51-11C-51-11C-40340 Section C403.4—HVAC system controls.
0.9K chars
C403.4 HVAC system controls. HVAC systems shall be provided with controls in accordance with Sections C403.4.1 through C403.4.12 and shall be capable of and configured to implement all required control functions in this code.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27…
51-11C-51-11C-40341 Section C403.4.1—Thermostatic controls.
8.1K chars
C403.4.1 Thermostatic controls. The supply of heating and cooling energy to each zone shall be controlled by individual thermostatic controls capable of responding to temperature within the zone. Controls in the same zone or in neighboring zones connected by openings larger than …
51-11C-51-11C-40342 Section C403.4.2—Off-hour controls.
3.6K chars
C403.4.2 Off-hour controls. For all occupancies other than Group R, each zone shall be provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system.EXCEPTIONS:1. Zones that will be operated continuously. 2. Zones…
51-11C-51-11C-40343 Section C403.4.3—Hydronic systems controls.
4.7K chars
C403.4.3 Hydronic systems controls. The heating of fluids that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Sections C403.4.3.1 through C403.4.3.3. Hydronic heating systems com…
51-11C-51-11C-403431 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-403431, filed 1/19/16, effective 7/1/16. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-403431, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40344 Section C403.4.4—Part load controls.
3.8K chars
C403.4.4 Part load controls. Hydronic systems greater than or equal to 300,000 Btu/h (88 kW) in design output capacity supplying heated or chilled water to comfort conditioning systems shall include controls that are configured to:1. Automatically reset the supply-water temperatu…
51-11C-51-11C-40345 Section C403.4.5—Pump isolation.
1.1K chars
C403.4.5 Pump isolation. Chilled water plants including more than one chiller shall be capable of and configured to reduce flow automatically through the chiller plant when a chiller is shut down and automatically shut off flow to chillers that are shut down. Chillers piped in se…
51-11C-51-11C-40346 Section C403.4.6—Variable flow controls.
1.7K chars
C403.4.6 Variable flow controls. Individual pumps required by this code to have variable speed control shall be controlled in one of the following manners:1. For systems having a combined pump motor horsepower less than or equal to 20 hp (15 kW) and without direct digital control…
51-11C-51-11C-40347 Section C403.4.7—Combustion heating equipment controls.
1.1K chars
C403.4.7 Combustion heating equipment controls. Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control.EXCEPTIONS:1. Boilers. 2. Radiant heaters.C403.4.7.1 Combustion decorative vented appliance, combustion fireplace and…
51-11C-51-11C-40348 Sections C403.4.8 through C403.4.10—Group R requirements.
2.7K chars
C403.4.8 Group R-1 hotel/motel guestrooms. See Section C403.7.4.C403.4.9 Group R-2 and R-3 dwelling units. The primary space conditioning system within each dwelling unit shall be provided with at least one programmable thermostat for the regulation of space temperature. The ther…
51-11C-51-11C-40349 Sections C403.4.11 and C403.4.12.
3.7K chars
C403.4.11 Direct digital control systems. Direct digital control (DDC) shall be required as specified in Sections C403.4.11.1 through C403.4.11.4.C403.4.11.1 DDC applications. DDC shall be provided in the applications and qualifications listed in Table C403.4.11.1 and for load ma…
51-11C-51-11C-40350 Section C403.5—Economizers.
8.8K chars
C403.5 Economizers. Air economizers shall be provided on all new cooling systems including those serving computer server rooms, electronic equipment, radio equipment, and telephone switchgear. Economizers shall comply with Sections C403.5.1 through C403.5.5.EXCEPTIONS:1a. For oth…
51-11C-51-11C-40351 Section C403.5.1—Integrated economizer control.
2.1K chars
C403.5.1 Integrated economizer control. Economizer systems shall be integrated with the mechanical cooling system and be configured to provide partial cooling even where additional mechanical cooling is required to provide the remainder of the cooling load. Controls shall not be …
51-11C-51-11C-40352 Section C403.5.2—Economizer heating system impact.
0.5K chars
C403.5.2 Economizer heating system impact. HVAC system design and economizer controls shall be such that economizer operation does not increase building heating energy use during normal operation.EXCEPTION:Economizers on VAV systems that cause zone level heating to increase due t…
51-11C-51-11C-40353 Section C403.5.3—Air economizers.
