51-11C-51-11C-40626 Section C406.2—Envelope measures.
1.0K chars
C406.2.12 Enhanced envelope performance. The Proposed Total UA of the thermal envelope of the project shall be 15 percent lower than the Allowable Total UA determined in accordance with Section C402.1.5 and Equation 4-2.C406.2.13 Reduced air leakage. Energy credits shall be achie…
51-11C-51-11C-40627 Section C406.2—Other measures.
4.0K chars
C406.2.14 Enhanced commercial kitchen equipment. For buildings or areas designated as Group A-2, or facilities whose primary business type involves the use of a commercial kitchen with at least one gas or electric fryer, all fryers, dishwashers, steam cookers and ovens shall comp…
51-11C-51-11C-40630 Section C406.3—Load management credits.
8.1K chars
C406.3 Load management credits. Load management measures installed in the building that meet the requirements in Sections C406.3.1 through C406.3.7 shall achieve the credits listed for the occupancy group in Table C406.3 or where calculations required by Sections C406.3.1 through…
51-11C-51-11C-40700 Section C407—Total building performance.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40700, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40701 Section C407.1—Scope.
0.7K chars
C407.1 Scope. This section establishes criteria for compliance using total building performance. All systems and loads shall be included in determining the total building performance including, but not limited to: Heating systems, cooling systems, service water heating, fan syste…
51-11C-51-11C-40702 Section C407.2—Mandatory requirements.
3.5K chars
C407.2 Mandatory requirements. Compliance with Section C407 also requires compliance with those sections shown in Table C407.2.The building permit application for projects utilizing this method shall include in one submittal all building and mechanical drawings and all informatio…
51-11C-51-11C-40703 Section C407.3—Performance-based compliance.
12.6K chars
C407.3 Performance-based compliance. Compliance with this section requires compliance with ASHRAE Standard 90.1 Appendix G, Performance Rating Method, in accordance with Standard 90.1 Section 4.2.1 with the following modifications:1. The mandatory requirements of the Washington S…
51-11C-51-11C-407031 Tables for Section C407.3.
0.8K chars
Table C407.3(1)ReservedTable C407.3(2)Building Performance Factors (BPF) to be used for Compliance with Section C407.3Building Area TypeBuilding Performance FactorMultifamily0.51Health care/hospital0.70Hotel/motel0.51Office0.44Restaurant0.33Retail0.41School0.35Warehouse0.18All ot…
51-11C-51-11C-40704 Section C407.4—Reserved.
0.3K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40704, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40704, filed 2/1/13, effe…
51-11C-51-11C-40705 Section C407.5—Reserved.
0.6K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40705, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40705, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-407051 Reserved.
0.8K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-407051, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter …
51-11C-51-11C-407052 Reserved.
0.7K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-407052, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.045, 19.27A.160, and 19.27.074. WSR 16-24-070, § 51-11C-407052, filed 12/6/16, effecti…
51-11C-51-11C-407053 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-407053, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-407053, filed 1/19/16, effective 7/1/16. S…
51-11C-51-11C-407054 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-407054, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-407054, filed 1/19/16, effective 7/1/16. S…
51-11C-51-11C-407055 Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-407055, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-407055, filed 1/19/16, effective 7/1/16. S…
51-11C-51-11C-40706 Section C407.6—Reserved.
0.4K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapter 19.27 RCW. WSR 19-24-040, § 51-11C-40706, filed 11/26/19, effective 7/1/20. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03-072, § 51-11C-40706, filed 1/19/16, effective 7/1/16. Sta…
51-11C-51-11C-40800 Section C408—System commissioning.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40800, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40801 Section C408.1—General.
9.2K chars
C408.1 General. A building commissioning process led by a certified commissioning professional and functional testing requirements shall be completed for mechanical systems in Section C403; service water heating systems in Section C404; controlled receptacle and lighting control …
51-11C-51-11C-408012 Figure C408.1.4.1—Commissioning compliance checklist.
3.3K chars
Figure C408.1.4.1Commissioning Compliance Checklist Project Name:Project InformationProject Address: Certified Commissioning Professional: Type of ISO Certification and Number:SupportingDocuments□Manuals, record documents and training have been completed or are scheduled (Section…
51-11C-51-11C-40802 Section C408.2—Mechanical systems commissioning.
