R.316.110 Examination, identification, installation, use, and listing of equipment
0.8K chars
SPS 316.110 Examination, identification, installation, use, and listing of equipment. (1) Substitute the following wording for the requirements in 2011 NEC 110.3 (B): Listed or labeled equipment shall be installed or used, or both, in accordance with any instructions included in …
R.316.210 Branch circuits
2.4K chars
SPS 316.210 Branch circuits. (1) GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (a) The re- quirements in 2017 NEC 210.8 (A) (7) do not apply to sinks located in kitchens. (b) The requirements in 2017 NEC 210.8 (A) (9) and (10) are not included as part of this chapter…
R.316.220 Branch-circuit, feeder and service
1.6K chars
SPS 316.220 Branch-circuit, feeder and service calculations. (1) GENERAL. This is a department exception to the requirements in 2011 NEC 220.10: Circuit load calculations may use unit load values lower than those identified in NEC Table 220.12 for lighting loads calculated using …
R.316.225 Outside branch circuits and feeders
1.1K chars
SPS 316.225 Outside branch circuits and feeders. (1) CLEARANCES FROM BUILDINGS FOR CONDUCTORS NOT OVER 600 VOLTS. Substitute the following wording for 2011 NEC 225.19 (A) Exception No. 4: The requirement for maintaining the vertical clearance 3 feet from the edge of the roof does…
R.316.230 Services
3.5K chars
SPS 316.230 Services. (1) NUMBER OF SERVICES. (a) This is a department informational note to be used under 2011 and 2017 NEC 230.2 (intro.): Note: It is recommended that the electric utility or cooperative supplying electric current be contacted prior to service equipment install…
R.316.240 Overcurrent protection
0.1K chars
SPS 316.240 Overcurrent protection. The requirements in 2017 NEC 240.67 do not apply to this chapter.
R.316.250 Grounding and bonding
2.7K chars
SPS 316.250 Grounding and bonding. (1) SUPPLEMENTAL ELECTRODE REQUIRED. The exception in 2011 and 2017 NEC 250.53 (A) (2) is not included as part of this chapter. (2) SUPPLEMENTAL ELECTRODE. This is a department rule in addition to the requirements in 2011 and 2017 NEC 250.53 (A)…
R.316.310 Conductors for general wiring
1.4K chars
SPS 316.310 Conductors for general wiring. (1) This is a department rule in addition to the requirements in 2011 NEC 310.15 (B) (3) (a): The derating factors shown in NEC Table 310.15 (B) (3) (a) do not apply to branch circuits supplying an individual dwelling unit except under t…
R.316.312 Cabinets, cutout boxes and meter
0.9K chars
SPS 316.312 Cabinets, cutout boxes and meter socket enclosures. (1) CABLES. Substitute the following wording for 2011 and 2017 NEC 312.5 (C) Exception (intro.): QUIREMENTS FOR PRIVATE ONSITE WASTEWATER TREATMENT the chapter was last published. SPS 316.312 WISCONSIN ADMINISTRATIVE…
R.316.314 Outlet, device, pull and junction
0.8K chars
SPS 316.314 Outlet, device, pull and junction boxes; conduit bodies; fittings; and handhole enclosures. (1) CONDUCTORS ENTERING BOXES, CONDUIT BODIES, OR FITTINGS. This is a department exception to the requirements of 2011 and 2017 NEC 314.17 (B) and (C): Exception: Nonmetallic s…
R.316.334 Nonmetallic-sheathed cable: Types
0.4K chars
SPS 316.334 Nonmetallic-sheathed cable: Types NM, NMC and NMS. (1) USES PERMITTED. Substitute the following wording for 2011 and 2017 NEC 334.10 (3): Other structures permitted to be of Types III, IV, and V construction except as prohibited in NEC 334.12. (2) TYPES NM, NMC, AND N…
R.316.358 Uses permitted
0.3K chars
SPS 316.358 Uses permitted. This is a department rule in addition to the requirements of 2011 and 2017 NEC 358.12: Electrical metallic tubing may not be used in direct contact with earth, in concrete slabs or floors poured on earth, or in exterior concrete walls below grade.