3.8K chars
C403.5.3 Air economizers. Air economizers shall comply with Sections C403.5.3.1 through C403.5.3.5.C403.5.3.1 Design capacity. Air economizer systems shall be configured to modulate outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity …
51-11C-51-11C-40354 Section C403.5.4—Waterside economizers.
1.4K chars
C403.5.4 Waterside economizers. Waterside economizers shall comply with Sections C403.5.4.1 and C403.5.4.2.C403.5.4.1 Design capacity. Water economizer systems shall be configured to cool supply air by indirect evaporation and providing up to 100 percent of the expected system co…
51-11C-51-11C-40355 Section C403.5.5—Economizer fault detection and diagnostics.
2.0K chars
C403.5.5 Economizer fault detection and diagnostics (FDD). Air-cooled unitary direct-expansion units with a cooling capacity of 54,000 Btu/h or greater listed in the tables in Section C403.3.2 that are equipped with an economizer in accordance with Section C403.5 shall include a …
51-11C-51-11C-40360 Section C403.6—Requirements for mechanical systems serving multiple zones.
7.2K chars
C403.6 Requirements for mechanical systems serving multiple zones. Sections C403.6.1 through C403.6.10 shall apply to mechanical systems serving multiple zones.C403.6.1 Variable air volume (VAV) and multiple zone systems. Supply air systems serving multiple zones shall be VAV sys…
51-11C-51-11C-403610 Section C403.6.10—High efficiency VAV systems.
10.0K chars
C403.6.10 High efficiency variable air volume (VAV) systems. For HVAC systems subject to the requirements of Section C403.3.5 but utilizing Exception 2 of that section, a high efficiency multiple-zone VAV system may be provided without a separate parallel DOAS when the system is …
51-11C-51-11C-4037 Section C403.7—Ventilation and exhaust systems.
0.4K chars
C403.7 Ventilation and exhaust systems. In addition to other requirements of Section C403 applicable to the provisions of ventilation air or the exhaust of air, ventilation and exhaust systems shall be in accordance with Sections C403.7.1 through C403.7.8.[Statutory Authority: RC…
51-11C-51-11C-40371 Section C403.7.1—Demand control ventilation.
2.9K chars
C403.7.1 Demand control ventilation.C403.7.1.1 Spaces requiring demand control ventilation. Demand control ventilation (DCV) shall be provided for the following:1. Spaces with ventilation provided by single-zone systems where an air economizer is provided to comply with Section C…
51-11C-51-11C-40372 Section C403.7.2—Occupancy sensors.
1.3K chars
C403.7.2 Occupancy sensors. Classrooms, gyms, auditoriums, conference rooms, and other spaces with an occupant load greater than or equal to 25 people per 1000 square feet (93 m2) of floor area (as established in Table 403.3.1.1 of the International Mechanical Code) that are larg…
51-11C-51-11C-40373 Section C403.7.3—Ventilation air heating control.
0.6K chars
C403.7.3 Ventilation air heating control. For ventilation air units with supplemental heating capacity that operate in conjunction with zone heating and cooling systems, supplemental heating shall not warm ventilation supply air to a temperature greater than 55°F (13°C).[Statutor…
51-11C-51-11C-40374 Section C403.7.4—HVAC serving guestrooms.
2.9K chars
C403.7.4 Automatic control of HVAC systems serving guestrooms. In Group R-1 buildings containing more than 50 guestrooms, each guestroom shall be provided with controls complying with the provisions of Sections C403.7.4.1 and C403.7.4.2. Card key controls comply with these requir…
51-11C-51-11C-40375 Section C403.7.5—Loading dock and garage ventilation system controls.
3.1K chars
C403.7.5 Loading dock, motor vehicle repair garage, and parking garage ventilation system controls. Mechanical ventilation systems for loading docks, motor vehicle repair garages, and parking garages shall be designed to exhaust the airflow rates (maximum and minimum) determined …
51-11C-51-11C-40376 Section C403.7.6—Energy recovery ventilation systems.
