R.8-1001 IFGC Section 401.9 Identification
0.1K chars
8-1001. IFGC Section 401.9 Identification. This section is deleted without substitution.
R.8-1002 IFGC Section 401.10 Third-party testing and certification
0.3K chars
8-1002. IFGC Section 401.10 Third-party testing and certification. All piping, tubing and fittings shall comply with the applicable referenced standards, specifications and performance criteria of this code, including Section 403 of the South Carolina Fuel Gas Code and correspond…
R.8-1003 IFGC Section 412.4 Listed equipment
0.2K chars
8-1003. IFGC Section 412.4 Listed equipment. Hoses, hose connections, vehicle fuel connections, dispensers, LP-gas pumps and electrical equip- ment used for LP-gas shall comply with the requirements of NFPA 58.
R.8-1004 IFGC Section 412.6 Location
1.3K chars
8-1004. IFGC Section 412.6 Location. In addition to the fuel dispensing requirements of the South Carolina Fire Code, the point of transfer for dispensing operations shall be 25 feet (7620 mm) or more from buildings having combustible exterior wall surfaces, buildings having nonc…
R.8-1005 IFGC Section 412.8.3 Vehicle impact protection
0.2K chars
8-1005. IFGC Section 412.8.3 Vehicle impact protection. Exception: An alternative method may be used that meets the intent of this section with the approval of the AHJ.
R.8-1006 IFGC Section 412.10 Private fueling of motor vehicles
0.6K chars
8-1006. IFGC Section 412.10 Private fueling of motor vehicles. Self-service LP-gas dispensing systems, including key, code and card lock dispensing systems, shall not be open to the public. In addition to the requirements of the South Carolina Fire Code, self-service LP-gas dispe…
R.8-1007 IFGC Section 505.1.1 Commercial cooking appliances vented by exhaust hoods
1.6K chars
8-1007. IFGC Section 505.1.1 Commercial cooking appliances vented by exhaust hoods. Where commercial cooking appliances are vented by means of the Type I or Type II kitchen exhaust hood system that serves such appliances, the exhaust system shall be fan powered and the appliances…
R.8-110 Registration Required. As evidence of registration, a certificate of registration must be issued by the Council, to each
0.5K chars
8-110. Registration Required. As evidence of registration, a certificate of registration must be issued by the Council, to each qualifying person. The certificate of registration must set forth the classification(s) for which the person is qualified to practice. HISTORY: Added by…
R.8-1101 Repealed
0.0K chars
8-1101. Repealed.
R.8-1102 Repealed
0.0K chars
8-1102. Repealed.
R.8-1103 NEC Article 210.8(A) Dwelling Units
2.1K chars
8-1103. NEC Article 210.8(A) Dwelling Units. All 125-volt receptacles installed in the locations specified in 210.8(A)(1) through (A)(11) and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit- interrupter protection for per…
R.8-1104 NEC Article 210.8(F) Outdoor Outlets
0.1K chars
8-1104. NEC Article 210.8(F) Outdoor Outlets. This article does not apply in this State.
R.8-1105 NEC Article 210.12(A) Dwelling Units
3.4K chars
8-1105. NEC Article 210.12(A) Dwelling Units. All 120-volt, single-phase, 15- and 20- ampere branch circuits supplying outlets or devices installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, …
R.8-1106 NEC Article 230.67 Surge Protection
0.9K chars
8-1106. NEC Article 230.67 Surge Protection. This article, including (A) through (D), does not apply in this State. HISTORY: Added by State Register Volume 37, Issue No. 6, eff June 28, 2013. Amended by State Register Volume 40, Issue No. 6, Doc. No. 4602, eff June 24, 2016; SCSR…
R.8-115 Classifications and Qualifications for Registration. A person applying for registration as a building code enforcement officer or special inspector must
3.0K chars
8-115. Classifications and Qualifications for Registration. A person applying for registration as a building code enforcement officer or special inspector must be certified in accordance with these regulations. An applicant is deemed to be qualified for registration upon submitta…
R.8-120 Requirements for Provisional Certification. A. Building Official
3.0K chars
8-120. Requirements for Provisional Certification. A. Building Official A person registered in the provisional classification of ‘‘Building Official’’ shall be under the direct supervision of the building official for the local jurisdiction for which contracted or employed or act…
R.8-1201 IRC Section R202 Definitions
0.5K chars
8-1201. IRC Section R202 Definitions Accepted Engineering Practice: The performance design of structures and/or structural elements that vary from prescriptive design methods of this code. Such design shall be made with accepted design standards by a South Carolina licensed Archi…
R.8-1202 IRC Section R301.2.1 Wind Design criteria