3.6K chars
C408.2 Mechanical systems commissioning. Mechanical equipment and controls subject to Section C403 shall be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include all energy code requirements for which the code states t…
51-11C-51-11C-40803 Section C408.3—Service water heating systems commissioning.
1.6K chars
C408.3 Service water heating systems commissioning. Service water heating equipment and controls subject to Section C404 shall be included in the commissioning process required by Section C408.1. The commissioning process shall minimally include equipment and components installed…
51-11C-51-11C-40804 Section C408.4—Controlled receptacle and lighting control system commissioning.
1.7K chars
C408.4 Controlled receptacle and lighting control system commissioning. Controlled receptacles and lighting control systems subject to Section C405 shall be included in the commissioning process required by Section C408.1. The configuration and function of controlled receptacles …
51-11C-51-11C-408045 Section C408.5—Other systems commissioning.
0.8K chars
C408.5 Systems installed to meet Section C406 or C407. Equipment, components, controls or configuration settings for systems which are included in the project to comply with Section C406 or C407 shall be included in the commissioning process required by Section C408.1.C408.5.1 Sy…
51-11C-51-11C-40805 Section C408.6—Metering system commissioning.
1.4K chars
C408.6 Metering system commissioning. Energy metering systems required by Section C409 shall comply with Section C408.6 and be included in the commissioning process required by Section C408.1. The commissioning process shall include all energy metering equipment and controls requ…
51-11C-51-11C-40807 Section C408.7—Refrigeration system commissioning.
1.0K chars
C408.7 Refrigeration system commissioning. All installed refrigeration systems subject to Section C410 shall be included in the commissioning process required by Section C408.1.EXCEPTIONS:1. Self-contained refrigeration systems are exempt from the commissioning process. 2.Total i…
51-11C-51-11C-40900 Section C409—Energy metering and energy consumption management.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-40900, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-40901 Section C409.1—General.
2.9K chars
C409.1 General. All new buildings and additions shall have the capability of metering all source energy usage in accordance with Section C409.2 in addition to the source energy for on-site renewable energy production in accordance with Section C409.2.4 and the end-use energy usag…
51-11C-51-11C-40902 Section C409.2—Energy source metering.
2.1K chars
C409.2 Energy source metering. Buildings shall have a meter at each energy source. For each energy supply source listed in Section C409.2.1 through C409.2.4, meters shall collect data for the whole building or for each separately metered portion of the building where not exempted…
51-11C-51-11C-40903 Section C409.3—End-use metering.
6.1K chars
C409.3 End-use metering. Meters shall be provided to collect energy use data for each end-use category listed in Sections C409.3.1 through C409.3.7. These meters shall collect data for the whole building or for each separately metered portion of the building where not exempted by…
51-11C-51-11C-40904 Section C409.4—Measurement devices, data acquisition system and energy display.
3.4K chars
C409.4 Measurement devices, data acquisition system and energy display.C409.4.1 Meters. Meters and other measurement devices required by this section shall be configured to automatically communicate energy data to a data acquisition system and energy display. Source meters may be…
51-11C-51-11C-40905 Reserved.
0.5K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-40905, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. WSR 16-03…
51-11C-51-11C-41000 Section C410—Refrigeration system requirements.
16.8K chars
C410.1 General. Walk-in coolers, walk-in freezers, refrigerated warehouse coolers, refrigerated warehouse freezers, and refrigerated display cases shall comply with this Section.Table C410.2Minimum Efficiency Requirements: Commercial Refrigerators and Freezers and RefrigerationEq…
51-11C-51-11C-41100 Section C411—Renewable energy.
11.5K chars
C411.1 On-site renewable energy. Each new building or addition larger than 10,000 square feet of gross conditioned floor area shall include a renewable energy generation system consisting of not less than 0.5 W/ft2 or 1.7 Btu/ft2 multiplied by the sum of the gross conditioned flo…
51-11C-51-11C-41200 Section C412—Compressed air systems.
