51-11C-51-11C-40500 Section C405—Electrical power and lighting systems.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40500, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40501 Section C405.1—General.
2.3K chars
C405.1 General. Lighting system controls, the maximum lighting power for interior and exterior applications, electrical energy consumption, vertical and horizontal transportation systems, and minimum efficiencies for motors and transformers shall comply with this section.Sleeping…
51-11C-51-11C-40502 Section C405.2—Electrical power and lighting systems.
1.5K chars
C405.2 Lighting controls. Lighting systems shall be provided with controls that comply with one of the following:1. Lighting controls as specified in Sections C405.2.1 through C405.2.10.2. Luminaire-level lighting controls (LLLC) as specified in Section C405.2.8.1.EXCEPTION:Excep…
51-11C-51-11C-405021 Section C405.2.1—Occupant sensor controls.
5.8K chars
C405.2.1 Occupant sensor controls. Occupant sensor controls shall be installed to control luminaires in the space types listed in Table C405.2.1, and shall comply with the requirements listed in the table.EXCEPTIONS:1. Corridors in manufacturing facilities. 2. General lighting an…
51-11C-51-11C-405022 Section C405.2.2—Time switch controls.
2.9K chars
C405.2.2 Time switch controls. Each area of the building that is not provided with occupant sensor controls complying with Section C405.2.1.1 shall be provided with time switch controls complying with Section C405.2.2.1.EXCEPTIONS:1. Luminaires which are required to have specific…
51-11C-51-11C-405023 Section C405.2.3—Manual controls.
1.5K chars
C405.2.3 Manual controls. All lighting shall have manual controls complying with the following:1. They shall be in a location with ready access to occupants.2. They shall be located where the controlled lights are visible, or shall identify the area served by the lights and indic…
51-11C-51-11C-405024 Section C405.2.4—Light-reduction controls.
2.3K chars
C405.2.4 Light-reduction controls. Where not provided with occupant sensor controls complying with Section C405.2.1.1, general lighting shall be provided with light-reduction controls complying with Section C405.2.4.1.EXCEPTIONS:1. Luminaires controlled by daylight responsive con…
51-11C-51-11C-405025 Section C405.2.5—Daylight responsive controls.
9.7K chars
C405.2.5 Daylight responsive controls.Daylight responsive controls complying with Section C405.2.5.1 shall be provided to control the general lighting within daylight zones in the following spaces:1. Spaces with a total of more than 75 watts of general lighting within primary sid…
51-11C-51-11C-405026 Section C405.2.6—Additional lighting controls.
2.8K chars
C405.2.6 Additional lighting controls. Specific application lighting shall be provided with controls, in addition to controls required by other sections, for the following:1. The following lighting shall be controlled by an occupant sensor complying with Section C405.2.1.1 or a t…
51-11C-51-11C-405027 Section C405.2.7—Area controls.
1.0K chars
C405.2.7 Area controls. The maximum lighting power that may be controlled from a single switch or automatic control device shall not exceed that which is provided by a 20 ampere circuit loaded to not more than 80 percent. A master control may be installed provided the individual …
51-11C-51-11C-405028 Section C405.2.8—Advanced lighting controls.
4.2K chars
C405.2.8 Advanced lighting controls. Any contiguous open office area larger than 5,000 square feet shall have its general lighting controlled by either:1. Luminaire-level lighting controls (LLLC) conforming to the requirements of Section C405.2.8.1.2. Networked lighting control (…
51-11C-51-11C-405029 Section C405.2.9—Exterior lighting controls.
2.6K chars
C405.2.9 Exterior lighting controls. Exterior lighting systems shall be provided with controls that comply with Sections C405.2.9.1 through C405.2.9.4.EXCEPTIONS:1. Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, sec…
51-11C-51-11C-40503 Section C405.2.10—Parking garage lighting control.
1.9K chars
C405.2.10 Parking garage lighting control. Parking garage lighting shall be controlled by an occupant sensor complying with Section C405.2.1.1 or a time-switch control complying with Section C405.2.2.1. Additional lighting controls shall be provided as follows:1. Lighting power o…
51-11C-51-11C-405030 Section C405.3—Lighting for plant growth and maintenance.
0.8K chars
C405.3 Lighting for plant growth and maintenance. All permanently installed luminaires used for plant growth and maintenance shall have a photosynthetic photon efficacy measured at the lamp for luminaires with serviceable or removable lamps or at the luminaire for integrated, non…
51-11C-51-11C-40504 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40504, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40504, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40505 Section C405.4—Interior lighting power requirements.
