RCSA 16-243-11 Exceptions
0.4K chars
Regulations of Connecticut State AgenciesSec. 16-243-11. ExceptionsThe installation procedures set forth in sections 16-243-1 to 16-243-12, inclusive, of the regulations of Connecticut state agencies, shall be followed unless a specific alteration, on a case by case basis, is all…
RCSA 16-243-12 Maintenance responsibilities
1.3K chars
Regulations of Connecticut State AgenciesSec. 16-243-12. Maintenance responsibilities(a) All new, relocated or revised attachments to poles owned by a public service company shall be accomplished by the electric distribution company, having an interest in said pole, or its author…
RCSA 16-243-2 Driven ground rods
0.4K chars
Regulations of Connecticut State AgenciesSec. 16-243-2. Driven ground rodsAt each foundation, handhole, and at each riser locating not associated with a foundation or handhole, a ⅝″ x 8′ minimum, driven ground rod shall be provided and conected to all controllers, conduits, walk …