1.6K chars
8-1202. IRC Section R301.2.1 Wind Design criteria. Buildings and portions thereof shall be constructed in accordance with the previously published maps by the South Carolina Building Codes Council. The local building official may delineate the wind design category within their ju…
R.8-1203 IRC Section R301.2.2.1 Determination of seismic design category
0.4K chars
8-1203. IRC Section R301.2.2.1 Determination of seismic design category. Buildings shall be assigned a seismic design category in accordance with the previously published maps by the S.C. Building Codes Council. The local building official may delineate the seismic design categor…
R.8-1204 IRC Figure R302.1 Exterior walls
1.8K chars
8-1204. IRC Figure R302.1 Exterior walls. Exception 6: Fire Separation Distance a. The minimum fire separation distance for improvement constructed on a lot shown on: [i] a recorded bonded or final subdivision plat, or [ii] a sketch plan, site plan, plan of phased develop- ment o…
R.8-1205 IRC Section R302.4.1 Through penetrations
1.5K chars
8-1205. IRC Section R302.4.1 Through penetrations. Through penetrations of fire-resistance-rated wall or floor assemblies shall comply with Section 302.4.1.1 or R302.4.1.2. No penetrations shall pass completely through the fire rated assembly separating townhouse units. Exception…
R.8-1206 IRC Section R302.5.1 Opening protection
0.4K chars
8-1206. IRC Section R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 1 3/8 inches (35 mm) in th…
R.8-1207 Section R.302.13 Fire Protection of Floors
1.4K chars
8-1207. Section R.302.13 Fire Protection of Floors. Floor assemblies that are not required elsewhere in this code to be fire-resistance rated, shall be provided with a 1/2-inch (12.7 mm) gypsum wallboard membrane, 5/8-inch (16 mm) wood structural panel membrane, or equivalent on …
R.8-1208 IRC Section R303.4 Mechanical ventilation
0.1K chars
8-1208. IRC Section R303.4 Mechanical ventilation. The Building Codes Council does not adopt IRC Section R303.4.
R.8-1209 IRC Figure R307.1 Minimum Fixture Clearances
0.1K chars
8-1209. IRC Figure R307.1 Minimum Fixture Clearances.
R.8-1210 IRC Section R311.7.5.1 Risers
0.9K chars
8-1210. IRC Section R311.7.5.1 Risers. The maximum riser height shall be 73/4 inches (196 mm). The maximum riser height for masonry stairs shall be 8 inches (203 mm). The riser height shall be measured vertically between leading edges of the adjacent treads. The greatest riser he…
R.8-1211 IRC Section R312.1.1 Where required
0.4K chars
8-1211. IRC Section R312.1.1 Where required. Guards shall be located along open-sided walking surfaces of all decks, porches, balconies, floors, stairs, ramps and landings that are located more than 30 inches measured vertically to the floor or grade below and at any point where …
R.8-1212 IRC Section R312.2 Window Fall Protection
0.2K chars
8-1212. IRC Section R312.2 Window Fall Protection The Building Codes Council does not adopt IRC Section R312.2. The Building Codes Council does not adopt IRC Section R312.2.1. The Building Codes Council does not adopt IRC Section R312.2.2.
R.8-1213 IRC Section R313 Automatic Fire Sprinkler Systems
1.2K chars
8-1213. IRC Section R313 Automatic Fire Sprinkler Systems. R313.1 Townhouse automatic fire sprinkler systems. An automatic residential fire sprinkler system shall not be required to be installed in townhouses when constructed in accordance with R302.2. Exception: An automatic res…
R.8-1214 IRC Section R317.1.1 Field treatment
0.3K chars
8-1214. IRC Section R317.1.1 Field treatment. Field-cut ends, notches and drilled holes of preservative-treated wood shall be treated in the field in accordance with AWPA M4 or in accordance with the preservative-treated wood product manufactur- er’s recommendations.
R.8-1215 IRC Section 318.1 Subterranean termite control methods
0.3K chars
8-1215. IRC Section 318.1 Subterranean termite control methods. A seventh item is added which reads: 7. Treatments may be conducted as outlined in Section 27-1085 of the Rules and Regulations for the Enforcement of the SC Pesticide Control Act and enforced by the Clemson Universi…
R.8-1216 IRC Section R318.4 Foam Plastic Protection
0.9K chars
8-1216. IRC Section R318.4 Foam Plastic Protection. In areas where the probability of termite infestation is ‘‘very heavy’’ as indicated in Figure R318.4, extruded and expanded polystyrene, polyisocyanurate and other foam plastics shall not be installed on the exterior face or un…
R.8-1217 IRC Section 318.5 Termite Inspection Strip
0.2K chars
8-1217. IRC Section 318.5 Termite Inspection Strip. Where foam plastic is applied in accordance with R318.4, a continuous 6 inch strip centered along the sill plate shall be left open for termite activity inspection.