R.316.400 Flexible cords and cables
0.9K chars
SPS 316.400 Flexible cords and cables. (1) This is a department exception in addition to the exception in 2011 NEC 400.8 (4): Exception No. 2: Flexible cords and cables permitted by NEC 400.7 (A) that are connected to sources other than busways may be attached to adequately suppo…
R.316.404 Switches controlling lighting loads
0.1K chars
SPS 316.404 Switches controlling lighting loads. The requirements in 2017 NEC 404.2 (C) do not apply to dwelling units.
R.316.406 Receptacles, cord connectors and attachment plugs (caps)
0.4K chars
SPS 316.406 Receptacles, cord connectors and attachment plugs (caps). (1) The requirements in 2011 and 2017 NEC 406.4 (D) (4) are not included as part of this chapter. (2) Substitute the following wording for 2017 NEC 406.9 (B) (1): Receptacles of 15 and 20 amperes, 125 and 250 v…
R.316.450 Transformers and transformer vaults
0.6K chars
SPS 316.450 Transformers and transformer vaults (including secondary ties). (1) OVERCURRENT PROTECTION. This is a department rule in addition to the requirements in 2011 and 2017 NEC Table 450.3 (A) Note 3: The qualified person shall be either an employee at that location or an e…
R.316.511 Commercial garages, repair and storage
1.7K chars
SPS 316.511 Commercial garages, repair and storage. (1) The requirements specified in 2011 NEC 511.3 (C) (1) (a) are not included as part of this chapter. (2) Substitute the following wording for 2011 NEC 511.3 (C) (2) (a): The ceiling area shall be unclassified where ventilation…
R.316.547 Agricultural buildings
0.5K chars
SPS 316.547 Agricultural buildings. This is a department exception to the requirements in 2011 and 2017 NEC 547.5 (G): Exception: Ground-fault circuit-interrupter protection is not required for a single receptacle providing power for an electric the chapter was last published. 9 …
R.316.551 Recreational vehicles and recreational vehicle parks
0.5K chars
SPS 316.551 Recreational vehicles and recreational vehicle parks. Substitute the following wording for 2017 NEC 551.71 (C): A minimum of 20 percent of existing and 40 percent of all new recreational vehicle sites, with electrical supply, shall each be equipped with a 50-ampre, 12…
R.316.620 Elevators, dumbwaiters, escalators,
0.6K chars
SPS 316.620 Elevators, dumbwaiters, escalators, moving walks, platform lifts and stairway chairlifts. This is a department exception to the requirements in 2011 and 2017 NEC 620: Exception: Wherever NEC 620 requires disconnecting means with overcurrent protection to be located in…
R.316.675 Electrically driven or controlled irrigation machines
0.5K chars
SPS 316.675 Electrically driven or controlled irrigation machines. (1) This is a department rule in addition to the requirements in 2011 NEC 675.8: A service disconnecting means with overcurrent protection shall be provided at the service point in accordance with NEC 230 subchapt…
R.316.680 Swimming pools, fountains and similar installations
0.6K chars
SPS 316.680 Swimming pools, fountains and similar installations. (1) PERIMETER SURFACES. This is a department rule in addition to the requirements of 2011 NEC 680.26 (B) (2): The requirements specified in NEC 680.26 (B) (2) do not apply to a listed self-contained spa or hot tub c…
R.316.700 Emergency systems
1.4K chars
SPS 316.700 Emergency systems. (1) WIRING, EMERGENCY SYSTEM. This is a department rule in addition to the requirements of 2011 and 2017 NEC 700.10 (B): (a) Except as provided in par. (b), emergency circuit wiring shall be listed raceways, Type AC cable or Type MC cable. (b) Emerg…
R.316.701 Legally required standby systems
1.1K chars
SPS 316.701 Legally required standby systems. (1) ADDITION. This is a department rule in addition to the requirements in 2011 and 2017 NEC 701.12 (intro.): The enclosure of the alternate source of power located outdoors for legally required standby systems shall be located at lea…
R.318.1001 Purpose
0.3K chars
SPS 318.1001 Purpose. Pursuant to ss. 101.982 and 101.983, Stats., the purpose of this chapter is to establish minimum safety standards for the design, construction, installation, operation, inspection, testing, maintenance, alteration, repair, and replacement of conveyances. Aug…
R.318.1002 Scope
0.1K chars
SPS 318.1002 Scope. This chapter applies to conveyances as defined in s. SPS 318.1004 (10).