6.2K chars
C403.7.6 Energy recovery ventilation systems. Energy recovery ventilation systems shall be provided as specified in Sections C403.7.6.1 and C403.7.6.2.C403.7.6.1 Ventilation for Group R-2 occupancy. For all Group R-2 dwelling and sleeping units, a balanced ventilation system with…
51-11C-51-11C-40377 Section C403.7.7—Exhaust systems.
6.6K chars
C403.7.7 Exhaust systems.C403.7.7.1 Kitchen exhaust systems.C403.7.7.1.1 Replacement air. Replacement air introduced directly into the exhaust hood cavity shall not be greater than 10 percent of the hood exhaust airflow rate.C403.7.7.1.2 Kitchen exhaust hood certification and max…
51-11C-51-11C-40378 Section C403.7.8—Shutoff dampers.
3.9K chars
C403.7.8 Shutoff dampers. Mechanical openings shall be provided with shutoff dampers in accordance with Sections C403.7.8.1 through C403.7.8.4.C403.7.8.1 Shutoff dampers for building isolation. Outdoor air supply, exhaust openings and relief outlets and stairway and elevator hois…
51-11C-51-11C-4038 Section C403.8—Fan and fan controls.
17.9K chars
C403.8 Fan and fan controls. Fans in HVAC systems shall comply with Sections C403.8.1 through C403.8.5.1.The airflow requirements of Section C403.8.5.1 shall apply to all fan motors. Low capacity ventilation fans shall also comply with Section C403.8.4.C403.8.1 Fan System. Each f…
51-11C-51-11C-4039 Section C403.9—Heat rejection and heat recovery equipment.
7.9K chars
C403.9 Heat rejection and heat recovery equipment.C403.9.1 Heat rejection equipment. Heat rejection equipment, including air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers and evaporative condensers, shall comply with this section.EXCEP…
51-11C-51-11C-40391 Section C403.10—Construction of HVAC system elements.
13.8K chars
C403.10 Construction of HVAC system elements. Ducts, plenums, piping and other elements that are part of an HVAC system shall be constructed and insulated in accordance with Sections C403.10.1 through C403.10.3.1.C403.10.1 Duct and plenum insulation and sealing.C403.10.1.1 Ducts,…
51-11C-51-11C-40392 Section C403.11—Mechanical systems outside the building envelope.
1.6K chars
C403.11 Mechanical systems located outside of the building thermal envelope. Mechanical systems providing heat outside of the thermal envelope of a building shall comply with Sections C403.11.1 through C403.11.3.C403.11.1 Heating outside a building. Systems installed to provide h…
51-11C-51-11C-40393 Section C403.12—High efficiency single zone VAV systems.
6.4K chars
C403.12 High efficiency single-zone variable air volume (VAV) systems. For HVAC systems subject to the requirements of Section C403.3.5 but utilizing Exception 2 of that section, a high efficiency single-zone VAV system may be provided without a separate parallel DOAS when the sy…
51-11C-51-11C-40394 Section C403.13—Dehumidification for plant growth.
1.4K chars
C403.13 Dehumidification in spaces for plant growth and maintenance. Equipment that dehumidifies building spaces used for plant growth and maintenance shall be one of the following:1. Stand-alone dehumidifiers that meet the following minimum integrated energy factors as measured …
51-11C-51-11C-40400 Section C404—Service water heating and pressure-booster systems.
0.3K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40400, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40400, filed 2/1/13, effe…
51-11C-51-11C-40401 Section C404.1—General.
0.7K chars
C404.1 General. This section covers the minimum efficiency of, and controls for, service water-heating equipment and insulation of service hot water piping.EXCEPTION:Energy using equipment used by a manufacturing, industrial or commercial process other than maintaining comfort an…
51-11C-51-11C-40402 Section C404.2—Service water-heating equipment performance efficiency.
7.4K chars
C404.2 Service water-heating equipment performance efficiency. Water-heating equipment and hot water storage tanks shall meet the requirements of Table C404.2. The efficiency shall be verified through certification and listed under an approved certification program, or if no cert…
51-11C-51-11C-404021 Table C404.2—Minimum performance of water-heating equipment.
