2017-12-E5-2017-12-E515 LABORATORY VENTILATING SYSTEMS
1.2K chars
515 LABORATORY VENTILATING SYSTEMS 515.1 Laboratory hoods. Laboratory hoods and laboratory ventilating systems shall be designed and installed in accordance with NFPA 45. SOURCE: Final Rulemaking published at 67 DCR 6078 (May 29, 2020 – Part 2). The District of Columbia Mechanica…
2017-12-E6-2017-12-E607 DUCT AND TRANSFER OPENINGS
5.9K chars
607 DUCT AND TRANSFER OPENINGS Strike Sections 607.5.4 and 607.5.4.1 of the International Mechanical Code in its entirety and insert new Sections 607.5.4, 607.5.4.1, 607.5.4.2 and 607.5.4.3 in the Mechanical Code in their place to read as follows: 607.5.4 Corridors/smoke barriers…
2017-12-E8-2017-12-E801 GENERAL
2.3K chars
801 GENERAL Strike Section 801.18 of the International Mechanical Code and insert a new Section 801.18 into the Mechanical Code to read as follows: 801.18 Existing chimneys and vents. Where an appliance is permanently disconnected from an existing chimney or vent, or where an app…
2017-12-E9-2017-12-E917 COOKING APPLIANCES
1.9K chars
917 COOKING APPLIANCES Strike Section 917.1 of the International Mechanical Code in its entirety and insert a new Section 917.1 into the Mechanical Code in its place to read as follows: 917.1 Cooking appliances. Cooking appliances that are designed for permanent installation, inc…
2017-12-E9-2017-12-E922 KEROSENE AND OIL-FIRED STOVES
1.3K chars
922 KEROSENE AND OIL-FIRED STOVES Strike Section 922.1 of the International Mechanical Code in its entirety and insert a new Section 922.1 into the Mechanical Code in its place to read as follows: 922.1 General. Kerosene and oil-fired stoves shall not be used or installed in any …
2017-12-F1-2017-12-F101 GENERAL
1.3K chars
101 GENERAL 101.1 Scope and Intent. Scope and intent of the Plumbing Code shall be governed by Chapter 1 of the Building Code, Title 12-A DCMR. 101.2 Administration and Enforcement. Administration and enforcement of the Plumbing Code shall be governed by Chapter 1 of the Building…
2017-12-F11-2017-12-F1101 GENERAL
1.8K chars
1101 GENERAL Strike Section 1101.2 in the International Plumbing Code in its entirety and insert a new Section 1101.2 into the Plumbing Code in its place to read as follows: 1101.2 Disposal. All roofs, paved areas, yards, courts and courtyards shall drain into a separate storm se…
2017-12-F13-2017-12-F1301 GENERAL
18.5K chars
1301 GENERAL 1301.1 Scope. The provisions of Chapter 13 shall govern the materials, design, construction and installation of systems for the collection, storage, treatment and distribution of nonpotable water. The use and application of nonpotable water shall comply with laws, ru…
2017-12-F13-2017-12-F1303 NONPOTABLE RAINWATER COLLECTION AND DISTRIBUTION SYSTEMS
7.1K chars
1303 NONPOTABLE RAINWATER COLLECTION AND DISTRIBUTION SYSTEMS Strike Section 1303.1 of the International Plumbing Code in its entirety and insert new Section 1303.1 into the Plumbing Code in its place to read as follows: 1303.1 General. The provisions of Section 1303 shall govern…
2017-12-F13-2017-12-F1304 RECLAIMED WATER SYSTEMS
2.8K chars
1304 RECLAIMED WATER SYSTEMS 1304.1 General. The provisions of this section shall govern the construction, installation, alteration and repair of systems supplying reclaimed water. 1304.2 Water pressure-reducing valve or regulator. Where the reclaimed water pressure supplied to t…
2017-12-F14-2017-12-F1400 SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS
1.1K chars
Strike Chapter 14 of the International Plumbing Code in its entirety without substitution. CHAPTER 14 SUBSURFACE LANDSCAPE IRRIGATION SYSTEMS SOURCE: Final Rulemaking published at 67 DCR 6148 (May 29, 2020 – Part 2). The District of Columbia Plumbing Code (2017), referred to as t…
2017-12-F2-2017-12-F202 GENERAL DEFINITIONS
2.9K chars
202 GENERAL DEFINITIONS Insert new definitions into Section 202 of the Plumbing Code to read as follows: CONTACT WATER FEATURE. Fountain or other ornamental water feature that is designed with the intent to allow or entice the public to come into direct contact with the water of …
2017-12-F3-2017-12-F305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS
2.2K chars