6.8K chars
C412.1 General. All new compressed air systems, and all additions or alterations of compressed air systems where the total combined horsepower (hp) of the compressor(s) is 25 hp or more, shall meet the requirements of this section. These requirements apply to the compressors, rel…
51-11C-51-11C-50000 Chapter 5 [CE]—Existing buildings.
5.5K chars
C501 General.C501.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing buildings and structures.C501.1.1 Existing buildings. Except as specified in this chapter, this code shall not be used to require the remov…
51-11C-51-11C-50200 Section C502—Additions.
5.8K chars
C502.1 General.Additions to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion of the existing building or building system to comply with this code. Addit…
51-11C-51-11C-50300 Section C503—Alterations.
31.7K chars
C503.1 General. Alterations to any building or structure shall comply with the requirements of Section C503 and the code for new construction. Alterations to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to ne…
51-11C-51-11C-50400 Section C504—Repairs.
1.5K chars
C504.1 General. Buildings and structures, and parts thereof, shall be repaired in compliance with Section C501.3 and this section. Work on nondamaged components that is necessary for the required repair of damaged components shall be considered part of the repair and shall not be…
51-11C-51-11C-50500 Section C505—Change of space conditioning, occupancy or use.
9.0K chars
C505.1 General. Buildings or spaces undergoing a change in space conditioning alteration shall comply with Sections C505.2 and C505.4. Buildings or spaces undergoing a change in occupancy alteration shall comply with Sections C505.3 and C505.4. Spaces changing from one use type t…
51-11C-51-11C-50600 Section C506—Metering for existing buildings.
1.1K chars
C506.1 Metering in existing buildings. Where new or replacement systems or equipment are installed in an existing building that was constructed subject to the requirements of this section, metering shall be provided for such new or replacement systems or equipment so that their e…
51-11C-51-11C-60000 Reserved.
0.3K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A, 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-60000, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24. Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05…
51-11C-51-11C-600000 Chapter 6 [CE]—Referenced standards.
19.1K chars
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that refe…
51-11C-51-11C-61000 Appendix A—Default heat loss coefficients.
0.2K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025, 19.27A.160 and chapters 19.27A and 19.27 RCW. WSR 22-14-091, 23-12-101, and 23-20-021, § 51-11C-61000, filed 7/1/22, 6/7/23, and 9/25/23, effective 3/15/24.]
51-11C-51-11C-61010 Section A101—General.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61010, filed 2/1/13, effective 7/1/13.]
51-11C-51-11C-61011 Section A101.1—Scope.
0.5K chars
A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the WSEC. This chapter includes tables of seasonal average heat loss coefficients for specified nominal insulation.[Statutory Authority: RCW 19.27A.025, 19.27A.160, and 19.27.074. …
51-11C-51-11C-61012 Section A101.2—Description.
0.5K chars
A101.2 Description. These coefficients were developed primarily from data and procedures from the ASHRAE Fundamentals Handbook.Coefficients not contained in this chapter may be computed using the procedures listed in this reference if the assumptions in the following sections are…
51-11C-51-11C-61013 Section A101.3—Air films.
0.4K chars
A101.3 Air films. Default R-values used for air films shall be as follows:R-ValueCondition0.17All exterior surfaces0.61Interior horizontal surfaces, heat flow up0.92Interior horizontal surfaces, heat flow down0.68Interior vertical surfaces[Statutory Authority: RCW 19.27A.020, 19.…
51-11C-51-11C-61014 Section A101.4—Compression of insulation.
1.0K chars
A101.4 Compression of insulation. Insulation which is compressed shall be rated in accordance with Table A101.4 or reduction in value may be calculated in accordance with the procedures in the ASHRAE Fundamentals Handbook.Table A101.4R-value of Fiberglass Batts Compressed Within …
51-11C-51-11C-61015 Section A101.5—Building materials.
3.2K chars
A101.5 Building materials. Default R-values used for building materials shall be as shown in Table A101.5.Table A101.5Default R-values for Building MaterialsMaterialNominal Size (in.)ActualSize (in.)R-Value(Heat Capacityc)Air cavity (unventilated), between metal studs at 16 inche…
51-11C-51-11C-61020 Section A102—Ceilings.
0.1K chars
[Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. WSR 13-04-056, § 51-11C-61020, filed 2/1/13, effective 7/1/13.]