with ANSI A118.4 or A118.15 for modified dry-set cement mortar. The cementitious bond coat shall comply with ANSI A118.4 or A118.15.[…
R.51-50-51-50-2104 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-2104, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-2104, filed 2/1/…
R.51-50-51-50-2106 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-2106, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.074, 19.27.020, and chapters 70.92, 19.27, and 34.05 RCW. WSR 07-01-091, § 51-50-2106, filed 12/19/06, effective 7/1/07.]
R.51-50-51-50-21070 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-21070, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-21-021, § 51-50-21070, filed 10/9/20, effective 11…
R.51-50-51-50-2108 Section 2108—Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-2108, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-2108, filed 1/20/10, effective 7/1/10. Statutory Authority: RCW 19.27.020, 1…
R.51-50-51-50-2111 Section 2111—Masonry fireplaces.
1.9K chars
2111.8 Fireplaces. Fireplaces shall be provided with each of the following:1. Tightly fitting flue dampers, operated by a readily accessible manual or approved automatic control.EXCEPTION:Fireplaces with gas logs shall be installed in accordance with the International Mechanical …
R.51-50-51-50-2114 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-21-021, § 51-50-2114, filed 10/9/20, effective 11/9/20. Statutory Authority: RCW 19.27.031 and chapters 19.27 and 34.05 RCW. WSR 13-04-067, § 51-50-2114, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.031 a…
R.51-50-51-50-2115 Section 2115—Emission standards.
1.2K chars
2115.1 Emission standards for factory-built fireplaces. No new or used factory-built fireplace shall be installed in Washington state unless it is certified and labeled in accordance with procedures and criteria specified in ASTM E2558 Standard Test Method for determining particu…
R.51-50-51-50-2303 Section 2303—Minimum standards and quality.
1.9K chars
2303.1.1.3 Used solid-sawn lumber. Used solid-sawn dimensional lumber in good condition and devoid of areas of decay, not meeting the requirements of Section 2303.1.1, 2303.1.1.1, or 2303.1.1.2, that has a nominal thickness of 2 inches with a nominal width of 6 inches or less, sh…
R.51-50-51-50-2304 Section 2304—General construction requirements.
1.4K chars
2304.11.2.1 Exterior walls.Exterior walls shall be permitted to be cross-laminated timber not less than 3.5 inches (88 mm) in actual thickness meeting the requirements of Section 2303.1.4.2304.11.2.2 Interior walls and partitions. Interior walls and partitions shall be of solid w…
R.51-50-51-50-2400 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27.031, 19.27.074, and 19.27.540. WSR 23-02-073, 23-12-103, and 23-20-023, § 51-50-2400, filed 1/4/23, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 10-03-097, § 51-50-2400, filed 1/20/10, effective 7/1/…
R.51-50-51-50-2405 Section 2405—Sloped glazing and skylights.
2.9K chars
2405.3 Screening. Where used in monolithic glazing systems, annealed, heat strengthened, fully tempered and wired glass shall have broken glass retention screens installed below the glazing material. The screens and their fastenings shall be:1. Capable of supporting twice the wei…
R.51-50-51-50-2407 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-01-090, § 51-50-2407, filed 12/12/19, effective 7/1/20; WSR 16-03-064, § 51-50-2407, filed 1/19/16, effective 7/1/16.]
R.51-50-51-50-2603 Reserved.
0.2K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 20-01-090, § 51-50-2603, filed 12/12/19, effective 7/1/20; WSR 16-03-064, § 51-50-2603, filed 1/19/16, effective 7/1/16.]
R.51-50-51-50-2702 Section 2702—Emergency and standby power systems.
0.5K chars
2702.1.5 Load duration. Emergency power systems and standby power systems shall be designed to provide the required power for a minimum duration of 8 hours without being refueled or recharged, unless specified otherwise in this code.EXCEPTION:The minimum duration of all required …
R.51-50-51-50-2900 Reserved.
1.3K chars
[Statutory Authority: RCW 19.27.031 and 19.27.074. WSR 22-13-094, 23-12-103, and 23-20-023, § 51-50-2900, filed 6/14/22, 6/7/23, and 9/25/23, effective 3/15/24; WSR 21-06-035, § 51-50-2900, filed 2/23/21, effective 3/26/21; WSR 20-21-021, § 51-50-2900, filed 10/9/20, effective 11…
R.51-50-51-50-2901 Section 2901—General.
1.2K chars
2901.1 Scope. The provisions of this chapter and the state plumbing code shall govern the design, construction, erection, and installation of plumbing components, appliances, equipment and systems used in buildings and structures covered by this code. Toilet and bathing rooms sha…