R.318.1003 Application
0.3K chars
SPS 318.1003 Application. (1) RETROACTIVITY. (a) The design, construction, and installation rules of this chapter, including the acceptance-inspection requirements and the applied criteria from the standards adopted in s. SPS 318.1005, do not apply retroactively to conveyances ex…
R.318.1004 Definitions
7.1K chars
SPS 318.1004 Definitions. In this chapter: (1) XAgent municipalityY means any municipality designated as an agent of the department under s. SPS 318.1012 (1) (a). (2) XAlterationY means any change to equipment, including its parts, components, or subsystems, other than maintenanc…
R.318.1005 Adoption of standards by reference
1.0K chars
SPS 318.1005 Adoption of standards by reference. (1) PRIMARY STANDARDS. The following standards are hereby incorporated by reference into this chapter, subject to the modifications specified in this chapter: (a) Safety Code for Elevators and Escalators, ASME A17.1]2016/CSA B44]16…
R.318.1006 Fees
0.3K chars
SPS 318.1006 Fees. Fees for plan review, permit application, inspection, permit to operate, and other services performed by the department pertaining to elevators, escalators, and lift devices shall be as determined in ch. SPS 302. 2014 No. 704, eff. 9-1-14.
R.318.1007 Plan review and approval
9.9K chars
SPS 318.1007 Plan review and approval. (1) APPROVALS. (a) 1. Before commencing the construction or installation of a conveyance, an approval shall be obtained from the department or agent municipality within whose boundaries the conveyance is to be located. 2. Before commencing a…
R.318.1008 Plan review actions
4.9K chars
SPS 318.1008 Plan review actions. (1) PROCESSING. The department shall review and make a determination on a request for plan approval within 15 business days, except as provided in sub. (2) (d). (2) DETERMINATIONS. (a) Conditional approval. 1. If the department determines the app…
R.318.1010 Product approvals
2.3K chars
SPS 318.1010 Product approvals. (1) VOLUNTARY APPROVAL. (a) Materials, equipment, and products regulated by this chapter may receive a written approval from the department indicating code compliance. (b) 1. Approval of materials, equipment, and products shall be based on sufficie…
R.318.1011 Inspections and permits to operate
9.2K chars
SPS 318.1011 Inspections and permits to operate. (1) GENERAL. Pursuant to s. 101.983 (2), Stats., no person may allow a conveyance to operate on property owned by the person unless the person holds a valid permit to operate for the conveyance, except this requirement does not app…
R.318.1012 Agent municipalities
1.4K chars
SPS 318.1012 Agent municipalities. (1) DESIGNATION. (a) Pursuant to ss. 101.12 and 101.983 (4), Stats., the department may designate a municipality as an agent of the department and thereby assign the authority to review and approve conveyance plans and specifications, conduct in…
R.318.1013 Accident reporting
1.9K chars
SPS 318.1013 Accident reporting. (1) (a) Any bodily injury requiring more than first-aid treatment, that occurs in conjunction with a conveyance, shall be reported by the owner or owner[s agent to the department or agent municipality within 2 business days of the injury, except a…
R.318.1014 Petition for variance
0.9K chars
SPS 318.1014 Petition for variance. A petition for variance relating to a provision in this chapter may be submitted and shall be processed in accordance with ch. SPS 303. The petition for variance shall include, where applicable, a position statement from the fire department or …
R.318.1015 Enforcement
0.2K chars
SPS 318.1015 Enforcement. Where an agent municipality administers and enforces this chapter, a regulated item or activity shall be directed to or addressed by the agent municipality before requesting input from the department.