R.8-1218 IRC Section R322.1 General
0.8K chars
8-1218. IRC Section R322.1 General. Buildings and structures constructed in whole or in part in flood hazard areas, including A or V Zones and Coastal A Zones, as established in Table R301.2(1), and substantial improvement and repair of substantial damage of buildings and structu…
R.8-1219 IRC Section R326.3 Story above grade plane
0.8K chars
8-1219. IRC Section R326.3 Story above grade plane. A habitable attic shall be considered a story above grade plane. Exceptions : A habitable attic shall not be considered to be a story above grade plane provided that the habitable attic meets all the following: 1. The aggregate …
R.8-1220 IRC Section R404.1.9.2 Masonry piers supporting floor girders
1.3K chars
8-1220. IRC Section R404.1.9.2 Masonry piers supporting floor girders. Masonry piers supporting wood girders sized in accordance with Tables R602.7(1) and R602.7(2) shall be permitted in accordance with this section. Piers supporting girders for interior bearing walls shall be fi…
R.8-1221 IRC Section R408.3 Unvented Crawl Space
1.4K chars
8-1221. IRC Section R408.3 Unvented Crawl Space. For unvented under-floor spaces, the following items shall be provided: 1. Exposed earth shall be covered with a continuous vapor retarder meeting ASTME 1745 Class A. Joints of the vapor retarder shall overlap by 6 inches (152 mm) …
R.8-1222 IRC Section R408.4 Access
0.6K chars
8-1222. IRC Section R408.4 Access. Access shall be provided to all under-floor spaces. Access openings through the floor shall be not smaller than 18 inches by 24 inches (457 mm by 610 mm). Openings through a perimeter wall shall be not less than 16 inches by 24 inches (407 mm by…
R.8-1223 IRC Section R408.8 Under-floor vapor retarder
0.1K chars
8-1223. IRC Section R408.8 Under-floor vapor retarder. Section R408.8 is deleted without substitution.
R.8-1224 IRC Section R502.11.4 Truss design drawings
1.6K chars
8-1224. IRC Section R502.11.4 Truss design drawings. Truss design drawings. Truss design drawings, prepared in compliance with Section R502.11.1, shall be provided to the building official at the time of inspection. Truss design drawings shall be provided with the shipment of tru…
R.8-1225 IRC Section R506.2.3 Vapor Retarder
0.7K chars
8-1225. IRC Section R506.2.3 Vapor Retarder. A minimum 10-mil (0.010 inch; 0.254 mm) vapor retarder conforming to ASTM E1745 Class A requirements with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared…
R.8-1226 IRC Section R606.7 Piers
0.6K chars
8-1226. IRC Section R606.7 Piers. The unsupported height of masonry piers shall not exceed 10 times their least dimension. Where structural clay tile or hollow concrete masonry units are used for isolated piers to support beams and girders, the cellular spaces shall be filled sol…
R.8-1227 IRC Section R802.10.1 Wood Truss Design
1.6K chars
8-1227. IRC Section R802.10.1 Wood Truss Design. Truss design drawings, prepared in conformance to Section R802.10 shall be provided to the building official at the time of their inspection. Truss design drawings shall be provided with the shipment of trusses delivered to the job…
R.8-1228 IRC Section R905.2.8.5 Drip Edge
0.2K chars
8-1228. IRC Section R905.2.8.5 Drip Edge. A drip edge shall be provided at eaves and rake edges of asphalt shingle roofs where required by the manufacturer.
R.8-1229 IRC Section M1411.6 Insulation of refrigerant piping
0.3K chars
8-1229. IRC Section M1411.6 Insulation of refrigerant piping. Pipings and fittings for refrigerant vapor (suction) lines shall be insulated with insulation having a thermal resistivity of at least R2.5 hr. ft2 F/Btu and having external surface permeance not exceeding 0.05 perm [2…
R.8-1230 IRC Chapter 11 Energy Efficiency
0.1K chars
8-1230. IRC Chapter 11 Energy Efficiency. The Building Codes Council does not adopt IRC Chapter 11.
R.8-1231 IRC Section M1411.9 Locking access port caps
0.1K chars
8-1231. IRC Section M1411.9 Locking access port caps. IRC Section M1411.9 is deleted without substitution.
R.8-1232 IRC Section M1502.3 Duct termination
0.3K chars
8-1232. IRC Section M1502.3 Duct termination. Exhaust ducts shall terminate on the outside of the building. Exhaust duct terminations shall be in accordance with the dryer manufacturer’s installation instructions. Exhaust duct terminations shall be equipped with a backdraft dampe…
R.8-1233 IRC Section M1502.4.2 Duct Installation
1.0K chars
8-1233. IRC Section M1502.4.2 Duct Installation. Exhaust ducts shall be supported at intervals not to exceed 8 feet and within 16 inches of each side of a joint that is not installed in a vertical orientation, secured in place, making rigid contact with the duct at not less than …
R.8-1234 IRC Section M1502.4.6 Duct length
0.2K chars
8-1234. IRC Section M1502.4.6 Duct length. The maximum length of a clothes dryer exhaust duct shall not exceed 35 feet (10668 mm) from the dryer location to the wall or roof termination.