305 PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS Strike Section 305.4 of the International Plumbing Code in its entirety and insert a new Section 305.4 into the Plumbing Code in its place to read as follows: 305.4 Freezing. Water, soil and waste pipes shall not be installed…
2017-12-F3-2017-12-F314 CONDENSATE DISPOSAL
1.8K chars
314 CONDENSATE DISPOSAL Strike Section 314.2.1 of the International Plumbing Code in its entirety and substitute a new Section 314.2.1 into the Plumbing Code in its place to read as follows: 314.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be c…
2017-12-F4-2017-12-F403 MINIMUM PLUMBING FACILITIES
3.1K chars
403 MINIMUM PLUMBING FACILITIES 403.1 Minimum number of fixtures. In Table 403.1 of the Plumbing Code, in row Number 5, Institutional, I-4 insert a new footnote “f” in column titled “Bathtubs/ Showers,” to read as follows: Table 403.1 Minimum Number of Required Plumbing Fixturesa…
2017-12-F4-2017-12-F410 DRINKING FOUNTAINS
1.8K chars
410 DRINKING FOUNTAINS Strike Section 410.4 of the International Plumbing Code in its entirety and insert a new Section 410.4 into the Plumbing Code in its place to read as follows: 410.4 Substitution. Where restaurants provide drinking water in a container free of charge, drinki…
2017-12-F6-2017-12-F603 WATER SERVICE
5.3K chars
603 WATER SERVICE Strike Section 603.1 of the International Plumbing Code in its entirety and insert a new Section 603.1 into the Plumbing Code in its place to read as follows: 603.1 Size of water service pipe. The water service pipe shall be sized to supply water to the structur…
2017-12-F6-2017-12-F605 MATERIALS, JOINTS AND CONNECTIONS
1.6K chars
605 MATERIALS, JOINTS AND CONNECTIONS Strike Section 605.2 of the International Plumbing Code and insert a new Section 605.2 into the Plumbing Code in its place to read as follows: 605.2 Lead content of water supply pipe and fittings. Pipe and pipe fittings, including valves and …
2017-12-F6-2017-12-F608 PROTECTION OF POTABLE WATER SUPPLY
4.9K chars
608 PROTECTION OF POTABLE WATER SUPPLY Strike Section 608.13.2 of the International Plumbing Code in its entirety and insert a new Section 608.13.2 into the Plumbing Code in its place to read as follows: 608.13.2 Reduced pressure principle backflow prevention assemblies. Reduced …
2017-12-F6-2017-12-F614 OUTDOOR FOUNTAINS
1.3K chars
614 OUTDOOR FOUNTAINS 614.1 General. Outdoor fountains shall comply with Section 614.2. 614.2 Outdoor fountains. Outdoor fountains shall be designed and installed to minimize as much as practicable the use of potable water. Nonpotable water shall not be used for outdoor contact w…
2017-12-F7-2017-12-F712 SUMPS AND EJECTORS
1.8K chars
712 SUMPS AND EJECTORS Strike Section 712.3.5 of the International Plumbing Code in its entirety and insert a new Section 712.3.5 into the Plumbing Code in its place to read as follows: 712.3.5 Pump connection to the drainage system. Pumps connected to the drainage system shall c…
2017-12-F7-2017-12-F715 BACKWATER VALVES
2.3K chars
715 BACKWATER VALVES Strike Section 715.1 of the International Plumbing Code in its entirety and insert a new Section 715.1 into the Plumbing Code in its place to read as follows: 715.1 Sewage backflow. Where plumbing fixtures are installed on a floor with a finished floor elevat…
2017-12-F8-2017-12-F802 INDIRECT WASTES
1.7K chars
802 INDIRECT WASTES Strike Section 802.3 of the International Plumbing Code in its entirety and insert a new Section 802.3 into the Plumbing Code in its place to read as follows: 802.3 Waste receptors. Waste receptors shall be of an approved type. A removable strainer or basket s…
2017-12-F9-2017-12-F903 VENT TERMINALS
1.4K chars
903 VENT TERMINALS 903.1 Roof extension. Open vent pipes that extend through a roof shall be terminated not less than 12 inches (304.8 mm) above the roof. Where a roof or a portion thereof is to be used for assembly or as a promenade, observation deck, sunbathing deck or similar …
2017-12-G1-2017-12-G101 GENERAL
2.5K chars
101 GENERAL 101.1 Title. The Property Maintenance Code shall consist of the 2015 edition of the International Property Maintenance Code (International Property Maintenance Code), as amended by the Property Maintenance Code Supplement (Title 12-G DCMR) of the Construction Codes Su…