0.7K chars
C405.4 Interior lighting power requirements. A building complies with this section if its total connected interior lighting power calculated under Section C405.4.1 is no greater than the interior lighting power allowance calculated under Section C405.4.2.[Statutory Authority: RCW…
51-11C-51-11C-405051 Section C405.4.1—Total connected interior lighting power.
4.4K chars
C405.4.1 Total connected interior lighting power. The total connected interior lighting power shall be determined in accordance with Equation 4-13.TCLP = [LVL + BLL + TRK + POE + Other](Equation 4-13)Where:TCLP = Total connected lighting power (watts).LVL = For luminaires with la…
51-11C-51-11C-405052 Section C405.4.2—Interior lighting power requirements.
4.8K chars
C405.4.2 Interior lighting power allowance. The total interior lighting power allowance (watts) for an entire building shall be determined according to Table C405.4.2(1) using the Building Area Method, or Table C405.4.2(2) using the Space-by-Space Method. The interior lighting po…
51-11C-51-11C-405053 Table C405.4.2(1)—Interior lighting power allowances—Building area method.
1.3K chars
Table C405.4.2(1)Interior Lighting Power Allowances—Building Area MethodBuilding Area TypeLPD(w/ft2)Automotive facility0.64Convention center0.64Court house0.79Dining: Bar lounge/leisure0.79Dining: Cafeteria/fast food0.72Dining: Family0.71Dormitory0.46Exercise center0.67Fire stati…
51-11C-51-11C-405054 Table C405.4.2(2)—Interior lighting power allowances—Space-by-space method.
7.0K chars
Table C405.4.2(2)Interior Lighting Power Allowances—Space-by-Space MethodCommon Space-by-Space Typesa,jLPD (w/ft2)Atrium - Less than 20 feet in height0.39Atrium - 20 to 40 feet in height0.48Atrium - Above 40 feet in height0.60Audience/seating area - Permanenti In an auditorium0.6…
51-11C-51-11C-40506 Section C405.5—Exterior lighting.
0.7K chars
C405.5 Exterior lighting power requirements. The total connected exterior lighting power calculated in accordance with Section C405.5.2 shall not be greater than the exterior lighting power allowance calculated in accordance with Section C405.5.3.[Statutory Authority: RCW 19.27A.…
51-11C-51-11C-405061 Section C405.5.1—Exterior building grounds lighting.
0.9K chars
C405.5.1 Exterior building grounds lighting. All exterior building grounds luminaires that operate at greater than 25 watts shall have a minimum efficacy of 100 lumens per watt.EXCEPTIONS:1. Luminaires controlled by a motion sensor. 2. Luminaires that qualify for one of the excep…
51-11C-51-11C-405062 Section C405.5.2—Exterior building lighting power.
3.3K chars
C405.5.2 Total connected exterior building lighting power. The total exterior connected lighting power shall be the total maximum rated wattage of all exterior lighting that is powered through the energy service for the building.EXCEPTION:Lighting used for the following applicati…
51-11C-51-11C-405063 Table C405.5.3(1)—Exterior lighting zones.
0.9K chars
Table C405.5.3(1)Exterior Lighting ZonesLighting ZoneDescription1Developed areas of national parks, state parks, forest land, and rural areas2Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial with limited nighttime use and res…
51-11C-51-11C-405064 Table C405.5.3(2)—Individual lighting power allowances for building exteriors.
3.1K chars
Table C405.5.3(2)Lighting Power Allowances for Building Exteriors Lighting Zones Zone 1Zone 2Zone 3Zone 4Base Site Allowance160 W280 W400 W560 WUncovered Parking AreasParking areas and drives0.015 W/ft20.026 W/ft20.037 W/ft20.052 W/ft2Building GroundsWalkways and ramps less than …
51-11C-51-11C-40507 Sections C405.6 and C405.7—Electrical energy consumption.
4.9K chars
C405.6 Electrical transformers. Low-voltage dry-type distribution electric transformers shall meet the minimum efficiency requirements of Table C405.6 as tested and rated in accordance with the test procedure listed in DOE 10 C.F.R. 431. The efficiency shall be verified through c…
51-11C-51-11C-40508 Section C405.8—Electric motors.
7.9K chars
C405.8 Electric motor efficiency. All electric motors, fractional or otherwise, shall meet the minimum efficiency requirements of Tables C405.8(1) through C405.8(4) when tested and rated in accordance with DOE 10 C.F.R. 431. The efficiency shall be verified through certification …
51-11C-51-11C-40509 Section C405.9—Vertical and horizontal transportation systems.