R.318.1016 Appeals
0.8K chars
SPS 318.1016 Appeals. (1) APPEAL OF DEPARTMENT ORDER. Pursuant to s. 101.02 (6) (e), Stats., any person who owns or operates a conveyance that is affected by an order of the department may petition the department for a hearing on the reasonableness of the order. (2) APPEAL OF LOC…
R.318.1017 Penalties
0.1K chars
SPS 318.1017 Penalties. Penalties for violations of this chapter are subject to and may be assessed in accordance with s. 101.988 (3), Stats.
R.318.1018 Investigations initiated by public
1.2K chars
SPS 318.1018 Investigations initiated by public. (1) VERIFICATION OF RECEIPT. The department shall provide verification of receipt for any notice filed in accordance with s. 101.988 (1) (b), Stats. The department shall provide electronic Note: The department may be contacted by t…
R.318.1700 Changes, additions, or omissions to
0.8K chars
SPS 318.1700 Changes, additions, or omissions to ASME A17.1. (1) GENERAL. Elevators, escalators, moving walks, and lifts shall be designed, constructed, installed, operated, maintained, tested, and inspected in accordance with ASME A17.1, except as otherwise provided in this chap…
R.318.1701 Scope, application, and definitions
2.8K chars
SPS 318.1701 Scope, application, and definitions. (1) Substitute the following informational notes for the requirements in ASME A17.1 section 1.1: Note: See sections SPS 318.1002 and 318.1003 for scope and application requirements. Note: See ASME A18.1 and subchapter V for requir…
R.318.1702 Electric elevators
10.0K chars
SPS 318.1702 Electric elevators. (1) PIT DRAINS AND (a) This is a department informational note to be used under ASME A17.1 section 2.2.2.3: SUMPS. Note: See ch. SPS 362 of the building code for hoistway drain and sump requirements for elevators in commercial buildings. (b) Subst…
R.318.1703 Hydraulic Elevators
2.1K chars
SPS 318.1703 Hydraulic Elevators. (1) HYDRAULIC JACKS. Substitute the following wording for the requirements in ASME A17.1 section 3.18.3.8.3(b): (a) The cylinder bottom and sides below the pit floor shall be completely surrounded by a protective material designed to withstand a …
R.318.1705 Special application elevators
5.1K chars
SPS 318.1705 Special application elevators. (1) LIMITED-USE, LIMITED-APPLICATION ELEVATORS. Substitute the following wording for the requirements in ASME A17.1 section 5.2.1.7: Equipment shall be permitted to be located in rooms containing other equipment essential for the operat…
R.318.1707 Dumbwaiter and Type B material
28.5K chars
SPS 318.1707 Dumbwaiter and Type B material lifts. (1) POWER AND HAND DUMBWAITERS WITHOUT AUTOMATIC TRANSFER DEVICES. Substitute the following wording for the requirements in ASME A17.1 Part 7, Scope: This part applies to power dumbwaiters and Type B material lifts. (2) HOISTWAY-…
SPS-318-318.17081 Security
0.0K chars
SPS 318.17081 Security.
SPS-318-318.170810 Acceptance inspections and tests, general requirements
0.1K chars
SPS 318.170810 Acceptance inspections and tests, general requirements.
SPS-318-318.170811 General requirements for periodic inspections and witnessing of
6.0K chars
SPS 318.170811 General requirements for periodic inspections and witnessing of tests. SPS 318.1709 Reference codes, standards, and specifications. Subchapter V — Changes, Additions, or Omissions to ASME A18.1 SPS 318.1800 Platform lifts and stairway lifts. SPS 318.1801 Scope, app…