2017-12-G1-2017-12-G102 APPLICABILITY
7.3K chars
102 APPLICABILITY Strike Section 102 of the International Property Maintenance Code in its entirety and insert new Section 102 in the Property Maintenance Code in its place to read as follows: 102.1 Code Precedence. Unless otherwise provided herein, or in the Construction Codes A…
2017-12-G1-2017-12-G103 DEPARTMENT OF CONSUMER AND REGULATORY AFFAIRS
2.0K chars
103 DEPARTMENT OF CONSUMER AND REGULATORY AFFAIRS Strike Section 103 of the International Property Maintenance Code in its entirety and insert new Section 103 in the Property Maintenance Code in its place to read as follows: 103.1 Department of Consumer and Regulatory Affairs. Th…
2017-12-G1-2017-12-G104 DUTIES AND POWERS OF THE CODE OFFICIAL
9.0K chars
104 DUTIES AND POWERS OF THE CODE OFFICIAL Strike Section 104 of the International Property Maintenance Code in its entirety and insert new Section 104 in the Property Maintenance Code in its place to read as follows: 104.1 General. The code official shall enforce the provisions …
2017-12-G1-2017-12-G105 APPROVAL
3.3K chars
105 APPROVAL Strike Section 105 of the International Property Maintenance Code in its entirety and insert new Section 105 in the Property Maintenance Code in its place to read as follows: 105.1 Modifications. Whenever there are practical difficulties involved in carrying out the …
2017-12-G1-2017-12-G106 VIOLATIONS, REMEDIES, PENALTIES AND OTHER ENFORCEMENT ACTIONS
17.1K chars
106 VIOLATIONS, REMEDIES, PENALTIES AND OTHER ENFORCEMENT ACTIONS Strike Section 106 of the International Property Maintenance Code in its entirety and insert new Section 106 in the Property Maintenance Code in its place to read as follows: 106.1 Unlawful acts. It shall be unlawf…
2017-12-G1-2017-12-G107 APPEALS
5.7K chars
107 APPEALS Strike Section 107 of the International Property Maintenance Code in its entirety and insert new Section 107 in the Property Maintenance Code in its place to read as follows: 107.1 Appeal of a Final Decision of the Code Official based on Alleged Violations of the Prop…
2017-12-G1-2017-12-G108 UNSAFE CONDITIONS
15.7K chars
108 UNSAFE CONDITIONS Strike Section 108 of the International Property Maintenance Code in its entirety and insert new Section 108 in the Property Maintenance Code in its place to read as follows: 108.1 General. Unsafe conditions shall be removed or made safe and secure as the co…
2017-12-G1-2017-12-G109 EMERGENCY CONDITIONS
10.6K chars
109 EMERGENCY CONDITIONS Strike Section 109 of the International Property Maintenance Code in its entirety and insert new Section 109 in the Property Maintenance Code in its place to read as follows: 109.1 Emergency Condition. When an emergency condition exists, the code official…
2017-12-G1-2017-12-G110 DEMOLITION
1.5K chars
110 DEMOLITION Strike Section 110 of the International Property Maintenance Code in its entirety and insert new Section 110 in the Property Maintenance Code in its place to read as follows: 110.1 Demolition of deteriorated structures. The code official is authorized to initiate p…
2017-12-G2-2017-12-G202 GENERAL DEFINITIONS
5.0K chars
202 GENERAL DEFINITIONS Insert the following new definitions into Section 202 of the Property Maintenance Code: COMMON SPACE. All portions of the premises used in common by the occupants of a building or structure not under the exclusive control of a single tenant. GROWING SEASON…
2017-12-G3-2017-12-G302 EXTERIOR PROPERTY AREAS
5.0K chars
302 EXTERIOR PROPERTY AREAS Strike Section 302.1 of the International Property Maintenance Code in its entirety and insert a new Section 302.1 into the Property Maintenance Code in its place to read as follows: 302.1 Sanitation. All exterior property and premises shall be maintai…
2017-12-G3-2017-12-G304 EXTERIOR STRUCTURE
8.1K chars
304 EXTERIOR STRUCTURE Insert a new Section 304.2.1 into the Property Maintenance Code to read as follows: 304.2.1 Elimination of peeling, flaking and chipped paint in pre-1978 structures. In structures (including building components) built before 1978, peeling, flaking and chipp…
2017-12-G3-2017-12-G305 INTERIOR STRUCTURE
3.1K chars