2.0K chars
C405.9 Vertical and horizontal transportation systems and equipment. Vertical and horizontal transportation systems and equipment shall comply with this section.C405.9.1 Elevator cabs. For the luminaires in each elevator cab, not including signals and displays, the sum of the lum…
51-11C-51-11C-40510 Section C405.10—Controlled receptacles.
3.1K chars
C405.10 Automatic receptacle control. The following shall have automatic receptacle control complying with Section C405.10.1:1. At least 50 percent of all 125V, 15- and 20-amp receptacles installed in enclosed offices, conference rooms, rooms used primarily for copy or print func…
51-11C-51-11C-40511 Section C405.11—Voltage drop.
1.1K chars
C405.11 Voltage drop. The total voltage drop across the combination of customer-owned service conductors, feeder conductors and branch circuit conductors shall not exceed five percent.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. …
51-11C-51-11C-40512 Section C405.12—Alternating current-output uninterruptible power supplies (AC-output UPS).
1.0K chars
AC-output UPS systems serving a computer room shall meet or exceed the calculation and testing requirements identified in ENERGY STAR Program Requirements for Uninterruptible Power Supplies (UPSs) – Eligibility Criteria Version 2.0.EXCEPTION:AC-output UPC that utilizes standardiz…
51-11C-51-11C-40513 Section C405.13—Electrical commissioning.
0.6K chars
C405.13 Commissioning. Controlled receptacles and lighting systems shall be commissioned in accordance with Section C408.[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40513, filed …
51-11C-51-11C-40600 Section C406—Efficiency and load management measures.
6.3K chars
C406.1 Additional energy efficiency and load management measures credit requirements. The project as defined in the building permit shall meet the following requirements as applicable:1. New buildings, changes in space conditioning category, change of occupancy group, and buildin…
51-11C-51-11C-40602 Reserved.
0.8K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40602, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.025, 19.27A.045 and chapter 19.27 RCW. WS…
51-11C-51-11C-40603 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40603, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.025, 19.27A.045 and chapter 19.27 RCW. WS…
51-11C-51-11C-40604 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40604, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40605 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40605, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40606 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40606, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.025, 19.27A.045 and chapter 19.27 RCW. WS…
51-11C-51-11C-40607 Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40607, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40608 Reserved.
0.8K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40608, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40609 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40609, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40610 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40610, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40611 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40611, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40612 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40612, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 1…
51-11C-51-11C-40620 Section C406.2—Additional energy efficiency credit measures.
8.7K chars
C406.2 Additional energy efficiency credit measures. Each energy efficiency credit measure used to meet credit requirements for the project shall include efficiency that is greater than the energy efficiency required for the building type and configuration requirements in Section…
51-11C-51-11C-40621 Section C406.2.1—Dwelling unit HVAC measures.
1.7K chars
C406.2.1 Dwelling unit HVAC controls. HVAC systems serving dwelling units or sleeping units shall be controlled with a programmable thermostat that is configured to automatically activate a setback condition of at least 5°F (3°C) for both heating and cooling. The programmable the…
51-11C-51-11C-40622 Section C406.2.2—HVAC measures.
12.4K chars
C406.2.2 More efficient HVAC system performance. All heating and cooling systems shall meet the minimum requirements of Section C403 and efficiency improvements shall be referenced to the minimum efficiency requirements listed in the tables in Section C403.3.2. Where multiple eff…
51-11C-51-11C-40623 Section C406.2.3—Lighting measures.
3.6K chars
C406.2.3 Reduced lighting power. Interior lighting within the whole project shall achieve credits by complying with Section C406.2.3.1 or C406.2.3.2. In Group R-1 and Group R-2 occupancies, dwelling and sleeping units shall comply with Section C406.2.3.3 and all other areas shall…
51-11C-51-11C-40624 Section C406.2.5—Renewable energy measures.
1.7K chars
C406.2.5 On-site and off-site renewable energy. Projects installing on-site or off-site renewable energy systems with a capacity of at least 0.1 watts per gross square foot (1.08 W/m2) of building area in addition to the renewable energy capacity required elsewhere in this code s…
51-11C-51-11C-40625 Section C406.2.6—Service water measures.
6.9K chars
C406.2.6 Reduced energy use in service water heating. Buildings with service hot water heating equipment that serves the whole building, building addition or tenant space shall achieve credits through compliance with:1. Section C406.2.6.1, C406.2.6.2, or C406.2.6.3.2. Sections C4…