8.2K chars
Table C404.2Minimum Performance of Water-Heating EquipmentEquipment TypeSize Category(input)Subcategory or Rating ConditionDraw PatternPerformance Requireda,jTest ProcedurebElectric table-top water heatersk≤ 12 kWc≥ 20 gal≤ 120 galVery smallLowMediumHighUEF ≥ 0.6323 - (0.0058 × V…
51-11C-51-11C-40403 Section C404.3—Efficient heated water supply piping.
3.6K chars
C404.3 Efficient heated water supply piping. Heated water supply piping shall be in accordance with Section C404.3.1 or C404.3.2. The flow rate through 1/4-inch (6.4 mm) piping shall be not greater than 0.5 gpm (1.9 L/m). The flow rate through 5/16-inch (7.9 mm) piping shall be n…
51-11C-51-11C-40404 Section C404.4—Heat traps.
1.0K chars
C404.4 Heat traps for hot water storage tanks. Storage tank-type water heaters and hot water storage tanks that have vertical water pipes connecting to the inlet and outlet of the tank shall be provided with integral heat traps at the vertical inlets and outlets or shall have pip…
51-11C-51-11C-40405 Section C404.5—Water heater installation.
0.3K chars
C404.5 Water heater installation. Electric water heaters in unconditioned spaces or on concrete floors shall be placed on an incompressible, insulated surface with a minimum thermal resistance of R-10.[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 R…
51-11C-51-11C-40406 Section C404.6—Pipe insulation.
3.4K chars
C404.6 Insulation of piping. Piping from a water heater to the termination of the heated water fixture supply pipe shall be insulated in accordance with Table C403.10.3. On both the inlet and outlet piping of a storage water heater or heated water storage tank, the piping to a he…
51-11C-51-11C-40407 Section C404.7—Heated-water circulating and temperature maintenance systems.
4.2K chars
C404.7 Heated-water circulating and heat trace temperature maintenance systems. Heated-water circulation systems for temperature maintenance shall be in accordance with Section C404.7.1. Electric resistance heat trace systems for temperature maintenance shall be in accordance wit…
51-11C-51-11C-40408 Section C404.8—Demand recirculation controls.
0.9K chars
C404.8 Demand recirculation controls.Demand recirculation water systems shall have controls that comply with both of the following:1. The controls shall start the pump upon receiving a signal from the action of a user of a fixture or appliance, sensing the presence of a user of a…
51-11C-51-11C-40409 Section C404.9—Domestic hot water meters.
1.0K chars
C404.9 Domestic hot water meters. Each individual dwelling unit in a Group R-2 occupancy with central service domestic hot water systems shall be provided with a domestic hot water meter to allow for domestic hot water billing based on actual domestic hot water usage.EXCEPTION:Dw…
51-11C-51-11C-404091 Section C404.10—Drain water heat recovery units.
0.4K chars
C404.10 Drain water heat recovery units. Drain water heat recovery units shall comply with CSA B55.2. Potable waterside pressure loss shall be less than 10 psi (69 kPa) at maximum design flow. For Group R occupancies, the efficiency of drain water heat recovery unit efficiency sh…
51-11C-51-11C-40410 Section C404.11—Pools and spas.
3.6K chars
C404.11 Energy consumption of pools and permanent spas. The energy consumption of pools and permanent spas shall be controlled by the requirements in Sections C404.11.1 through C404.11.4.C404.11.1 Heaters. Pool water heaters using electric resistance heating as the primary source…
51-11C-51-11C-40413 Section C404.13—Service water pressure-booster systems.
1.3K chars
C404.13 Servicewater pressure-booster systems. Service water pressure-booster systems shall be designed and configured such that the following apply:1. One or more pressure sensors shall be used to vary pump speed and/or start and stop pumps. The sensors shall either be located n…
51-11C-51-11C-40414 Section C404.14—Demand responsive water heating.
1.1K chars
C404.14 Demand responsive water heating. Electric storage water heaters with rated water storage volume between 40 and 120 gallons and a nameplate input rating equal to or less than 12kW shall be provided with demand responsive controls that comply with ANSI/CTA-2045-B Level 2 or…
51-11C-51-11C-40415 Section C404.15—Service water heating commissioning.
0.3K chars
C404.15 Commissioning. Service water heating systems shall be commissioned in accordance with Section C408.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40415, filed 7/1/22, 6/7/23…