305 INTERIOR STRUCTURE Strike Section 305.3 in the International Property Maintenance Code in its entirety and insert new Section 305.3 and 305.3.1 in the Property Maintenance Code in its place to read as follows: 305.3 Interior surfaces. All interior surfaces, including windows …
2017-12-G3-2017-12-G307 HANDRAILS AND GUARDRAILS
2.0K chars
307 HANDRAILS AND GUARDRAILS Strike Section 307.1 of the International Property Maintenance Code in its entirety and insert a new Section 307.1 into the Property Maintenance Code in its place to read as follows: 307.1 General. Every exterior and interior flight of stairs having m…
2017-12-G3-2017-12-G308 RUBBISH AND GARBAGE
4.1K chars
308 RUBBISH AND GARBAGE Strike Section 308.1 of the International Property Maintenance Code in its entirety and insert a new Section 308.1 in the Property Maintenance Code in its place to read as follows: 308.1 Accumulation of rubbish or garbage. All exterior property and premise…
2017-12-G3-2017-12-G309 PEST ELIMINATION
4.5K chars
309 PEST ELIMINATION Strike Section 309 of the International Property Maintenance Code in its entirety and insert a new Section 309 into the Property Maintenance Code in its place to read as follows: 309.1 Infestation. All structures shall be kept free from insect and rodent infe…
2017-12-G3-2017-12-G310 CARBON MONOXIDE ALARMS
12.1K chars
310 CARBON MONOXIDE ALARMS 310.1 Carbon monoxide detection. Carbon monoxide detection shall be provided in Group I-1, I-2, I-4 and R occupancies, in buildings regulated by the Residential Code, and in classrooms in Group E occupancies, where required by and in accordance with Sec…
2017-12-G4-2017-12-G401 GENERAL
2.2K chars
401 GENERAL Strike Section 401.3 in the International Property Maintenance Code in its entirety and insert new Section 401.3 into the Property Maintenance Code in its place to read as follows: 401.3 Window obstruction where natural light or natural ventilation is required. Exteri…
2017-12-G4-2017-12-G402 LIGHT
5.1K chars
402 LIGHT Strike Section 402.1 of the International Property Maintenance Code in its entirety and insert new Section 402.1 in its place in the Property Maintenance Code to read as follows: 402.1 General. Every space intended for human occupancy shall be provided with natural ligh…
2017-12-G4-2017-12-G403 VENTILATION
1.8K chars
403 VENTILATION Strike Section 403.1 of the International Property Maintenance Code in its entirety and insert new Section 403.1 in its place in the Property Maintenance Code to read as follows: 403.1 General. Every space intended for human occupancy shall be provided with natura…
2017-12-G4-2017-12-G404 OCCUPANCY LIMITS
5.0K chars
404 OCCUPANCY LIMITS Strike Section 404.1 in the International Property Maintenance Code in its entirety and insert new Section 404.1 in the Property Maintenance Code in its place to read as follows: 404.1 Privacy. Dwelling units, hotel units, housekeeping units, rooming units an…
2017-12-G5-2017-12-G503 TOILET ROOMS
1.8K chars
503 TOILET ROOMS Strike Section 503.4 of the International Property Maintenance Code in its entirety and insert new Section 503.4 in the Property Maintenance Code in its place to read as follows: 503.4 Floor surface. In other than dwelling units, every toilet room floor and every…
2017-12-G5-2017-12-G505 WATER SYSTEM
1.6K chars
505 WATER SYSTEM 505.4 Water heating facilities. Insert a new Section 505.4.1 into the Property Maintenance Code to read as follows: 505.4.1 Inspection. The owner or operator of a housing business, with one or more dwelling units occupied by a tenant or tenants served by a water …
2017-12-G6-2017-12-G602 HEATING FACILITIES
4.6K chars
602 HEATING FACILITIES Strike Section 602.2 of the International Property Maintenance Code in its entirety and insert new Section 602.2 into the Property Maintenance Code in its place to read as follows: 602.2 Residential occupancies. Dwellings shall be provided with heating faci…
2017-12-G6-2017-12-G603 MECHANICAL EQUIPMENT
2.9K chars
603 MECHANICAL EQUIPMENT 603.1 Mechanical appliances. Insert new Section 603.1.1 into the Property Maintenance Code to read as follows: 603.1.1 Prohibited Locations. Gas meters and fuel-fired appliances and equipment shall not be located in sleeping rooms, bathrooms, toilet rooms…